Make wire connections by stripping about 3/8” of insulation from the end of 
the wire. Then, slide the bare end of the wire under the appropriate clamping 
plate (See Figure 1), and tighten the clamping plate screw. Do NOT loop the 
wire under the clamping plate (See Figure 2) The wiring diagram for a typical 
2-wire intelligent system is shown in Figure 4.

For system monitoring - for terminals 2, 3, 4, and 5, do not use looped wire 
under terminals.  Break wire run as shown in Figure 2 to provide monitoring 
of connections.

B200S TerminaLS

No. Function
1.  Not Used
2.  Positive (+) Comm. Line In and Out
3.  Negative (-) Comm. Line In and Out
4.  External Supply Positive (+)
5.  External Supply Negative (-)
6.  Remote Annunciator 

mOunTing

Mount the B200S mounting plate directly to an electrical box. The plate will 
mount directly to 4˝ square (with and without plaster ring), 4˝ octagon, 3 

1

/

2

˝ 

octagon, single gang or double gang junction boxes.

1. Connect field wiring to terminals, as shown in Figure 1 and 2.
2. Attach the mounting plate to the junction box as shown in Figure 3.
3.  To mount the sounder base, hook the tab on the sounder base to the groove 

on the mounting plate.

4.  Then, swing the sounder base into position to engage the pins on the  

product with the terminals on the mounting plate.

5. Secure the sounder base by tightening the mounting screws.
6.  Install a compatible smoke sensor as described in the installation manual 

for the sensor.

Tamper reSiSTanT FeaTure

NOTE: Do not use the tamper-resist feature if the removal tool is to be used. 
This detector base includes a tamper-resist feature that prevents its removal 
from the base without the use of a tool. To activate this feature, break the tab 
from the detector base as shown in Figure 6A. Then, install the detector. To 
remove the detector from the base once the tamper-resist feature has been 
activated, insert a small-bladed screwdriver into the slot from the top and 
press down on the lever (see Figure 6B). This allows the detector to be rotated 
counterclockwise for removal. The tamper-resist feature can be defeated by 
breaking and removing the plastic lever from the base. However, this prevents 
the feature from being used again.

TeSTing and mainTenanCe

Sensors and bases must be tested after installation and as an integral part of a 
periodic maintenance program. Test the B200S as follows: 

NOTE: Before testing, notify the proper authorities that the smoke sensor 
system is undergoing maintenance and, therefore, will be temporarily out of 
service. Disable the system undergoing maintenance to prevent unwanted 
alarms.
1.  Via the fire alarm control panel, command the individual B200S to activate 

using the associated sensor address. That sounder base should sound in 
approximately five seconds.

2.  Via the fire alarm control panel, command all B200S sounder bases to acti-

vate using group communication to all associated addresses. All devices on 
the loop should sound, and if a temporal tone is commanded, the tones can 
be synchronized to each other.

NOTE: Synchronization requires a power supply capable of producing the Sys-
tem Sensor synchronization pulses.

When performing maintenance on connected smoke sensors, carefully note 
the location and address of each removed sensor. When re-installed, the 
B200S will confirm that address of the sensor matches the address stored in 
the sounder base memory. If there is a mismatch, this will be communicated 
to the fire alarm control panel and the sounder base can be commanded to 
chirp at regular intervals until the correct head is installed.

If a replacement head is installed or address changes are required, the mis-
match may be resolved at the panel by commanding the B200S sounder base 
to re-enter its address learning mode and adopting the address of the new 
sensor.

Figure 3: mOunTing

Figure 2:

C0471-07

C0473-00

C0891-07

Figure 1: 

1

2

3

4

5

6

CAUTION

Содержание B200S

Страница 1: ...ensor synchronization protocol or a separate synchronization mod ule In this scenario the sounder bases will have the ability to synchronize with other System Sensor horns horn strobes and chimes using the same power source Specifications Base Diameter 6 875 17 46 cm Base Height less sensor 2 0 5 08 cm Weight 0 50 lb 227 gm Operating Temperature Range Refer to applicable sensor Operating Temperatu...

Страница 2: ...st feature has been activated insert a small bladed screwdriver into the slot from the top and press down on the lever see Figure 6B This allows the detector to be rotated counterclockwise for removal The tamper resist feature can be defeated by breaking and removing the plastic lever from the base However this prevents the feature from being used again Testing and Maintenance Sensors and bases mu...

Страница 3: ...OL RESISTOR VALUE EOL RESISTOR MAY NOT BE NEEDED FOR CLASS A WIRING E O L HORN HORN HORN STROBE C0474 07 C1090 00 NOTE The wiring diagram below represents the most common wiring configurations Please consult your FACP manufacturer for panel specific wiring configu rations and special cases Additional Audible Visible devices may be connected to the same power supply or the the NAC output of the Fir...

Страница 4: ...ee Year Limited Warranty Department RA __________ 3825 Ohio Avenue St Charles IL 60174 Please include a note describing the malfunction and suspected cause of failure The Company shall not be obligated to repair or replace units which are found to be defective because of damage unreasonable use modifications or alterations occurring after the date of manufacture In no case shall the Company be lia...

Отзывы: