12
Scheme of connecting servo drive
Belimo BE 230-12
Technical data
BE 230, BE 230-12
Nominal voltage
AC230V 50/60 Hz
Nominal voltage range
AC198 – 264 V
For wire sizing
15 VA (lmax. 7.9A @ 5 ms)
Power consumption
- motoring
8W
- holding
0,5W
Connection cable
- motor
lead 1 m, 3 x 0.75 mm
2
(halogen-free)
- auxiliary switch
lead 1 m, 6 x 0.75 mm
2
(halogen-free)
Auxiliary switch
2x EPU 6(3)A,AC 250V
K
- switching points
3
o
/87
o
(referred to 0 –90
o
)
- tolerance
±2
o
Angle of rotation
100
o
(incl. 5
o
mechanical overrun on each side)
Torque (nominal torque)
40 Nm
Blocking torque
- dynamic
40 Nm
- steady-state
50 Nm
Direction of rotation
Selected by mounting L/R
Damper stem
form-fit 14x14mm form-fit 12x12 mm
Running time
<60s for 90
o
Sound power level
max. 62dB(A)
Service life
At least 10’000 cycles
Position indication
Mechanical with pointer
Protection class
II (totally insulated)
Degree of protection
IP54
Ambient temperature range
- normal duty
-30
o
– +50
o
C
- crash case
see text/graph crash case
Non-operating temperature
-40 ... +80
o
C
Ambient humidity range
According to EN 60335-1
Mode of operation
type 1.C (EN 60730)
EMV low-voltage directive
CE according to 89/336/EWG, 92/31/EWG, 93/68/EWG
Maintenance
maintenance-free
Weight
appr. 2.7 kg
Содержание PKI-C EI120S
Страница 1: ...www systemair com Systemair Fire damper...
Страница 21: ...Declaration of conformity...
Страница 37: ...PVM Fire air grilles www systemair com Systemair Fire damper...
Страница 45: ...DKI Smoke dampers www systemair com Systemair Fire damper...
Страница 53: ...10 Scheme of principle of BKSE 24 6 example...
Страница 62: ......