System Sensor BEAM200 Скачать руководство пользователя страница 8

Sensitivity 

Setting

Percent 

Obscuration

Display 

Reading

Acceptable Distance 

Between Detector & Reflector

Feet

Meters

Level 1

25

25

16.4 to 120

5.0 to 36.6

Level 2

30

30

25 to 150

7.6 to 45.7

Level 3

40

40

60 to 220

18.3 to 67

Level 4

50

50

80 to 328

24.4 to 100

Acclimate 

Level 1

30 to 50

A1

80 to 150

24.4 to 45.7

Acclimate 

Level 2

40 to 50

A2

80 to 220

24.4 to 67

In addition to the four standard sensitivity selections the detector has two Ac-
climate settings. When either of these settings is chosen the detector will au-
tomatically adjust its sensitivity using advanced software algorithms to select 
the optimum sensitivity for the environment. The sensitivity will be continu-
ously adjusted within the ranges specified in the chart above.

SENSITIvITy

Total  obscuration  can  be  converted  to  percent  per  foot,  assuming  uniform 
smoke density for the entire length of the beam. The charts below converts 
total obscuration to percent per foot for all acceptable sensitivity settings.

2.0

1.5

1.0

0.5

0.0

0

25% SETTING

30% SETTING

40% SETTING

50% SETTING

50

100

150

200

250

300

350

OBSCURA

TION (%/FT

.)

SENSITIVITY IN PERCENT PER FOOT VS. DISTANCE

(ASSUMES UNIFORM SMOKE DISTRIBUTION)

DISTANCE IN FEET

C0268-00

SENSITIvITy TESTINg

NOTE:  Before  testing,  notify  the  proper  authorities  that  the  smoke  detector 
system is undergoing maintenance, and therefore the system will be tempo-
rarily out of service. Disable the zone or system undergoing maintenance to 
prevent unwanted alarms.

Detectors must be tested after installation and following periodic maintenance. 
The sensitivity of the BEAM200/BEAM200S may be tested as follows:

NOTE:

 Before testing the detector, check for the presence of the flashing green 

LED at the receiver, making sure not to disturb or block the beam. If it does 
not flash and the detector is not in trouble or alarm, power has been lost to 
the detector (check the wiring).

A. Calibrated Test Filter

The sensitivity of the detector can be tested using an opaque material to cover 
the reflector by an amount indicated by the graduated scale on the reflector. 
(Due to the high optical efficiency of the reflector the selection of the opaque 
material  used  to  block  the  reflector  is  not  critical.  Acceptable  materials  in-
clude, but aren’t limited to, this manual or the cardboard packaging inserts.)
Refer to Figure 14 for this procedure.
 

1.   Verify the sensitivity setting of the detector in % obscuration. See the 

Sensitivity Selection section of this manual for sensitivity determina-
tion if sensitivity is unknown.

 

2.   Place the blocking material over the reflector, lining it up with the 

graduated marks that are 10 less than the detector’s setting in % ob-
scuration. The detector should not alarm or fault. Keep the material 
in place for a minimum of 1 minute.

 

3.   Place  the  blocking  material  over  the  reflector  lining  it  up  with  the 

graduated  marks  that  are  10  more  than  the  detectors  setting  in  % 
obscuration. The detector should enter alarm within 1 minute.

fIgURE 14. REfLECTOR TEST CARD PROCEDURE

LINE UP EDGE OF

TEST CARD WITH

APPROPRIATE

OBSCURATION LEVEL

MOVE TEST CARD TO DESIRED AMOUNT OF OBSCURATION

C0267-00

 

4.   The detector can be reset with the reset switch on the detector unit or 

remote reset.

 

5.   Notify the proper authorities that the system is back on line.

 If the detector fails this test several steps should be taken to determine if the 
detector is faulty or simply needs to be re-adjusted before returning the unit. 
These steps include:
 

1.   Verify  all  wiring  connections  and  appropriate  power  is  applied  to 

the detector.

 

2.   Verify that the optical line of sight is free from obstructions and re-

flective objects.

 

3.   Apply the maintenance procedure in this manual. Repeat the test pro-

cedure. If the detector still fails the test procedure proceed with step 4.

 

4.   Repeat the alignment procedure in this manual. If the alignment pro-

cedure is successful repeat the test procedure. If the detector still fails 
the test it should be returned.

NOTE: For the BEAM200S the external power supply must be connected for 
the test switch to work.

B. Test Switch 

The detector can be tested using the local test switch on the transmitter/re-
ceiver unit or remotely using the remote test station.
The  remote  test  station  can  be  used  with  the  BEAM200/BEAM200S  beam 
smoke detector. Follow instructions included with the test station for proper 
use. See Figure 8 (Remote Test Station) for wiring diagram.
The BEAM200S is equipped with an integral sensitivity test feature that con-
sists of a calibrated test filter attached to a servo motor inside the detector 
optics. When a test is initiated using the remote test station or local test switch 
the test filter is moved in the pathway of the light beam. The on-board micro-
processor then determines if the proper level of signal reduction is received 
at the receiver. If the proper level of signal reduction is received the detector 
will enter alarm. If the proper level of signal reduction was not achieved, indi-
cating that the sensitivity of the detector is out of tolerance, the detector will 
enter the trouble condition.
Always perform a complete reflector blockage test as in step 4 of the Instal-
lation/Alignment procedure to Ensure that the pathway between the detector 
and reflector is clear.
NOTE: For the BEAM200 this test does not satisfy the requirements of NFPA72 
for periodic maintenance and sensitivity verification of beam type detectors. 
For the BEAM200S this test in conjunction with the complete reflector block-
age test (see step 4 of the Installation/Alignment procedure in this manual) 
does satisfy the requirements of NFPA72 for periodic maintenance and sensi-
tivity verification of beam type detectors.

D400-74-00 

I56-2289-005R

Содержание BEAM200

Страница 1: ...1 communication every 5 sec LED flashing SLC 24 V Max Alarm LED on 8 5mA Max Max Trouble LED on 4 5mA Max Max Alignment 20mA Max External Supply BEAM200S only VOLTAGE 15 to 32 VDC CURRENT 0 5A Max Remote Output alarm VOLTAGE 15 to 32 VDC NOTE Output voltage same as device input voltage CURRENT 15mA maximum 6mA minimum NOTE Output current is limited by 2 2Kohm resistor I56 2289 005R 3825 Ohio Avenu...

Страница 2: ... The kit includes the hardware neces sary to mount either a single transmitter receiver unit or a single reflector To mount the transmitter receiver the surface mount kit BEAMSMK must also be used If the transmitter receiver and the reflector require additional alignment range two kits are required The kit is not compatible with the long range reflector kit BEAMLRK BEAMSMK The BEAMSMK allows Syste...

Страница 3: ...ures size and shape of the room and bays occupancy and uses of the area ceiling height ceiling shape surface and obstructions ventilation ambi ent environment burning characteristics of the combustible materials present and the configuration of the contents in the area to be protected Figure 3 Sloped ceiling shed type S 3 FT 0 9M MAX S 1 2 S MAX Tx Rx REFLECTOR C0256 00 Figure 4 Sloped ceiling pea...

Страница 4: ...detector will not be able to distinguish these reflections from those of the re flector and the protected space will be compromised Panes of glass will also absorb some of the light as it passes through it This absorption of light will reduce the acceptable installed distance between the detector and the reflector In cases where operation through panes of glass cannot be avoided some spe cific ins...

Страница 5: ...r alignment of the product If the detector and reflector are mounted per Mounting Loca tions and Mounting Instructions sections of this manual and the alignment procedures are executed properly false alarms and nuisance trouble signals will be minimized Pre Alignment Checklist Ensure that both the detector and reflector are mounted securely to stable surfaces Ensure that all wiring is correct Ensu...

Страница 6: ...ncrease the electronic gain 4 Once satisfied that it is not possible to achieve a higher reading on the display depress the alignment switch to complete the fine adjustment step The digital display readout will turn OFF and the yellow LED will remain ON NOTE It may not be possible to achieve a value near 90 on the display during the last adjustment iteration The final value of the display will not...

Страница 7: ...t the isolator is disabled This is the default state Sensitivity Selection The detector has six sensitivity selections Each of these selections is only acceptable over a specific distance separation between the detector and the reflector per UL268 The chart below is used to determine which selections are acceptable for your installed distance The sensitivity of the detector can be set only when th...

Страница 8: ...m of 1 minute 3 Place the blocking material over the reflector lining it up with the graduated marks that are 10 more than the detectors setting in obscuration The detector should enter alarm within 1 minute Figure 14 Reflector Test Card Procedure LINE UP EDGE OF TEST CARD WITH APPROPRIATE OBSCURATION LEVEL MOVE TEST CARD TO DESIRED AMOUNT OF OBSCURATION C0267 00 4 The detector can be reset with t...

Страница 9: ...h to work Maintenance NOTE Before cleaning the detector notify the proper authorities that the smoke detector system is undergoing maintenance and therefore the system will be temporarily out of service Disable the zone or system undergoing maintenance to prevent unwanted alarms 1 Carefully clean the outer housing lens face A damp soft cloth with a mild soap may be used Avoid products with solvent...

Страница 10: ...er Range Off 2 Quick Blinks Blink Blink Off Increase of Reflected Signal Inspect line of sight between detector and reflector for reflective objects in the pathway Trouble Beam Blockage Response Off 4 Quick Blinks Blink Blink Off Beam Blockage Remove blockage Faulty unit Initialization Power on Off Blink until complete Blink Blink Off Apply Power from discharged state Initialization alignment exit...

Страница 11: ...Scale 1 1 D400 74 00 11 I56 2289 005R Appendix II Detector Drilling Template 4 345 6 190 157 mm 110 mm ...

Страница 12: ...D400 74 00 12 I56 2289 005R ...

Страница 13: ...Appendix III Reflector Drilling Template Scale 1 1 5 512 140mm 8 465 215mm D400 74 00 13 I56 2289 005R ...

Страница 14: ...D400 74 00 14 I56 2289 005R ...

Страница 15: ...o not allow the exclusion or limitation of incidental or consequential damages so the above limitation or exclusion may not apply to you This Warranty gives you specific legal rights and you may also have other rights which vary from state to state Three Year Limited Warranty FCC Statement This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 Thi...

Отзывы: