10.3.2 Damage to the fan
HAZARD
Hazard of explosion of an ignition-capable gas/air atmosphere!
›
Repair or replacement of the fan parts is expressly not allowed with EX-examined products.
"
In all cases of damage (e.g. coil damage), get in touch with our service department. Defective EX fans must be
completely replaced. Repairs may only be done on the manufacturer‘s premises and by the manufacturer. You will
find the address on the back of these operating instructions.
Failure to comply means a loss of ATEX admission.
10.4 Accessories
When ordering accessories, state the type designation of your EX fan. You will find it on the name plate.
Accessories
10.5
Faults and troubleshooting
Fault
Possible causes
Remedy
EX fan does not run smoothly
Rotor imbalance
Re-balancing by specialist company
Adhesions to the rotor
Clean carefully, rebalance if necessary
Material decomposition on the rotor due
to aggressive material conveyed
Contact the manufacturer
Deformation of rotor due to excessive
temperature
Contact manufacturer, install new rotor,
check bearings
Output of X fan too low
Wrong direction of rotation of rotor
Change direction of rotation
Loss of pressure in lines too high
Different line guidance
Throttle organs not or only partly open
Check opening position on site
Intake or pressure paths blocked
Remove obstacles
Grinding sounds in operation
or start of the Ex fan
Intake line installed twisted.
Loosen intake line and realign.
Thermo-contacts have
reacted
Minimum pressure does not exist
Check whether the minimum pressure
on the name plate can be reached by the
system
Capacitor not or not correctly connected
Connect capacitor
One or more phases not connected
Connect all three phases on fan.
Motor blocked
Contact manufacturer
Ex fan does not reach nominal
speed
Electrical switching devices set wrongly Check and possibly reset setting of swit-
ching device
Motor coil defective
Contact manufacturer
Drive motor has been designed wrongly
Contact manufacturer for check of start
torque
Current or consumption too
high
Minimum pressure does not exist
Check whether the minimum pressure
on the name plate can be reached by the
system
Rotor is mechanically decelerated
Check and remedy fault
Y or D switching dependent on the vol-
tage stated on the motor
Check circuitry with the circuit diagram
Table 12: Troubleshooting
Maintenance/troubleshooting
66