Sophomore Series 4000 & 5000 Cabinet - Classroom Air Handler - Owner's Manual - Installation, Operation, and Service Instructions
5.5 Figure 11 |
General Wall Sleeves Visual Assembly
5.6 Rear Standoff (RSO)
Installation Note:
When the classroom air handler is fitted with a rear standoff (RSO) or rear plenum assembly (RPA) it becomes
necessary to fasten the unit to the wall by using a 2” x 2” x 34” 18ga. angle brace (supplied by others), that must be secured to
the top cover of the RSO assembly as described below.
We recommend the use of ¾” x #10 round head self-tapping sheet metal screws to fasten the accessories to the unit.
Care should be taken to protect the painted finish when handling the unit and accessories.
1.
On a clean, flat, unobstructed floor surface, lay out the pieces of the standoff relative to the positions they are to be installed,
shown in the Installation/Assembly Drawings sent with the unit.
2.
Clamp the angle brace so it is flush to the top, back edge of top cover. Fasten the angle brace with four evenly spaced
screws. (This will be used at a later step to fasten the air handler to the wall.)
5.4 Exterior Louver
The exterior louver is supplied with the unit and should slide into the wall sleeve from the outside of the building. Fasten to the
wall through the standard 2” flange. Refer to Information Package and installation diagrams shipped with the unit. (screws not
provided)
NOTE:
Two condensate drain lines exit through the back of the unit and are supported by the exterior louver.
You may require an assistant's help for this procedure.
Fig. 11
General Wall Sleeves Visual Assembly