65/70 |
FDS...EX
Electrical connections
Type of activation H0-EX
IMPORTANT: Fire damper must be grounded. Wires connecting damper parts, must not be removed
This type of activation mechanism does not have any electrical equipment.
Type of activation H2-EX
IMPORTANT: Risk of electric shock!
Each explosion-proof electrical equipment installed in or on the fire damper must conform to its explosion-proof given
explosive atmospheres according to EN 60079-10.
Fire damper must be grounded. Wires connecting damper parts must not be removed
Switch off the power supply before working on any electrical equipment.
Only qualified electricians are allowed to work on the electrical system.
Microswitch:
Power Supply: AC 125/250 V or DC 12/24 VElectrical Parameters: 3A
NOTES:
• Supply via safety isolation transformer.
• Power consumption must be observed!
Legend
1
Grey cable colour
2
Orange cable colour
3
Pink cable colour
4
White cable colour
5
Red cable colour
6
Brown cable colour (Do not use for type of activation H2-EX)
X:7
Blue cable colour (Do not use for type of activation H2-EX)
Содержание FDS-3G EX Series
Страница 1: ...FDS EX Atex Fire Damper ...
Страница 8: ...8 70 FDS EX Product parts ...
Страница 27: ...27 70 FDS EX ...
Страница 30: ...30 70 FDS EX ...
Страница 31: ...31 70 FDS EX ...
Страница 35: ...35 70 FDS EX ...
Страница 36: ...36 70 FDS EX ...
Страница 39: ...39 70 FDS EX ...
Страница 40: ...40 70 FDS EX ...
Страница 43: ...43 70 FDS EX 5 1 On Out FDS EI90S EX W 1600 H 1000 EI 90 ve i o S a b ...
Страница 44: ...44 70 FDS EX ...
Страница 48: ...48 70 FDS EX ...
Страница 49: ...49 70 FDS EX ...
Страница 52: ...52 70 FDS EX ...
Страница 53: ...53 70 FDS EX ...
Страница 57: ...57 70 FDS EX 5 4 On Out FDS 3G EX 100 100 1200 800 EI 60 ve i o S a b ...
Страница 58: ...58 70 FDS EX ...
Страница 59: ...59 70 FDS EX ...
Страница 63: ...63 70 FDS EX 7 Multi FDS EI90S EX W 1600 H 1000 EI 90 ve i o S b ...
Страница 70: ...Systemair DESIGN 2021 04 27 Handbook_FDS_EX_en GB ...