background image

SS-200-035  1 I56-4175-002

WFDNA Series Vane-type Waterflow 

Detectors

INSTALLATION AND MAINTENANCE INSTRUCTIONS

 6581 Kitimat Road, Unit 6, Mississauga, Ontario L5N-3T5

1-800-SENSOR2, FAX: 905-812-0771

www.systemsensor.ca

IMPORTANT
Please Read Carefully And Save

This instruction manual contains important information about the installation 
and operation of waterflow detectors. Purchasers who install waterflow detec-
tors for use by others must leave this manual or a copy of it with the user.

Read all instructions carefully before beginning. Follow only those instruc-
tions that apply to the model you are installing.

CAUTION

The model WFDNA is a vane-type waterflow detector for use in wet-pipe fire 
sprinkler systems only. Vane-type waterflow detectors shall not be used as 
the sole initiating device in both deluge and preaction systems; waterflow de-
tectors used in these types of systems may result in an unintended discharge 
caused by a surge, trapped air or a short retard time. 

WARNING

Installation must be performed by qualified personnel and in accordance with 
all national and local codes and ordinances.

Shock hazard:

 Disconnect power source before servicing. Serious injury or 

death could result.

Risk  of  explosion:

 Not for use in hazardous locations. Serious injury or 

death could result.

PRINCIPLES OF OPERATION

Vane-type waterflow detectors mount to water-filled pipes in fire sprinkler 
systems. Waterflow in the pipe deflects a vane, which produces a switched 
output, usually after a specified delay. All WFDNA’s have a pneumatically 
controlled mechanical delay mechanism. Delays do NOT accumulate; they 
reset if the flow of water stops or drops below minimum triggering flow rate 
before the entire delay has elapsed. 

All switches actuate when the water flow rate is 10 gallons per minute or 
greater, but will not actuate if the flow rate is less than 4 gallons per minute. 
This System Sensor installation manual covers the following waterflow detec-
tors for fire sprinkler/fire alarm applications.

Model

Pipe Size

(inches)

Pipe

Schedule

Max. Pressure

Rating (psig)

WFD20NA

2

7 thru 40

450

WFD25NA

2.5

7 thru 40

450

WFD30NA

3

7 thru 40

450

WFD40NA

4

7 thru 40

450

WFD50NA

5

10 thru 40

450

WFD60NA

6

10 thru 40

450

WFD80NA

8

10 thru 40

450

SPECIFICATIONS

Contact Ratings: 

   

10 A @ 125/250 VAC 

; 2.5 A @ 24 VDC 

Triggering Threshold Bandwidth (Flow Rate): 

4 to 10 gpm

Static Pressure Rating: 

   

See models listed below

Dimensions, Installed: 

   

2.6 in H x 3.5 in W x 6.7 in D

Operating Temperature Range: 

   

32°F to 150°F (0°C to 66°C)

Compatible Pipe: 

   

Steel water pipe, schedule 7 through 40 (See chart below)

Shipping Weight: 

   

3 to 6 lbs (according to size)

Enclosure Rating: 

   

NEMA Type 4, as tested by Underwriters Laboratories, Inc.

U. S. Patent Numbers:  

   

5,213,205

CAUTION

Do NOT use any of the WFDNA models on copper pipe. The clamping forces 
of the mounting bolts may collapse the pipe sufficiently to prevent the detec-
tor from functioning properly.

Do NOT install steel or iron pipe sections in copper piping for mounting a 
waterflow detector. Incompatibility between the dissimilar metals causes bi-
metallic corrosion.

INSTALLATION GUIDELINES

Before installing any waterflow alarm device, be thoroughly familiar with:

NFPA 72:

 National Fire Alarm Code

NFPA 13:

 Installation of Sprinkler Systems, Sect. 3.17

NFPA  25:

 Inspection, Testing and Maintenance of Sprinkler Systems, Sect. 

5.3.3.2

CAN/ULC S524: 

Installation of Fire Alarm Systems

Other applicable Canadian and NFPA standards, local codes, and the re-
quirements of the authority having jurisdiction

NOTE:

 Installation methods other than those listed in this installation manual 

may prevent the device from reporting the flow of water in the event the associ-
ated fire sprinkler system is activated by a fire. System Sensor is not respon-
sible for devices that have been improperly installed, tested, or maintained.

1. 

 Mount the detector where there is adequate clearance for installation and 
removal and a clear view of it for inspections. See 

Figure 1

 for mounting 

dimensions.

2. 

 Locate the detector 6 to 7 feet above the floor to protect from accidental 
damage.

3. 

 On horizontal runs, position the detector on the top or side of the pipe. Do 
not mount it upside down because condensation may collect in the hous-
ing and impair the operation of the detector. For vertical flow applications, 
mount the detector on pipe through which water flows upward. Otherwise, 
the unit may not operate properly.

4. 

 Mount the detector at least 6 inches from a fitting that changes the direc-
tion of water flow and no less than 24 inches from a valve or drain.

5. 

 Be sure the direction-of-flow arrows and directional cover match the direc-
tion of flow in the pipe. See 

Figure 6

.

MOUNTING INSTRUCTIONS

1. 

Drain the pipe.

2. 

 Cut a hole in the pipe at the desired location. Center the hole on the pipe, 
as shown in 

Figure 2

, and be sure the hole is perpendicular to the center 

of the pipe. Before drilling, use a punch or scribe to mark the drill site to 
prevent the bit from slipping. If the hole is off center, the vane will bind 
against the inside wall of the pipe. Use a drill or hole saw to cut a hole of 
the proper diameter. See 

Table 1

 for hole size.

CAUTION

When drilling the hole with a hole saw, make certain that the center of the cut 
does not remain in the pipe.

Отзывы: