![SystemAir PAW-200W5APAC Скачать руководство пользователя страница 22](http://html.mh-extra.com/html/systemair/paw-200w5apac/paw-200w5apac_installation-and-maintenance-manual_1423363022.webp)
20
5 - Start-up
4. Select the "Set data" by pressing the
or
button.
select one of the "Set data" by pressing the
or
button. then press the
button. (refer to the next table for
the parameters' value)
5. Select the "unit no." by pressing the
or
button and
press the
button. The "Exit detailed settings and restart?"
(Detailed setting-end) screen appears on the LCD display.
Select "Yes" and press the
button.
Insert the following parameters in the exact orders:
Model Configuration
DN
PAW-
200W5APAC
PAW-
250W5APAC
Initial parameters (set at shipment)
Type
10
31(WE2)
31(WE2)
Indoor unit capacity
11
21 (22.4)
23 (25.0)
Heating intake temperature shift
06
00 (none)
00 (none)
Demand setting
0B
01 (O2)
01 (O2)
Heating preparation display
0C
01 (none)
01 (none)
Cool/heat auto
0D
01 (invalid)
01 (invalid)
Sensor valid
15
31 (all)
31 (all)
Air speed
16
00 (none)
00 (none)
Cooling Upper limit
1F
15 (15°C)
15 (15°C)
Cooling Lower limit
20
05 (5°C)
05 (5°C)
Heating Upper limit
21
55 (55°C)
55 (55°C)
Heating Lower limit
22
35 (35°C)
35 (35°C)
Power shut down auto ON
28
01 (valid)
01 (valid)
Indoor unit electronic control valve
2C
6 (none)
6 (none)
Operation mode
2D
10 (C/H)
10 (C/H)
Commissioning settings
On the outdoor unit operating with WHE, always set the following
parameters during commissioning*
5.3
Test run procedure
YES
YES
YES
NO
NO
NO
Check the combination (wiring) of indoor and outdoor units.
Is system “single-type”?
(1 indoor unit is connected to 1 outdoor unit
and remote controller)
Is group control with
multiple outdoor units used?
Turn ON the indoor and outdoor power.
Indicate (mark) the combination number.
Automatic address
Set the remote controller to “test run”.
Can
operation be
started?
Return the remote controller to normal control.
Turn ON the indoor
and outdoor power.
(Automatic
Address)
Setting the Outdoor
Unit System Address
Set the outdoor
unit system address.
Automatic Address Settin g
Use the remote controller
to perform automatic
address setting.
See “Contents of Remote
Controller Switch Alarm Display”
to check the system.
Note:
(*1) Required for simultaneous-operation
multi systems and for group control.
(*1)
Test run using remote controller
1. Keep pressing the
,
and
buttons
simultaneously for 4 or more seconds. the "maintenance func"
screen appears on the LCD display.
2. Press the
or
button to see each menu. if you
wish to see the next screen instantly, press the
or
button. Select "4. Test run" on the LCD display and press the
button.
Change the display from OFF to ON by pressing the
or
button. Then press the
button.
Model Configuration
DN
PAW-
200W5APAC
PAW-
250W5APAC
On the Outdoor unit operating with WHE, set the following parameters
Condensing Temperature lower limit
35
0 (46°C)
0 (46°C)
Condensing Temperature upper limit
36
0 (50°C)
0 (50°C)
High pressure setting for PS
4B 1 (4.15 Mpa) 1 (4.15 Mpa)
* RTC-2 or RTC-4 remote controllers are required for these settings