NTC - IR2
GB - 6
Configuration menu
Item 4- - Item 5-:
The user desired temperature can be set through buttons F or D.
Temperature increase or decrease starts from the factory-set value
of 22C (72F).
Each time button F or D is pressed, temperature is increased or
decreased by ±0.5 degrees (or ±1F).
In this case the temperature range is between 20 C and 24C (68F
to 76F).
In any case, the user can increase this temperature range by
changing item 4 and 5 values.
Item 4 is the starting temperature and item 5 is the value to be
assigned each time button F or D is pressed.
There follow some examples according to the scale range required
(we suggest changing item 5 ONLY):
Configuration menu – Supplement
Item 5 = 2C (4F)
Minimum temp. = 14C (56F) —> automatically set at 15C (59F)
Maximum temp. = 30C (88F)
Item 5 = 1.5C (3F)
Minimum temp. = 16C (60F)
Maximum temp. = 28C (84F)
Item 5 = 1C (2F)
Minimum temp. = 18C (64F)
Maximum temp. = 26C (80F)
The user can also set the value of item 4 so that no temperature
increase or decrease can change it when button F or D is pressed.
To do so, set the desired fixed temperature value in item 4 and set
0C (0F) in item 5.
Anyway, the desired maximum temperature value is 32C (90F).
9-
Lights groups available
0
1
...
4
5
There is no lights/groups to control: no icons
will be displayed
Just one lights group is available: “1” group icons
will not be illuminated
...
Four lights groups are available: “Lamp” and “4”
groups icons will be illuminated
There is no group, but user can manage the light
[Defaults: “0” Lights control disabled.]
YES: Once the Lights Menu
is selected, the groups icon
will be energized on the lcd
(no icons if just one group is
selected)
“A” and “1” icons are
energized in the light
menu.User can manage
all lights or just one
10-
Louver presence
No
Ye
Some units doesn’t have the louver installed. This item
consents to don’t show the louver icon on the LCD
None
Louver installed (Stepper motor or
Synchronous motor + home position)
[Defaults: “No” No louver presence.]
YES
If the unit has the louver,
this icon will be activated
This icon will show on
the LCD the functioning
of the louver
11-
Unit's remote ID
A
1
2
3
...
7
Unit remote ID ALL
Unit remote ID 1
Unit remote ID 2
Unit remote ID 3
...
Unit remote ID 7
[Defaults: “A” All]
YES
12-
YES
In both Occupied or
Unoccupied mode:
The temperature icon will
be hidden
Light and Blind icons will
appear just if selected
HVAC system
Ye
No
Some application needs to manage just the power
module, without any other system linked
An HVAC system is present
An HVAC system is NOT present
[Default: “Ye”: HVAC system is present]
NTC - IR2
GB - 6
Configuration menu
Item 4- - Item 5-:
The user desired temperature can be set through buttons F or D.
Temperature increase or decrease starts from the factory-set value
of 22C (72F).
Each time button F or D is pressed, temperature is increased or
decreased by ±0.5 degrees (or ±1F).
In this case the temperature range is between 20 C and 24C (68F
to 76F).
In any case, the user can increase this temperature range by
changing item 4 and 5 values.
Item 4 is the starting temperature and item 5 is the value to be
assigned each time button F or D is pressed.
There follow some examples according to the scale range required
(we suggest changing item 5 ONLY):
Configuration menu – Supplement
Item 5 = 2C (4F)
Minimum temp. = 14C (56F) —> automatically set at 15C (59F)
Maximum temp. = 30C (88F)
Item 5 = 1.5C (3F)
Minimum temp. = 16C (60F)
Maximum temp. = 28C (84F)
Item 5 = 1C (2F)
Minimum temp. = 18C (64F)
Maximum temp. = 26C (80F)
The user can also set the value of item 4 so that no temperature
increase or decrease can change it when button F or D is pressed.
To do so, set the desired fixed temperature value in item 4 and set
0C (0F) in item 5.
Anyway, the desired maximum temperature value is 32C (90F).
9-
Lights groups available
0
1
...
4
5
There is no lights/groups to control: no icons
will be displayed
Just one lights group is available: “1” group icons
will not be illuminated
...
Four lights groups are available: “Lamp” and “4”
groups icons will be illuminated
There is no group, but user can manage the light
[Defaults: “0” Lights control disabled.]
YES: Once the Lights Menu
is selected, the groups icon
will be energized on the lcd
(no icons if just one group is
selected)
“A” and “1” icons are
energized in the light
menu.User can manage
all lights or just one
10-
Louver presence
No
Ye
Some units doesn’t have the louver installed. This item
consents to don’t show the louver icon on the LCD
None
Louver installed (Stepper motor or
Synchronous motor + home position)
[Defaults: “No” No louver presence.]
YES
If the unit has the louver,
this icon will be activated
This icon will show on
the LCD the functioning
of the louver
11-
Unit's remote ID
A
1
2
3
...
7
Unit remote ID ALL
Unit remote ID 1
Unit remote ID 2
Unit remote ID 3
...
Unit remote ID 7
[Defaults: “A” All]
YES
12-
YES
In both Occupied or
Unoccupied mode:
The temperature icon will
be hidden
Light and Blind icons will
appear just if selected
HVAC system
Ye
No
Some application needs to manage just the power
module, without any other system linked
An HVAC system is present
An HVAC system is NOT present
[Default: “Ye”: HVAC system is present]
IRC
GB
Содержание IRC
Страница 11: ...NTC IR2 I 2 Dimensioni mm 28 61 181 63 2 5 32 8 77 2 85 7 87 A Sostegno a parete Telecomando IRC I ...
Страница 18: ...NTC IR2 F 2 Dimension mm 28 61 181 63 2 5 32 8 77 2 85 7 87 A Support mural Télécommande IRC F ...
Страница 25: ...NTC IR2 D 2 Abmessungen mm 28 61 181 63 2 5 32 8 77 2 85 7 87 A Wandhalterung Fernbedienung IRC D ...
Страница 32: ...NTC IR2 E 2 28 61 181 63 2 5 32 8 77 2 85 7 87 A Soporte de pared Mando a distancia Dimensiones mm IRC E ...
Страница 39: ...NTC IR2 NL 2 28 61 181 63 2 5 32 8 77 2 85 7 87 A Wandsteun Afstandsbediening Afmetingen mm IRC NL ...
Страница 45: ... K GR 1 NTC IR2 mm 2 3 4 4 5 6 6 7 IR2 IR2 IRC IRC IRC ΕΛΛHNIKA GR 1 ...
Страница 46: ...NTC IR2 GR 2 28 61 181 63 2 5 32 8 77 2 85 7 87 A mm IRC GR ...
Страница 48: ...NTC IR2 GR 4 beep M V V 25 mm 0 984 in 5 mm 0 196 in IRC GR ...
Страница 53: ...NTC IR2 P 2 28 61 181 63 2 5 32 8 77 2 85 7 87 A Suporte de parede Controlo remoto Aspecto e ecrã IRC P ...
Страница 60: ...NTC IR2 S 2 28 61 181 63 2 5 32 8 77 2 85 7 87 A Vägghållare Fjärrkontroll Mått mm IRC S ...
Страница 67: ...NTC IR2 FIN 2 28 61 181 63 2 5 32 8 77 2 85 7 87 A Seinäteline Kaukosäädin Mitat mm IRC FIN ...