background image

 SS-450-000 

I56-3387-005R

B200S 
intelligent Sounder Base

inSTaLLaTiOn and mainTenanCe inSTruCTiOnS

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

BeFOre inSTaLLing

Please read the System Sensor Smoke Detector Application Guide, which pro-
vides detailed information on sensor spacing, placement, zoning, wiring, and 
special applications. Copies of this manual are available from System Sensor. 
NFPA 72 and NEMA guidelines should be observed.

NOTE: 200 Series sounder bases are not compatible with remote test capable 
200 series detectors.

NOTICE

: This manual should be left with the owner/user of this equipment.

IMPORTANT

: The detector used with this base must be tested and maintained 

regularly following NFPA 72 requirements. The detector should be cleaned at 
least once a year.

generaL deSCripTiOn

The B200S sounder base is used with System Sensor 200-Series sensor heads or 
equivalent. For a list of compatible sensors, refer to the System Sensor website 
at www.systemsensor.com. Refer to the appropriate manual for more informa-
tion on sensors.

The B200S sounder base was designed specifically to meet the needs of dwell-
ing unit applications. It offers maximum flexibility in configuration and opera-
tion to meet or exceed the requirements of UL268 and UL464.

The sounder base is capable of producing a variety of tone patterns, including 
the distinctive three-pulse temporal pattern (ANSI Temporal 3) fire alarm sig-
nal now required by NFPA 72 for commercial and residential applications.

The B200S can be commanded by the Fire Alarm Control Panel to adopt the 
address of the attached sensor head, but as a unique device type on the loop. 
By using the address, the fire alarm control panel can command an individual 
sounder base to activate, or a group of sounders in a suite or other multi-room 
configuration. The command set from the panel can be tailored to the specific 
event, allowing selection of volume, tone, and group. The device offers two 
volume levels: 75 dBA and 85 dBA. The available tones are Continuous, ANSI 
Temporal 3, ANSI Temporal 4, and March Time. In addition, some fire alarm 
panels will offer the ability to command a custom tone pattern. Refer to the 
appropriate fire alarm control panel manual for more information.

In addition, the B200S is equipped with the circuitry to recognize the System 
Sensor synchronization protocol, enabling the sounder base to be used as a 
component of the general evacuation signal – producing an NFPA 72 compli-
ant Temporal 3 pattern in synchronization with other System Sensor notifica-
tion devices. This requires connection to a power supply capable of generating 
the System Sensor synchronization pulses, a FACP NAC output configured to 
System Sensor synchronization protocol, or a separate synchronization mod-
ule. In this scenario, the sounder bases will have the ability to synchronize 
with other System Sensor horns, horn/strobes, and chimes using the same 
power source.

Specifications

Base Diameter: 

6.875” (17.46 cm)

Base Height (less sensor): 

2.0” (5.08 cm)

Weight: 

0.50 lb. (227 gm)

Operating Temperature Range: 

Refer to applicable sensor Operating Temperature Range using the Base/Sensor Cross Reference Chart at systemsensor.com

Operating Humidity Range: 

10% to 93% relative humidity (non-condensing)

External Supply Electrical Ratings

External Supply Voltage: 

16 to 33 VDC (VFWR)

Standby Current: 

500 μA maximum

Alarm Current: 

35 mA maximum (at high volume setting)

 

15 mA maximum (at low volume setting)

SLC Electrical Ratings

SLC Operating Voltage: 

15 to 32 VDC

SLC Standby Current: 

300 μA maximum

Sound Output

 

High Volume: 

Greater than 85 dBA minimum measured in a UL reverberant room at 10 feet, 24 Volts (in continuous tone)

Low Volume: 

Greater than 75 dBA minimum measured in a UL reverberant room at 10 feet, 24 Volts (in continuous tone)

The sounder base is intended for use with intelligent systems. The sounder 
base requires an external 24 VDC power supply. The connections for the 
external power supply and the communication loop are isolated to prevent 
electrical interaction between them. Refer to the panel manual for maximum 
allowable number of units per loop.

NOTE:

 For NFPA72 Installations, the Temporal 3 tone at high volume should 

be used for public mode evacuation.  The use of other tone styles and low 
volume level will be at the discretion of the local Authority Having Jurisdic-
tion (AHJ).

NOTE

: When not used as a supplementary evacuation system, the external 24 

VDC supply shall be treated as a component of the main power supply system 
and shall fall under the requirements of the main power supply system per 
NFPA 72.

Wiring guideLineS

All wiring must be installed in compliance with the National Electrical Code 
and the local codes having jurisdiction and must not be of such length or wire 
size which would cause the base to operate outside of its published specifica-
tions. The conductors used to connect smoke sensors to control panels and 
accessory devices should be color coded to reduce the likelihood of wiring 
errors. Improper connections can prevent a system from responding properly 
in the event of a fire.

Wire sizes up to 12 AWG (2.5 mm

2

) may be used with the base. The sounder 

base will be shipped with the screw terminals set for 14 AWG wiring. If 12 
AWG wire is to be used, back out the screws to allow the wire to fit beneath 
the clamping plates.For best system performance, the power (+ and -) wires 
and the communication circuit wires should be twisted pair or shielded cable 
installed in a separate grounded conduit to protect the communication loop 
from electrical interference.

I56-3387-00

5R

This model is compatible with Sytem Sensor Models MDL, MDL3R, MDLW, MDL3W and SYNC-1

Содержание B200S

Страница 1: ...ensor synchronization protocol or a separate synchronization mod ule In this scenario the sounder bases will have the ability to synchronize with other System Sensor horns horn strobes and chimes using the same power source Specifications Base Diameter 6 875 17 46 cm Base Height less sensor 2 0 5 08 cm Weight 0 50 lb 227 gm Operating Temperature Range Refer to applicable sensor Operating Temperatu...

Страница 2: ...st feature has been activated insert a small bladed screwdriver into the slot from the top and press down on the lever see Figure 6B This allows the detector to be rotated counterclockwise for removal The tamper resist feature can be defeated by breaking and removing the plastic lever from the base However this prevents the feature from being used again Testing and Maintenance Sensors and bases mu...

Страница 3: ...OL RESISTOR VALUE EOL RESISTOR MAY NOT BE NEEDED FOR CLASS A WIRING E O L HORN HORN HORN STROBE C0474 07 C1090 00 NOTE The wiring diagram below represents the most common wiring configurations Please consult your FACP manufacturer for panel specific wiring configu rations and special cases Additional Audible Visible devices may be connected to the same power supply or the the NAC output of the Fir...

Страница 4: ...ee Year Limited Warranty Department RA __________ 3825 Ohio Avenue St Charles IL 60174 Please include a note describing the malfunction and suspected cause of failure The Company shall not be obligated to repair or replace units which are found to be defective because of damage unreasonable use modifications or alterations occurring after the date of manufacture In no case shall the Company be lia...

Отзывы: