background image

D150-01-00

2

I56-599-03R

The B116LP base is intended for use in 2-wire systems,
with screw terminals provided for power and relay contact
connections. These bases MUST be current limited by the
system control panel in the alarm state.

Mounting

This detector base mounts directly to 3-1/2-inch and 4-
inch octagon boxes, and 4-inch square boxes (with or with-
out plaster rings). To mount, remove decorative ring by
turning it in either direction to unhook the snaps, then sep-
arate the ring from the base. Install the base to the box
using the screws supplied with the junction box and the
appropriate mounting slots in the base. Place decorative
ring onto base, then turn in either direction until the ring
snaps in place (see Figure 1).

Installation Guidelines

All wiring must be installed in compliance with the
National Electrical Code and the local codes having
jurISdiction. Proper wire gauges should be used. The con-
ductors used to connect smoke detectors to control panels
and accessory devices should be color-coded to prevent
wiring mistakes. Improper connections can prevent a sys-
tem from responding properly in the event of a fire.

For signal wiring (the wiring between inter-connected
detectors), it is recommended that the wire be no smaller
than 18 gauge. Wire sizes up to 12 gauge may be used with
the base. For best system performance, the power (+) and
(–) loop wires should be twisted pair and installed in sep-
arate grounded conduit to protect the loop from extraneous
electrical interference.

Smoke detectors and alarm system control panels have
specifications for allowable loop resistance. Consult the
control panel manufacturer’s specifications for the total
loop resistance allowed for the particular model control
panel being used before wiring the detector loops.

Locate installations where normal ambient temperatures do
not exceed 100°F.

Wiring Instructions

For system supervision — For terminals 2, 3, and 5 do not
use looped wire under terminals. Break wire run to provide
system supervision of connections.

Wire connections are made by simply stripping insulation
from the end of the wire, sliding the bare end of the wire
under the clamping plate, and tightening the clamping
plate screw. Use the strip gauges molded into the inside

CAUTION

and underside of the base for ease of wiring to terminals 1
through 5, and to terminals 12 through 14, respectively.

System Sensor smoke detectors and mounting bases are
marked with a compatibility identifier located as the last
digit of a five digit code stamped on the back of the prod-
uct. Connect detectors/mounting bases only to compatible
control units as indicated in System Sensor’s compatibility
chart which contains a current list of UL listed control units
and detector head/base combinations. A copy of this list is
available from System Sensor upon request.

The zone wiring of the detector base should be checked
before the detector heads are installed in them. To make
this possible, this base contains a special spring-type short-
ing jumper. After a detector base is properly wired and
mounted on an electrical box, make sure that the jumper
spring is in contact with the base of Terminal 3. This tem-
porary connection shorts the positive-in and positive-out
leads and permits the wiring of the loop to be checked for
continuity.

SNAP ON 
DECORATIVE
RING

SCREWS (NOT
SUPPLIED)

DETECTOR
BASE

BOX (NOT
SUPPLIED)

SHORTING
SPRING

Figure 1. Mounting base to box:

A78-1175-01

Содержание B116LP

Страница 1: ...ure Range 0 to 49 C 32 to 120 F US and Canadian Installations 10 to 60 C 14 to 140 F European Installations Operating Humidity Range 10 to 93 Relative Humidity Electrical Ratings includes base and detector System Voltage 24 VDC Maximum Ripple Voltage 4 Volts peak to peak Start up Capacitance 0 02µF Maximum Standby Ratings 15 VDC Minimum 35 VDC Maximum 120 µA Maximum Alarm Ratings 8 V Minimum at 16...

Страница 2: ...l panel manufacturer s specifications for the total loop resistance allowed for the particular model control panel being used before wiring the detector loops Locate installations where normal ambient temperatures do not exceed 100 F Wiring Instructions For system supervision For terminals 2 3 and 5 do not use looped wire under terminals Break wire run to provide system supervision of connections ...

Страница 3: ...ring diagram POWER LOOP 2 WIRE CONTROL PANEL POWER LOOP 3 2 4 5 1 12 13 14 COM CONTACT N C AUXILIARY N O FORM C E O L CLASS A OPTIONAL WIRING A78 1577 00 remove the detector from the base once the tamper resist ance feature has been activated place a small bladed screwdriver into the small hole on the side of the base and push plastic lever away from the detector head see Figure 3B This will allow...

Страница 4: ... 800 SENSOR2 736 7672 for a Return Authorization number send defective units postage prepaid to System Sensor Repair Department RA __________ 3825 Ohio Avenue St Charles IL 60174 Please include a note describing the malfunction and suspected cause of failure The Company shall not be obligated to repair or replace units which are found to be defective because of damage unreasonable use modification...

Отзывы: