5.  

Install the U-bolt, tightening the nuts alternately to ensure a uniform seal 
(see 

Table 1

 for torque values).

6. 

Remove the metal cover with the tamper-proof wrench provided. Move 

the actuator lever back and forth to check for binding. If the vane binds, re-
move the detector and correct the cause before proceeding.

CAUTION

Be sure the direction-of-flow arrow points in the right direction or else water 
flow will go unreported. See 

Figure 3

.

FIGURE 1. MOUNTING DIMENSIONS:

7.6 CM

(3˝)

9.5 CM

(3

3

/

4

˝)

PIPE DIAMETER

PLUS 13.3 CM

(5

1

/

4

˝)

PIPE

VANE

PIPE

U-BOLT 

NUT

PIPE 

SADDLE

U-BOLT

OVERALL WIDTH = PIPE DI 7.6 CM (3˝)

W0105-00

FIGURE 2. MOUNTING HOLE LOCATION:

WRONG

RIGHT

REMOVE BURRS FROM EDGE OF HOLE. CLEAN OUT SCALE

AND FOREIGN MATTER FROM INSIDE WALL OF PIPE.

W0106-00

TABLE 1:

WFD MODEL

HOLE SIZE (IN)

TORQUE

20, 25, 35

1

1

/

4

30–35 ft.-lb.

30-2, 40, 50, 60, 80

2

55–60 ft.-lb.

D770-01-00 2 

I56-0459-017R

PRE-OPERATION TESTING 

1.  

Fill the sprinkler system and check for leaks around the waterflow detec-
tor. If it leaks, first check for the proper torque on the U-bolt nuts. If the 
leak persists, drain the system and remove the detector (refer to Mainte-
nance). Check for dirt or foreign objects under the gasket, and make sure 
that the pipe surface is not dented. Reinstall the detector and check again 
for leaks. Do not proceed until all leaks have been stopped.

2.  

Connect an ohmmeter or continuity tester across the COM and B-NO 
switch terminals. The ohmmeter should indicate an open circuit.

3.  

Deflect the actuator lever and hold it until the pneumatic delay shaft 
releases the switch buttons. The ohmmeter or continuity tester should 
show a short circuit after the delay has elapsed. If there is no delay, 
check the setting of the delay adjustment dial.

FIGURE 3. ASSEMBLY DIAGRAM:

COVER

WA

TERFLOW

PIPE

U-BOLT

TAMPER PROOF 

WRENCH

(P/N WFDW)

DELAY

MECHANISM 

(REPLACEMENT 

(P/N A3008-00)

MOUNTING PLATE

PIPE SADDLE

PLASTIC VANE

ROLL PADDLE 
OPPOSITE OF 

FLOW ARROW 

WHILE INSERTING

SADDLE GASKET

REFER TO 

TABLE 1

ELECTRICAL 

CONDUIT 

ENTRANCE

U-BOLT 

NUT

TERMINAL 

BLOCK 

(REPLACEMENT 

P/N A77-01-02)

W101-01

WIRING

1.    All models have two SPDT switches. Switch contacts COM and B-NO 

are closed when water is flowing and open when it is not. Connect the 
switches, as shown in Figure 4, depending on the application.

2.    When connected to a listed sprinkler/fire alarm control panel, the initiat-

ing circuit must be nonsilenceable.

3.    A ground screw is provided with all waterflow detectors. When ground-

ing is required, clamp wire with screw in hole located between conduit 
entrance holes. See Figure 5A, page 4.

4.  

If a second conduit entry is required, remove the knockout plug using a 
flat blade screwdriver as shown on Figure 5B, page 4. Strike sharply with a 
hammer to pierce the wall of the knockout plug. Move to an adjacent wall 
section and repeat until the plug falls out. Make sure that the waterflow 
detector is supported adequately during this operation to avoid injury.