9
Operation
9.1
Safety information
HAZARD
Hazard of explosion of an ignition-capable gas/air atmosphere!
When commissioning the EX fan, the fundamental information from BGR 104 (explosion protection rules
of the employers‘ insurance schemes) and BGR 132 (avoidance of risk of ignition as a result of electro-
static charges) must be known.
Do not open or tip the fan if an explosive atmosphere exists.
WARNING
Risk from electrical voltage!
›
The device may only be operated by people who have been instructed about function and risks, have
understood them and are in a position to act accordingly.
›
Make sure that children do not operate the device without supervision or play with it.
›
Make sure that only people who are in a position to operate the device safely have access to it.
9.2
Operating conditions
•
During operation, touching the rotor must be impossible.
•
Safety components may not be circumvented or put out of function.
•
Only operate the EX fan within the limits stated on the name plate.
•
Intake of foreign bodies can destroy the fan.
•
Switching frequency:
–
The EX fan has been admitted for S1 continuous operation.
–
Controls may not permit any external switching operations!
•
Sound development can be reduced by the use of a noise filter
.
Fans in the external area:
In long periods of standstill of the fans, condensation may form in the motor.
"
Therefore ensure a regular switch-on time of 2 hours per week.
9.3
Operation/use
"
Switching on, see Commissioning
"
Only operate the EX fans in compliance with these operating instructions and the instructions for use of the motor.
"
Monitor the EX fans for correct function during operation.
"
Switch the EX fans off as planned.
WARNING
Risk from electrical voltage or risk of bursting!
Faults occurring can lead to personal and/or property damage.
Switch the EX fan off immediately:
›
in untypical running noises, oscillations, fluctuations in pressure,
›
if the figures for current, voltage and temperature are exceeded (name plate).
Operation
63