INSTALLATION AND MAINTENANCE INSTRUCTIONS

BEAM200, BEAM200S
Single-ended Reflected Type 
Projected Beam Smoke Detector

D400-74-00 

I56-2289-005R

SPECIfICATIONS

GENERAL

Range: 

16 to 230 Feet (5 to 70m); 230 to 328 Feet (70 to 100m) using optional accessory BEAMLRK

Sensitivity: 

25% to 50% Total Obscuration in 6 levels

 

 

 

Level 1 = 25%

 

 

 

Level 2 = 30%

 

 

 

Level 3 = 40%

 

 

 

Level 4 = 50%

 

 

 

Level 5 = 30% to 50% (Acclimate)

 

 

 

Level 6 = 40% to 50% (Acclimate)

Spacing: 

30 to 60 Feet (9.1 to 18.3m)

Response Time: 

ALARM - 20 seconds typical; TROUBLE - 30 seconds typical

Trouble Conditions: 

Beam Blockage (96% or More Obscuration)

 

Improper Initial Alignment

 

Self-compensation limit reached (service needed)

 

In Alignment mode

Test/Reset Features: 

Integral Sensitivity Test Filter (BEAM200S only, requires additional external power supply)

 

Sensitivity Filter (Incremental scale on reflector)

 

Local Alarm Test Switch

 

Local Alarm Reset Switch

 

Remote Test and Reset Switch Capability

Indicators: 

ALARM - Remote Output, Local LED (red)

 

TROUBLE - Remote Output, Local LED (yellow), Blink Pattern Indicates Trouble Diagnostics

 

NORMAL OPERATION - Local LED (flashing green with communication)

 

ALIGNMENT AIDS - Optical Gunsight (coarse adjustment), 00 to 99 Digital Display (fine adjustment)

 

SENSITIVITY - Digital Display Readout in Percent Obscuration

Style 7 Operation: 

On-board isolators provide style 7 operation,(may be disabled via shunts on circuit board)

ENVIRONMENTAL

Temperature: 

22°F to 131°F (

30°C to 55°C) NOTE: for applications below 32°F (0°C) see Special Applications section of this manual.

Humidity: 

10% to 93% RH Non-condensing

MECHANICAL

Shipping Weight: 

Complete unit: 3.9 lbs. (1.77 kg)

Shipping Size: 

15˝ × 10.5˝ × 6.5˝ (381mm × 267mm × 165mm)

Mounting: 

Wall only without optional accessories

Wiring: 

Plug-in Terminal Blocks (12 to 22AWG)

Adjustment Angle: 

±10° Horizontal and Vertical

Paintable Trim Ring: 

May be painted using enamel or acrylic type paints

ELECTRICAL

Voltage: 

15 to 32 VDC

Standby Current: 

Avg. Standby -    

2mA Max. (1 communication every 5 sec., LED flashing, SLC @ 24 V)

 

Max. Alarm (LED on) -  

8.5mA Max.

 

Max. Trouble (LED on) -   4.5mA Max.

 

Max. Alignment -  

20mA Max.

External Supply (BEAM200S only):  VOLTAGE - 15 to 32 VDC
 

CURRENT - 0.5A Max.

Remote Output (alarm): 

VOLTAGE - 15 to 32 VDC, NOTE: Output voltage same as device input voltage.

 

CURRENT - 15mA maximum, 6mA minimum; NOTE: Output current is limited by 2.2Kohm resistor

I56-2289-00

5R

3825 Ohio Avenue, St. Charles, Illinois 60174

1.800.SENSOR2; Fax: 630.377.6495

www.systemsensor.com

BEfORE INSTALLINg

Please thoroughly read this manual and applicable sections of System Sensor’s 
Projected Beam Detector Application Guide. Copies of this manual are avail-
able from System Sensor.

gENERAL DESCRIPTION

System Sensor Model BEAM200/BEAM200S is a long range projected beam 
smoke detector designed to provide open area protection. It is to be used with 
UL-listed compatible control panels only. The detector consists of a transmit-
ter/receiver unit and a reflector. When the obscuration reaches alarm thresh-
olds (chosen at the transmitter/receiver unit), the detector generates an alarm 
signal. Complete blockage of the beam causes a trouble signal. Slow changes 
in obscuration due to a build up of dirt or dust on the lens of the detector are 

compensated for by a microcontroller that continuously monitors the signal 
strength and periodically updates the alarm and trouble thresholds. When the 
self-compensation  circuit  reaches  its  limit,  the  detector  generates  a  trouble 
signal, indicating the need for service.

Three LEDs on the detector indicate the current status: a red LED for alarm, a 
yellow LED for trouble, and a blinking green LED for standby operation. Note: 
The panel controls the status of the red and green LEDs. The local reset but-
ton is accessible by removing the outer paintable trim ring. The yellow LED 
will blink in specific patterns to provide a diagnostic aid when diagnosing the 
cause of a trouble signal. It will also blink the amount of drift compensation 
that  has  been  used  at  the  conclusion  of  the  test.  Trouble  signals  automati-
cally reset upon removing the cause of trouble. Red and yellow LEDs can be 

Содержание BEAM200

Страница 1: ...1 communication every 5 sec LED flashing SLC 24 V Max Alarm LED on 8 5mA Max Max Trouble LED on 4 5mA Max Max Alignment 20mA Max External Supply BEAM200S only VOLTAGE 15 to 32 VDC CURRENT 0 5A Max Remote Output alarm VOLTAGE 15 to 32 VDC NOTE Output voltage same as device input voltage CURRENT 15mA maximum 6mA minimum NOTE Output current is limited by 2 2Kohm resistor I56 2289 005R 3825 Ohio Avenu...

Страница 2: ... The kit includes the hardware neces sary to mount either a single transmitter receiver unit or a single reflector To mount the transmitter receiver the surface mount kit BEAMSMK must also be used If the transmitter receiver and the reflector require additional alignment range two kits are required The kit is not compatible with the long range reflector kit BEAMLRK BEAMSMK The BEAMSMK allows Syste...

Страница 3: ...ures size and shape of the room and bays occupancy and uses of the area ceiling height ceiling shape surface and obstructions ventilation ambi ent environment burning characteristics of the combustible materials present and the configuration of the contents in the area to be protected Figure 3 Sloped ceiling shed type S 3 FT 0 9M MAX S 1 2 S MAX Tx Rx REFLECTOR C0256 00 Figure 4 Sloped ceiling pea...

Страница 4: ...detector will not be able to distinguish these reflections from those of the re flector and the protected space will be compromised Panes of glass will also absorb some of the light as it passes through it This absorption of light will reduce the acceptable installed distance between the detector and the reflector In cases where operation through panes of glass cannot be avoided some spe cific ins...

Страница 5: ...r alignment of the product If the detector and reflector are mounted per Mounting Loca tions and Mounting Instructions sections of this manual and the alignment procedures are executed properly false alarms and nuisance trouble signals will be minimized Pre Alignment Checklist Ensure that both the detector and reflector are mounted securely to stable surfaces Ensure that all wiring is correct Ensu...

Страница 6: ...ncrease the electronic gain 4 Once satisfied that it is not possible to achieve a higher reading on the display depress the alignment switch to complete the fine adjustment step The digital display readout will turn OFF and the yellow LED will remain ON NOTE It may not be possible to achieve a value near 90 on the display during the last adjustment iteration The final value of the display will not...

Страница 7: ...t the isolator is disabled This is the default state Sensitivity Selection The detector has six sensitivity selections Each of these selections is only acceptable over a specific distance separation between the detector and the reflector per UL268 The chart below is used to determine which selections are acceptable for your installed distance The sensitivity of the detector can be set only when th...

Страница 8: ...m of 1 minute 3 Place the blocking material over the reflector lining it up with the graduated marks that are 10 more than the detectors setting in obscuration The detector should enter alarm within 1 minute Figure 14 Reflector Test Card Procedure LINE UP EDGE OF TEST CARD WITH APPROPRIATE OBSCURATION LEVEL MOVE TEST CARD TO DESIRED AMOUNT OF OBSCURATION C0267 00 4 The detector can be reset with t...

Страница 9: ...h to work Maintenance NOTE Before cleaning the detector notify the proper authorities that the smoke detector system is undergoing maintenance and therefore the system will be temporarily out of service Disable the zone or system undergoing maintenance to prevent unwanted alarms 1 Carefully clean the outer housing lens face A damp soft cloth with a mild soap may be used Avoid products with solvent...

Страница 10: ...er Range Off 2 Quick Blinks Blink Blink Off Increase of Reflected Signal Inspect line of sight between detector and reflector for reflective objects in the pathway Trouble Beam Blockage Response Off 4 Quick Blinks Blink Blink Off Beam Blockage Remove blockage Faulty unit Initialization Power on Off Blink until complete Blink Blink Off Apply Power from discharged state Initialization alignment exit...

Страница 11: ...Scale 1 1 D400 74 00 11 I56 2289 005R Appendix II Detector Drilling Template 4 345 6 190 157 mm 110 mm ...

Страница 12: ...D400 74 00 12 I56 2289 005R ...

Страница 13: ...Appendix III Reflector Drilling Template Scale 1 1 5 512 140mm 8 465 215mm D400 74 00 13 I56 2289 005R ...

Страница 14: ...D400 74 00 14 I56 2289 005R ...

Страница 15: ...o not allow the exclusion or limitation of incidental or consequential damages so the above limitation or exclusion may not apply to you This Warranty gives you specific legal rights and you may also have other rights which vary from state to state Three Year Limited Warranty FCC Statement This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 Thi...

Отзывы: