D690-04-00 3
I56-2783-001R
Tone Selection
Chime tone setting selection is accomplished by using the ro-
tary switch on the back of the product (see Table 4). The cur-
rent draw for various tone settings for chimes is listed in Table
5. The sound measurements for various chime tone settings
are shown in Table 6 for chime and chime/strobe products.
Table 4. Chime Patterns
Setting
Repetition Rate
dB Out
1
1 Second Chime
High
2
1 Second Chime
Low
3
1
/
4
Second Chime
High
4
1
/
4
Second Chime
Low
5
Temporal Chime
High
6
Temporal Chime
Low
7
5 Second Whoop
High
8
5 Second Whoop
Low
9
One Test Chime
High
Table 5. Chime Current Draw (mA)
Sound Pattern
dB
8–17.5 Volts
16–33 Volts
DC
FWR
DC
FWR
1 Second Chime
High
34
50
58
51
1 Second Chime
Low
30
51
51
54
1
/
4
Second Chime
High
34
51
50
50
1
/
4
Second Chime
Low
31
51
50
52
Temporal Chime
High
30
50
48
54
Temporal Chime
Low
30
47
50
51
5 Second Whoop
High
32
52
34
54
5 Second Whoop
Low
30
40
34
52
One Test Chime
High
48
49
50
50
Table 6. Chime & Chime/Strobe Output (dBA)
Switch
Position
Sound Pattern
dB
8–17.5 Volts 16–33 Volts
DC
FWR
DC
FWR
1
1 Second Chime
High
58
59
61
61
2
1 Second Chime
Low
53
54
55
55
3
1
/
4
Second Chime High
63
64
66
66
4
1
/
4
Second Chime Low
58
59
60
60
5
Temporal Chime
High
62
64
68
69
6
Temporal Chime
Low
55
57
60
60
7
5 Second Whoop
High
68
71
75
77
8
5 Second Whoop
Low
62
64
67
68
9
One Test Chime
High
57
55
61
57
Wiring
Figure 1. Non-Synchronized devices; any combination
of models powered by a 2-wire circuit
Chime
(+)
(–)
(+)
(–)
E
O
L
(+)
(–)
(+)
(–)
Chime/strobe
Chime
Two Wire System
Any Mix of Models
Wired for Tandem
Operation
Figure 2. Synchronized devices; any combination of
models powered by a 2-wire circuit
Chime
Synchronization Module
(+)
(–)
(+)
(–)
E
O
L
(+)
(–)
(+)
(–)
Chime/strobe
Chime
Two Wire System
Any Mix of Models
Wired for Tandem
Operation
MDL
A0345-00
NOTE:
For further information on synchronization see MDL,
panel, or power supply installation manual.
Terminal Definitions
Figure 3.
Mounting
Figure 4.
1.
Attach mounting plate to junction box. The mounting
plate is compatible with 4˝ square, single gang, double
gang, and 4˝ octagon junction boxes. If using a back box
skirt, attach the mounting plate to the skirt and then at-
tach the entire assembly to the junction box.
2.
Connect field wiring according to terminal definitions.
3.
If the product is not to be installed at this point, use the
dust cover to prevent contamination of the wiring termi-
nals of the mounting plate.
4.
To attach product to mounting plate, hook tabs on the
product housing into the grooves on mounting plate.
Then, swing product into position to engage the pins on
the product with the terminals on the mounting plate.
Make sure that the tabs on the back of the product hous-
ing fully engage with the mounting plate.
5.
Secure product by tightening the single mounting screw
in the front of the product housing.
A0353-00
A0350-00