WARNING
Danger from falling parts!
›
Check the underground (ceiling/wall) for strength before assembly,
›
when selecting the fitting material, pay attention to the weight, vibration tendency and shearing
forces (weight, see name plate).
"
Fit the fan on a firm base with suitable fitting material
"
Prepare the fan with hinged frame for connection and secure (see Fig. 9 A, B, C)
–
Close the fan carefully, do not drop it.
–
Secure it with an M 6x10 screw (2 screws from size 450 upwards).
–
Secure the two flaps by means of an M 8x16 screw. They also act as protection against shutting.
"
Fit the air connection lines and the accessories.
NOTE
The channel installation must be such that protection class IP 20 (contact distance rotating part < 12
mm) is fulfilled on the admission side and protection class IP 10 (contact distance rotating part < 50
mm) can be guaranteed on the blow-out side.
6.4.2.1 Securing the hinged frame
"
If a hinged frame is used, secure the DVEX fan as shown in Fig. 9.
•
M8x16
M8x16
M6x10
A
B
C
Fig. 9:
Secure DVEX fan
7
Electrical connection
NOTE
›
The safety information in Section 7.1 applies to all the fans described in these operating instructions.
›
The fans may only be installed if the explosion-protected area has been classified according to DIN EN
60079-10 and the Operational Safety Ordinance.
Electrical connection
58