D400-74-00
10
I56-2289-005R
Blinks output by Yellow LED and Remote Trouble Output
once the device has passed a local remote test:
Percent The Detector Has Drifted
Number Of Blinks Output
<10%
None
<20%
1
<30%
2
<40%
3
<50%
4
<60%
5
<70%
6
<80%
7
<90%
8
<100%
9
Modes
*Red
See Note
Below
Yellow and
Remote Trouble
Output
*Green
See Note
Below
Remote
Alarm
Output
Dual Digital Display
Initiating means
Comments & Troubleshooting
Tips
Normal
Off
Off
Blink
Blink
Off
Successful completion
of initialization or
detector reset
Alignment
Off
On
Blink
Blink
On, Relative amount
of signal 0-99, or – if
automatic gain resetting,
or Lo if signal is too low
Alignment Switch
Alarm
On
Off
Off
On
Off
Smoke, Test Filter,
RTS451 or RTS151
Test Stations
Trouble-Drift
Comp Elevated
Signal
Off
3 Quick Blinks
Blink
Blink
Off
Long Term Drift
Reference Out of
Range
• Sunlight into detector or reflector.
• Re-Align detector.
Trouble-Drift
Comp Reduced
Signal
Off
2 Quick Blinks
Blink
Blink
Off
Long Term Drift
Reference Out of
Range
• Clean detector and reflector.
Trouble-Signal
Over Range
Off
2 Quick Blinks
Blink
Blink
Off
Increase of Reflected
Signal
• Inspect line of sight between
detector and reflector for
reflective objects in the pathway.
Trouble-Beam
Blockage
Response
Off
4 Quick Blinks
Blink
Blink
Off
Beam Blockage
• Remove blockage.
• Faulty unit.
Initialization-
Power on
Off
Blink until
complete
Blink
Blink
Off
Apply Power from
discharged state.
Initialization-
alignment exit
Off
Blink until
complete
Blink
Blink
Off
Depressing RESET
switch after alignment
Local Test
(BEAM-200S)
Pass Result
On
Blinks out amount
of drift used
Off
On
Off
Panel or RTS451/KEY
or RTS151/KEY
Remains in alarm until reset or
time-out
Local Test
(BEAM-200S)
Fail Result
Off
On until reset or
time-out
Blink
Blink
Off
Panel or RTS451/KEY
or RTS151/KEY test
input
Remains in fault until reset or
time-out
Local Test
(BEAM-200)
Fail
Off
On until reset or
time-out
Blink
Blink
Off
Panel or RTS451/KEY
or RTS151/KEY test
input
Remains in fault until reset or
time-out
Local Test
(BEAM-200)
Pass Result
On
Blinks out amount
of drift used
Off
On
Off
Panel or RTS451/KEY
or RTS151/KEY
Remains in alarm until reset or
time-out
Note: Green and Red LEDs are controlled by the control panel.
APPENDIx I. OPERATION MODES AND TROUBLEShOOTINg gUIDE: