39
Rev. 04GB1410
SYSTEMA S.p.A.
EOLO BLULINE
ATTENTION!
Type B installation is not allowed in locals with extracting mechanical ventilation and depression
local.
The local in depression con compromise the functioning of EOLO BLULINE
5
EXHAUST AND SUCTION DUCTS
Exhaust and suction type C53
The equipment can be combined with separate ducts,
for the air intake and the fume discharge.
The ducts can be placed on different vent conditions
(example roof fume discharge and wall air intake).
Maximum pipe length 6+6 meters
Exhaust type B23
The comburent air is taken from the installation room.
The equipment can be combined with separate ducts,
for the air intake and the fume are discharged through a
roof duct.
Maximum pipe length 8 meters
Exhaust and suction type C13 (separated)
The comburent air is taken from the installation room.
The equipment can be combined with separate ducts,
for the air intake and the fume are discharged through a
wall duct.
Maximum pipe length 6+6 meters
Exhaust and suction type C33 (separated)
The comburent air is taken from the installation room.
The equipment can be combined with separate ducts,
for the air intake and the fume are discharged through a
wall duct.
Maximum pipe length 6+6 meters
Exhaust and suction type C33 (coaxial)
The equipment can be combined with concentric or near
vertical ducts for the air intake and the roof fume exhaust.
Maximum pipe length 5+5 meters
Type C53
Type B23
Type B23
Type C13
Type C33
Type C33
Maximum pipe length
6+6 meters Ø100 mm
Maximum pipe length
6+6 meters Ø100 mm
Maximum pipe length
6+6 meters Ø100 mm
Maximum pipe length
5+5 meters Ø100 mm
Maximum pipe length
8 meters Ø100 mm
Maximum pipe length
8 meters Ø100 mm