background image

Figure 7. Wiring Diagram

+ –

+

+

+

TO NEXT

DEVICE

FROM PANEL OR

PREVIOUS DEVICE

LISTED

REMOTE

POWER

SOURCE

Only used for

 BEAM200SA. See

 electrical ratings.

COMMUNICATION LINE

32 VDC MAX.

TWISTED PAIR IS

RECOMMENDED.

+

T3

T2

T1

C0261-00

Figure 8. Wiring Diagram (RTS451)

RTS 451/KEYA

BEAM200A/BEAM200SA

Pin 1

Remote Alarm Out

T2-1

T2-2
T2-4
T2-3

AUX  (–)
Reset Input
Test Input

Pin 2

Pin 4

Pin 3

Pin 5

See RTS451/KEYA Installation Inst

for electrical r

atings of RTS451/KEY

A.

C0307-00

Figure 9. Wiring Diagram (RTS451)

BEAM200A/SA

Alarm

Signal

Circuit

(Note 1)

T2-1

T2-2

Note 1: 

See electrical r

atings section of this

 

manual f

or circuit output r

atings.

SLC (+)

SLC (–)

Red

C0319-00

Installation / Alignment

Reference  Figures  10  through  14  for  installation,  alignment, 
and maintenance.

The  alignment  of  the  BEAM200A/BEAM200SA  is  divided 
into  four  steps:  coarse  alignment,  fine  adjustment,  final  gain 
adjustment,  and  final  verification.  It  is  necessary  for  all  four 
steps to be executed properly to ensure proper alignment of the 
product. If the detector and reflector are mounted per Mounting 
Locations and Mounting Instructions sections of this manual and 
the alignment procedures are executed properly, false alarms 
and nuisance trouble signals will be minimized.

Pre-Alignment Checklist

•   Insure  that  both  the  detector  and  reflector  are  mounted 

securely to stable surfaces.

•   Insure that all wiring is correct.
•   Insure  that  terminal  blocks  are  fully  seated  into  their 

receptacles on the detector.

•    Complete  any  wiring  dressing  to  minimize  movement 

to  the  detector  once  the  alignment  procedure  is  com-
pleted.

•    Insure  that  the  appropriate  number  of  reflectors  are 

used  for  the  installed  distance.  Distances  between  230 
&  328  Feet  (70  -  100m)  require  additional  reflectors  (4 
total).  The  BEAMLRK  accessory  should  be  used  in  these 
cases.

•   Insure  that  the  line  of  sight  between  the  detector  and 

reflector  is  clear  and  that  reflective  objects  are  not  too 
near. See Mounting Instructions for more details.

•   Insure  that  both  the  detector  and  reflector  are  mounted 

within  their  operational  parameters  for  off  axis  angles. 
See Mounting Instructions for more details.

•   Disable  the  zone  or  system  to  prevent  unwanted  alarms 

before applying power.

•   Insure power to the detector is “ON”.
•   Insure  that  the  appropriate  address  is  set  on  the  code 

wheels.

You are now ready to begin the alignment procedure.

Step 1. Coarse Alignment

Refer to Figures 11 and 12 for this step.

1.   Insure  that  both  of  the  optics  lock-down  screws  are  loos-

ened so that the optics will move feely.

2.   Looking  through  the  alignment  mirror  at  both  the  align-

ment sight and reflector simultaneously locate the position 
of  the  reflector  in  the  optical  sight. This  step  will  require 
some  practice.  It  is  necessary  to  train  your  eyes  to  shift 
focus  between  the  reflector  and  the  mirror  in  order  to 
locate  the  reflector.  If  the  distance  between  the  reflector 

D400-74-00 

I56-2542-00R

Содержание BEAM200A

Страница 1: ... Reset Switch Capability compatible with RTS451 RTS451KEYA Indicators Alarm Remote Output Local LED red Trouble Local LED yellow Blink Pattern Indicates Trouble Diagnostics Normal Operation Local LED flashing green with communication Alignment Aids Optical Gunsight coarse adjustment 00 to 99 Digital Display fine adjustment Sensitivity Digital Display Readout in Percent Obscuration Style 7 Operatio...

Страница 2: ... a dual digi tal display that reads 00 to 99 This display is used to indi cate the signal strength of the beam in alignment mode and to indicate the sensitivity setting of the detector in percent obscuration when setting the sensitivity of the detector No additional equipment is needed for alignment of the beam Special Applications Due to the inherent capabilities of projected type beam detectors ...

Страница 3: ...minal Blocks 3 Isolator Shunts 2 Instruction Manual 1 Orange Sticky Paper 1 Parts Diagram not to scale C0306 00 Detector Placement Thissectionofthemanualdiscussestheplacementofprojected beamdetectors Thoughthisinformationisbaseduponindustry expertise it is intended to be used only as a technical guide Always comply with the requirements of applicable codes and standards such as ULC S524 NFPA 72 Na...

Страница 4: ...detectors shall be the result of an engi neering evaluation that includes the following structural features size and shape of the room and bays occupancy and uses of the area ceiling height ceiling shape surface and obstructions ventilation ambient environment burn ing characteristics of the combustible materials present and the configuration of the contents in the area to be protected Figure 3 Sl...

Страница 5: ...ay be used to provide greater angular adjustment of the transmitter receiver unit If the perpen dicular plane of the reflector cannot be mounted within 10 of the optical line of sight then the multi mount kit can be used for the reflector See BEAMMMK instructions To aid in locating the reflector in the alignment mirror at long distances a bright orange sticky backed piece of paper is provided Remo...

Страница 6: ...tector shall be no smaller than 22 AWG 1 0 mm2 For best system perfor mance all wiring should be twisted pair and installed in separate grounded conduit Do NOT mix fire system wiring in the same conduit as any other electrical wiring Shielded cable may be used to provide additional protection against electrical interference When installing the beam smoke detector in applications where the head uni...

Страница 7: ...all wiring is correct Insure that terminal blocks are fully seated into their receptacles on the detector Complete any wiring dressing to minimize movement to the detector once the alignment procedure is com pleted Insure that the appropriate number of reflectors are used for the installed distance Distances between 230 328 Feet 70 100m require additional reflectors 4 total The BEAMLRK accessory s...

Страница 8: ...the horizontal and vertical alignment knobs one at a time in the direction that increases the numeric signal level on the display Continue adjusting each axis one at a time going back and forth between them until a peak value is indicated If a value of 90 is achieved the detector will re adjust the electronic gain once again This will be indicated by a reading on the display When this happens halt...

Страница 9: ...the high optical efficiency of the reflec tor the selection of the opaque material used to block the reflector is not critical Acceptable materials include but aren t limited to this manual or the cardboard packaging inserts See Figure 14 The detector should enter the fault condition indicated by the fault relay and the yellow LED see Appendix I If the detector does not enter the trouble condition...

Страница 10: ...tinue to depress the sensitivity switch until the desired setting is achieved The digital display will turn off automatically if no further switch presses occur Sensitivity Setting Obscuration Display Reading Acceptable Distance Between Detector and Reflector Feet Acceptable Distance Between Detector and Reflector meters Level 1 25 25 16 4 to 120 5 0 to 37 2 Level 2 30 30 25 to 150 7 6 to 46 6 Lev...

Страница 11: ...erial over the reflector lining it up with the graduated marks that are 10 less than the detec tor s setting in obscuration The detector should not alarm or fault Keep the material in place for a minimum of 1 minute 3 Place the blocking material over the reflector lining it up with the graduated marks that are 10 more than the detec tors setting in obscuration The detector should enter alarm withi...

Страница 12: ...f NFPA72 and or ULC for peri odic maintenance and sensitivity verification of beam type detectors If the detector fails this test several steps should be taken to determine if the detector is faulty or simply needs to be re adjusted before returning the unit These steps include 1 Verify all wiring connections and appropriate power is applied to the detector 2 Verify that the optical line of sight ...

Страница 13: ...detector and reflector for reflective objects in the pathway Trouble Beam Blockage Initial Response Off 4 Quick Blinks Blink Blink Off Beam Blockage Remove blockage Faulty unit Trouble Beam Blockage Long Term Response On 4 Quick Blinks Blink On Off Beam Blockage Remove blockage Faulty unit Initialization Power on Off Blink until complete Blink Blink Off Apply Power from discharged state Initializa...

Страница 14: ...D400 74 00 14 I56 2542 00R Scale 1 1 D400 74 00 14 I56 2542 00R Appendix II Detector Drilling Template 4 345 6 190 ...

Страница 15: ...Appendix III Reflector Drilling Template Scale 1 1 5 512 140mm 8 465 215mm D400 74 00 15 I56 2542 00R ...

Страница 16: ...iscausedbytheCompany snegligenceorfault Somestates donotallowtheexclusionorlimitationofincidentalorconsequentialdamages so the above limitation or exclusion may not apply to you This Warranty gives you specific legal rights and you may also have other rights which vary from state to state Three Year Limited Warranty FCC Statement This device complies with part 15 of the FCC Rules Operation is subj...

Отзывы: