background image

D450-03-00

1

I56-374-05R

B402B Plug-in Detector Base

For use with the following smoke detectors: 
1451, 2451, and 2451TH

INSTALLATION AND MAINTENANCE INSTRUCTIONS

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

Before Installing 

Please read the System Sensor manual I56-407, 

Guide for

Proper Use of System Smoke Detectors,

which provides

detailed information on detector spacing, placement, zon-
ing, wiring, and special applications. Copies of this manual
are available at no charge from System Sensor. (For instal-
lations in Canada, refer to CAN4-S524, 

Standard for the

Installation of Fire Alarm Systems,

and CEC Part 1, Sec. 32.)

NOTICE: 

This manual should be left with the owner/user

of this equipment.

IMPORTANT: 

The detector used with this base must be

tested and maintained regularly following NFPA 72 require-
ments. The detector used with this base should be cleaned
at least once a year.

Specifications

Base Diameter:

6.2 inches (15.7 cm)

Base Height:

1.1 inches (2.8 cm)

Weight:

0.3 lb. (130 g)

Mounting:

4 inch square box with or without plaster ring. Min. Depth: 1.5 inches
4 inch octagon box. Min. Depth: 1.5 inches
3-1/2 inch octagon box. Min. Depth: 1.5 inches

Operating Temperature Range:

0° to +49°C (32° to 120°F)

Operating Humidity Range:

10% to 93 % Relative Humidity, Non-condensing

Electrical Ratings — includes base and detector

System Voltage:

24 VDC

Maximum Ripple Voltage:

4 Volts peak to peak

Start-up Capacitance:

0.02 

µ

F Maximum

Standby Ratings:

20 VDC Minimum
29 VDC Maximum
120 

µ

A Maximum

Alarm Ratings:

17 mA Minimum
36 mA Maximum

Reset Voltage:

1.4 VDC Minimum

Reset Time:

0.3 Seconds Maximum
(If used, the RA400 remote lamp operates within the specified 
detector alarm currents.)

Start-up Time:

34.0 Seconds Maximum

Relay Contact Ratings
Resistive or Inductive (60% Power Factor):
Form A:

2.0A @ 30 VAC/DC

Form C:

2.0A @ 30 VAC/DC
0.6A @ 110 VDC
1.0A @ 125 VAC

General Description

The plug-in detector base B402B is used with System
Sensor model 2451 and 2451TH photoelectronic detector
heads, and model 1451 ionization detector head. The capa-
bility of plugging these detectors into a variety of special
bases makes them more versatile than equivalent direct-
wired models. Refer to the System Sensor catalog for other
available plug-in detector bases.

This B402B base is intended for use in 4-wire systems, with
screw terminals provided for power, remote annunciator,
and relay contact connections. These bases also contain a
resistor to provide current limiting in the alarm state.