background image

D770-01-00 3 

I56-0459-017R

WARNING

High Voltage. Electrocution Hazard. Do not handle live AC wiring or work on a 
device to which AC power is applied. Doing so may result in injury or death.

When utilizing switches at voltages greater than 74VDC 

 or 49VAC 

 

means to provide all–pole disconnection must be incorporated in the fixed 
wiring, such as a circuit breaker.

FIGURE 4. WFD WIRING:

+

+

SSM24-X

SSV120-X

NOTE:

 COMMON AND B-NO 

CONNECTIONS WILL CLOSE 
WHEN VANE IS DEFLECTED, I.E., 
WHEN WATER IS FLOWING. DUAL 
SWITCHES PERMIT 
APPLICATIONS TO BE COMBINED 
ON A SINGLE DETECTOR.

BREAK WIRE AS 
SHOWN FOR 
SUPERVISION OF 
CONNECTION. DO 
NOT ALLOW 
STRIPPED WIRE 
LEADS TO EXTEND 
BEYOND SWITCH 
HOUSING. DO NOT 
LOOP WIRES.

POWER 
24VDC OR 
120VDC

INITIATING 

LOOP

UL LISTED 
COMPATIBLE 
CONTROL PANEL

CONTACT RATINGS

125/250 VAC

24 VDC

10 AMPS

2.5 AMPS

SCHEMATIC OF 
INDIVIDUAL 
SWITCH IN
“NO WATERFLOW” 
CONDITION

SUGGESTED EOL 

RESISTOR

B-NO

COM

A-NC

W0356-00

MECHANICAL DELAY ADJUSTMENT

The pneumatic delay is preset at the factory to 30 seconds. To adjust the set-
ting, turn the adjustment dial clockwise to increase the delay, counterclock-
wise to decrease it. The delay is adjustable from 0 to 90 seconds. See Figure 
6, page 4.

NOTE:

 Set the delay to the minimum required to prevent false alarms from 

flow surges.

Periodically test time delay as required by Authority Having Jurisdiction or 
code authority.

OPERATIONAL TESTING

Always notify a central station monitoring waterflow alarms before repairing, 
maintaining, or testing waterflow alarm devices.

1.  

Replace the cover and tighten the tamper proof screws with the tamper 
proof wrench. Store the wrench in a secure place.

2.  

Open the inspector’s test valve and time how long it takes for the detec-
tor to indicate a flow condition. The detector should remain activated un-
til the inspector’s test valve is closed. Air pockets in the sprinkler system 
may increase the apparent delay.

MAINTENANCE

To prevent accidental water damage, control valves should be shut tight and 
the system completely drained before waterflow detectors are removed or re-
placed.

Inspect detectors in accordance with applicable NFPA codes and standards 
and/or the authority having jurisdiction for leaks and replace if a leak occurs. 
Test detectors at least quarterly, as described under Operational Testing, to 
ensure proper operation. Test more often if required by the authority having 
jurisdiction.

Under normal conditions, System Sensor waterflow detectors should provide 
years of trouble-free service. However, if the delay mechanism or switch en-
closure needs to be replaced, follow these directions. To replace the delay 
mechanism or switch enclosure, use a 3/16  socket head screwdriver to re-
move the three screws that hold it in place. Either mechanism can be easily 
replaced without removing the detector from the pipe or draining the pipe. To 
replace the delay mechanism, request Part No. A3008-00. For switch enclo-
sure, request Part No. A77-01-02. Do not repair or replace any other waterflow 
detector components. If any other part of the detector does not perform prop-
erly, replace the entire detector. Installation methods other than those listed 
in this installation manual may prevent the device from reporting the flow of 
water in the event the associated sprinkler system is activated by a fire. Sys-

tem Sensor is not responsible for devices that have been improperly installed, 
tested, or maintained.

To remove a detector:

1. 

Drain the pipe.

2. 

Turn off electrical power to the detector and disconnect the wiring.

3. 

Loosen the nuts and remove the U-bolts.

4.  

Gently lift the saddle far enough to get your fingers under it. Then, roll 
the vane so it will fit through the hole while continuing to lift the water-
flow detector saddle.

5. 

Lift the detector clear of the pipe.

CAUTION

If a vane breaks in a pipe, find and remove it. If it is not removed, the vane 
may restrict the flow of water to all or part of the sprinkler system. 

FIGURE 5A. GROUND SCREW LOCATION:

GROUND
SCREW
(GREEN)

MOUNTING
PLATE

W103-00

FIGURE 5B. KNOCKOUT PLUG REMOVAL:

W0148-01

FIGURE 6. DELAY ADJUSTMENT DIAL:

DELAY
ADJUSTMENT
DIAL

55

70

0

15

45

30

TI

M

E  

DE

LAY  IN  SECO

ND

S

N

U

M

BE

 ON

  DIAL  IS  APPR

OX

IM

AT

E

NOTE:

 RETARD TIME MAY EXCEED 90 SECONDS. ADJUST 

AND VERIFY THAT TIME DOES NOT EXCEED 90 SECONDS. 
NUMBER ON DIAL IS APPROXIMATE TIME DELAY IN 
SECONDS WITH AN ACCURACY OF +/− 50%.

W0112-02

Отзывы: