GB

Design

The DXRE is used for central cooling of the ventilation air in a 

ventilation system. DXRE can also be used with a outdoor unit 

and it´s controller which switches between heat and cold. DXRE 

has a coil of copper tubes and hydrophilic coated aluminium fins. 

The stainless steel drip tray leans towards the drain connection. 

Same model for left-hand or right-hand installation.

Mounting ventilation duct

The fitting must be done so that the drip tray, droplet eliminator 

and condensate outlet are easily removable and the coil accessible 

for cleaning (see also under Cleaning).

DXRE can be installed either upstream or downstream of the fan 

unit in a horizontal duct, and it´s either bolted to the duct system 

or connected by means of slip clamps. When fitted downstream 

of the fan, it should be installed so that the airflow across the coil 

will be uniform. We recommend that the distance to or from a 

duct bend, fan, damper, etc. should be at least the same as the 

diagonal dimension of the duct.

In order to ensure maximum cooling capacity and reliable opera-

tion, it is inadvisable to install it immediately downstream of the 

fan outlet or a duct bend.

When installed upstream of the fan, check that the fan motor and 

other components are suitable for the humid air downstream of 

the cooler. Max. air velocity without droplet eliminator: 2.5 m/s 

when used as cooler.

The G ½” condensate outlet should be connected across a water 

trap in order to prevent air leakage.

N.B. The size of the outlet should be determined so that no stag-

nant water will remain in the drip tray.

An efficient air filter is recommended for the system.

When used as a cooler, DXRE and the ducts carrying cooled air, 

must be insulated so that no condensate will form on the outside.

Connection of refrigerant circuit

Installation must be preformed by a certified refrigerant techni-

can. The connection is made by soldering or press fittings that are 

approved for the purpose. Use nitrogen inside the copper tubes to 

avoid oxidation during soldering.

Make sure that DXRE connections are not subjected to expansion

forces in the system or to the deadweight of the pipe system. 

Make sure that the gaskets are not subjected to excessive heat dur-

ing brazing.

Design data

Max. operating pressure: 4.29 MPa (42,9 bar).  

Test pressure: 4.8 MPa (48 bar).

All coils are pressure tested and tested for leakage. On delivery, 

the coil is pressurised with dry air.

 

Capacity heat-cooling

Calculation of heating and cooling capacity is done via our web-

based calculation program, or get in touch with our sales division 

for assistance.

To fit the droplet eliminator

Droplet eliminator DE must be installed downstream of the cool-

ing coil in the duct cooler.

Fitting is done according to seperate instruction.

Connection refrigerant

DXRE 400x200-3-2,5

Gas

Liquid

Gas

DXRE 500x250-3-2,5 - 

DXRE 1200x600-3-2,5

Liquid

Содержание DXRE

Страница 1: ...with a outdoor unit and it s controller which switches between heat and cold IMPORTANT Read these instructions before installation connection and putting the product into use Save the instructions for...

Страница 2: ...aren Max lufthastighet utan droppavskiljare r 2 5m s vid kyldrift Kondensvattenavloppet G ansluts via ett vattenl s f r att undvika luftl ckage OBS Avloppets storlek skall dimensione ras s att vatten...

Страница 3: ...oppssidan Var f rsiktig s att lamellkanterna inte deformeras Reng r droppl dans botten och kontrollera att kondensavloppet r fritt fr n smuts Montera d refter tillbaka eventuell droppavskiljare med lu...

Страница 4: ...plet eliminator 2 5 m s when used as cooler The G condensate outlet should be connected across a water trap in order to prevent air leakage N B The size of the outlet should be determined so that no s...

Страница 5: ...the dirt away in a direction away from the air outlet side and towards the inlet side Take care not to deform the edges of the fins Clean the bottom of the drip tray and check that no dirt is lodged i...

Страница 6: ...hte Luft hinter dem K hler geeignet sind Bei K hlbetrieb betr gt die max Luftgeschwindigkeit ohne Tropfabscheider 2 5m s Der Kondenswasserauslass G wird ber einen Ge ruchverschluss angeschlossen um zu...

Страница 7: ...nn der gesamter W rmetauscher mit tels Druckluft oder Staubsaugen gereinigt werden Den Schmutz von der Luftaustrittsseite in Richtung Eintrittsseite blasen Hierbei vorsichtig vorgehen damit die Lamell...

Страница 8: ...8 DXRE RU DXRE DXRE DXRE 2 5 G DXRE 4 29 M a 42 9 4 8 M a 48 DXRE 2 DE DXRE 400x200 3 2 5 DXRE 500x250 3 2 5 DXRE 1200x600 3 2 5...

Страница 9: ...0 DXRE 600x300 3 2 5 638 338 56 70 40 85 165 67 5 8 3 8 1 7 16 2 DE 60x30 DXRE 600x350 3 2 5 638 388 56 70 40 85 165 67 5 8 3 8 1 9 17 4 DE 60x35 DXRE 700x400 3 2 5 738 438 56 70 40 85 165 67 5 8 3 8...

Страница 10: ...10 DXRE...

Страница 11: ...11 DXRE...

Страница 12: ...Systemair reservs the right to make changes and improvment to the contents without prior notice 12 Systemair AB Industriv gen 3 SE 739 30 Skinnskatteberg Phone 46 222 440 00 Fax 46 222 440 99...

Отзывы: