background image

INSTALLATION AND MAINTENANCE INSTRUCTIONS

Selectable Output Chimes and Chime/Strobes

3825 Ohio Avenue, St. Charles, Illinois 60174

800/736-7672, FAX: 630/377-6495

www.systemsensor.com

D690-04-00 1 

I56-2783-001R

For use with the following models: CHSR, CHSW, CHR, CHW.

Specifications

General Specifications

Standard Operating Temperature: 

32°F to 120°F (0°C to 49°C)

Humidity Range: 

10 to 93% non-condensing

Strobe Flash Rate: 

1 flash per second

Nominal Voltage: 

Regulated 12DC/FWR or regulated 24DC/FWR

1

Operating Voltage Range: 

8 to 17.5 V (12V nominal) or 16 to 33 V (24 nominal)

Operating Voltage with MDL: 

9 to 17.5 V (12V nominal) or 17 to 33 V (24 V nominal)

1

CHS

 

products will operate at 12 V nominal only for 15 & 15/75 cd.

Mechanical Specifications

Input terminal wire gauge: 

   

12 to 18 AWG

Chime/strobe dimensions (including lens): 

5.6˝L×4.7˝W×2.5˝D (142 mm L×119 mm W×64 mm D)

Chime dimensions: 

   

5.6˝L×4.7˝W×1.3˝D (142 mm L×119 mm W×33 mm D)

The products in this manual may be covered by one or more of the following patents: 5,593,569; 5,914,665; 5,850,178; 5,598,139; 6,049,446; 6,127,935; 6,133,843; 

6,661,337; 6,833,783; 6,856,241; 6,822,400; 6,522,261.

General Description

Chimes and chime/strobes are private mode notification 
appliances used to alert trained personnel to investigate 
possible emergency situations and take appropriate action. 
SpectrAlert Advance chimes and chime/strobes are electri-
cally backward compatible with the previous generation of 
notification appliances. While they are specifically designed 
for use on the wall, the products are listed to be used on 
the wall or ceiling. SpectrAlert products are designed to be 
used in either 12 or 24 volt DC or full wave rectified (FWR) 
systems. If required, the MDL module may be used in order 
to provide synchronization.

NOTICE:

 This manual shall be left with the owner/user of 

this equipment.

Fire Alarm System Considerations

The National Fire Alarm Code, NFPA 72, requires that all 
horns, used for building evacuation installed after July 1, 
1996, produce temporal coded signals. Signals other than 
those used for evacuation purposes do not have to produce 
the temporal coded signal.

Power Supply Considerations

Panels typically supply DC filtered voltage or FWR (full 
wave rectified) voltage. The system design engineer must 
calculate the number of units used on a loop based on the 
type of panel supply. Be certain the sum of all the device 
currents does not exceed the current capability of the panel. 
Calculations are based on using the device current found 
in the subsequent charts and must be compatible with the 
current specified for the panel or power supply used.

NOTE:

 SpectrAlert chimes and chime/strobes must be pow-

ered from a non-coded power supply.

Wire Sizes

The designer must be sure that the last device on the circuit 
has sufficient voltage to operate the device within its rated 
voltage. When calculating the voltage available to the last 
device, it is necessary to consider the voltage drop due to 
the resistance of the wire. The thicker the wire, the smaller 
the voltage drop. Generally, for purposes of determining the 
wire size necessary for the system, it is best to consider all 
of the devices as “lumped” on the end of the supply circuit 
to simulate worst case. For the most accurate voltage drop 
calculations use the System Sensor voltage drop calculator 
available on the web or CD-ROM.

Approximate wire resistance:

18 AWG solid: 8 ohms/1000 ft.
16 AWG solid: 5 ohms/1000 ft.
14 AWG solid: 3 ohms/1000 ft.
12 AWG solid: 2 ohms/1000 ft.

NOTE:

 If Class A wiring is installed, the wire length may be 

up to twice as long as on non-fault tolerant circuits.

Candela Selection for CHS series models

For strobe candela selection, adjust the slide switch located 
on the rear of the product while watching the viewing win-
dow under the reflector on the front of the unit. Use Table 
1 to determine current draw at various candela and chime 
tone settings. Tables 2 and 3 can be used to determine 
strobe light output at various viewing angles.

NOTE:

 SpectrAlert products set at 15 and 15/75 candela au-

tomatically work on either 12V or 24V power supplies. The 
products are not listed for 12V operating voltages when set 
to any other candela settings.

Отзывы: