ARGUS-RC-H

3

Settings

Control state

Argus-RC-H has control state: Heating and cooling in sequence. The 

change-over function can be activated, see below.

Change-over function

Argus-RC-H has an input for change-over that automatically resets 

the output UO1 to operate with heating or cooling function. The input 

can be connected to sensors of type PT1000 and have the sensor 

mounted so that it senses the temperature on the supply pipe to the 

coil. 

When the temperature exceeds 22°C, the output function is set to 

heating and when the temperature drops below 18°C, the output is 

set to cooling. 

As an alternative, a potential-free contact can be used. When the con-

tact is open the controller works with the heating function and when it 

is closed, with the cooling function. 

To ensure satisfactory functioning using sensor, the system must 

have continuous primary circuit circulation. When the change-over 

function is not used, the input must be left disconnected.

Operating mode

There are three different operating modes. Switching between these 

modes is performed locally.

Stand-by:

 Both heating and cooling are disconnected within a tempe-

rature interval around the applicable setpoint (heating setpoint value 

- 3°C, cooling se 3°C).

Occupied:

 The room temperature is controlled according to the appli-

cable cooling setpoint (24°C) or heating setpoint (22°C). 

Bypass:

 Is controlled by the occupancy detector or other digital 

contact connected to the controller, closing activates Bypass. Control 

of the room temperature in the same way as Occupied mode. Bypass 

also controls forced ventilation. Reset to Preset operating mode occurs 

after 10 minutes of non-occupancy (no signal from presence detector).

Preset operating mode

Occupied is the preset operating mode. It can be set to Stand-by with 

DIP-switch SW3. See table 3 above. 

Occupancy detector

An occupancy detector is connected for local control of the operating 

mode between Preset operating mode and Bypass.

Open window

Heating and cooling are disconnected.

Setpoint

The setpoint can be adjusted l/-3°C from the back of the  
electronics cassette with a small screwdriver.

In Occupied mode, the controller operates from a heating setpoint 

i

Läs denna instruktion innan produkten 

monteras och ansluts

INSTRUKTION

 

ARGUS-RC-H

Rumsregulator

Argus-RC-H är en rumsregulator i Argus-serien avsedd att styra 
värme och kyla i efterbehandlingssystem. Montage sker direkt på 
vägg eller eldosa. Regulatorn har ej kommunikationsanslutning. 

Tekniska data

Matningsspänning  

18...30 V AC, 50...60 Hz

Egenförbrukning   

2,5 VA

Omgivningstemperatur 

0...50°C 

Omgivande luftfuktighet 

Max 90% RH 

Lagringstemperatur 

-20...+70°C

Inbyggd temperaturgivare  Typ NTC, mätområde 0...50°C,  

 

 

 

mätnoggr/-0,5°C vid 15...30°C

Ingångar och utgångar 

Se inkopplingsbilder och tabell nedan

Anslutningsplintar   

Av hisstyp för kabelarea max 2,1 mm

2

Skyddsklass 

 

IP20

Material hölje 

 

Polycarbonat, PC

Vikt 

 

110 g 

Mått 

 

95 x 95 x 28 mm

Installation

Montera regulatorn på en plats med för rummet representativ tem-
peratur. Lämplig placering är ca 1,6 m över golvet, utan omgivande 
hinder för luftcirkulation. Ta av ramen genom att trycka in låshaken i 
nederkanten av kåpan med en skruvmejsel. Se figur 1. 
Plocka därefter ur elektronikkassetten med hjälp av de fyra demonter-
ingshålen genom att bända mejseln mot kanten på bottenplattan. Se 
figur 2. 

OBS! 

Var försiktig så att du inte kommer åt elektroniken när 

du sticker in mejseln i demonteringshålen. 

Figur 1

Figur 2

(22°C), or a cooling setpoint (24°C) that can be changed locally using the 
DIP switches and local setpoint displacement.
Switching between heating and cooling setpoints is done automatically 
in the controller depending on the heating and cooling requirement. The 
controller's control setpoint is the same as the current setpoint plus/minus 
the local setpoint displacement.

Frost protection

Independent of the operating mode, the heating control is forced on when 
the room temperature drops below 8°C. Return to normal control occurs 
automatically when the room temperature exceeds 8°C.

Condensation detector

If there is condensation, the cooling control is blocked. Return to normal 
control occurs automatically when condensation ceases. 

Choice of actuator

The output function can be set to NO or NC for thermal actuators  
via DIP-switch SW8. The function only applies to UO1.

EMC emission and immunity standard

The product fulfills the demands for the current European EMC-standard 
CENELEC EN61000-6-1 and EN61000-6-3, and is CE-marked.

LVD, Low Voltage Directive

The product fulfills the demands for the current European LVD-standard IEC 
60 730-1.

Contact

Systemair AB, 739 39 Skinnskatteberg, Sweden 
Tel: +46 222 440 00, Fax: +46 222 440 99 
www.systemair.com, [email protected]

SV

Содержание ARGUS-RC-H

Страница 1: ...ur rectangular screwdri ver slots and levering against the edge of the bottom plate See figure 2 Note Take care not to damage the electronics when inserting the screw driver into the slots Figure 1 Fi...

Страница 2: ...l free contact A potential free contact is connected between terminals 31 and 41 AGnd 32 DI1 Occupancy detector A potential free contact is connected between terminals 32 and 40 C Closed contact corre...

Страница 3: ...ON ARGUS RC H Rumsregulator Argus RC H r en rumsregulator i Argus serien avsedd att styra v rme och kyla i efterbehandlingssystem Montage sker direkt p v gg eller eldosa Regulatorn har ej kommunikatio...

Страница 4: ...1 Utstyrning v rme FI eller kyla via change over F r 0 10 V DC ventilst lldon max 5 mA FI Ventilst lldonets 0 10 V styrsignalplint ansluts till plint 23 och dess matningsplintar till plint 10 och 11 N...

Страница 5: ...H har ing ng f r change over som automatiskt st ller om ut g ng UO1 att verka med v rme eller kylfunktion Ing ngen kan anslutas till givare typ PT1000 och givaren monteras s att den k nner temperatu r...

Страница 6: ...s 110 g Dimensions 95 x 95 x 28 mm Installation Monter le r gulateur dans un endroit repr sentatif de la temp rature dans la pi ce et qui ne pr sente pas d obstacle la libre circulation de l air La ha...

Страница 7: ...2 Sortie de contr le du refroidissement Pour des moteurs de vannes 0 10 V DC max 5 mA RU La borne du signal de commande 0 10 V de l actionneur est branch e la borne 24 et les bornes d alimentation lec...

Страница 8: ...n certain intervalle de temp rature autour de la consigne point de consigne chauffage 3 C point de consigne refroidissement 3 C Confort Pr sence Occupied La temp rature de la pi ce est r gul e en fonc...

Отзывы: