CAUTION

Once all the detector bases have been wired and mounted,
and the loop wiring has been checked, the detector heads
may be installed in the bases. The shorting spring in the
base will disengage automatically when the detector head
is removed from the base. DO NOT remove the shorting
spring since it reengages as the detector head is fully
turned into the base, completing the circuit.

Tamper-resistance Feature

Do NOT use the tamper-resistance feature if the XR2
Removal Tool will be used.

This detector base includes a tamper-resistance feature that
prevents removal of the detector without the use of a tool. 

To  activate this feature, break off the tab on the detector
base shown in Figure 3A, then install the detector. To

D150-01-00

3

I56-599-03R

Figure 2. Typical wiring diagram:

(+) POWER LOOP

2-WIRE CONTROL PANEL

(–) POWER LOOP

3

2

4

5

1

12

13

14

COM CONTACT
N.C. AUXILIARY
N.O. FORM C

E

O

L

CLASS A OPTIONAL WIRING

A78-1577-00

remove the detector from the base once the tamper-resist-
ance feature has been activated, place a small-bladed
screwdriver into the small hole on the side of the base and
push plastic lever away from the detector head (see Figure
3B). This will allow the detector to be rotated counter-
clockwise for removal.

NOTE:

Head removal after the tamper-resistance feature
has been activated requires removal of the decora-
tive ring.

The tamper-resistance feature can be defeated by breaking
and removing the plastic lever from the base, however this
prevents using the feature again.

PLASTIC LEVER

BREAK TAB AT
DOTTED LINE BY
TWISTING TOWARD
CENTER OF BASE.

USE SMALL-BLADED
SCREWDRIVER TO
PUSH PLASTIC LEVER
IN DIRECTION OF
ARROW.

A78-1175-03

Figure 3B. Removing detector head from base:

Figure 3A. Activating tamper-resistance feature:

Содержание B116LP

Страница 1: ...ure Range 0 to 49 C 32 to 120 F US and Canadian Installations 10 to 60 C 14 to 140 F European Installations Operating Humidity Range 10 to 93 Relative Humidity Electrical Ratings includes base and detector System Voltage 24 VDC Maximum Ripple Voltage 4 Volts peak to peak Start up Capacitance 0 02µF Maximum Standby Ratings 15 VDC Minimum 35 VDC Maximum 120 µA Maximum Alarm Ratings 8 V Minimum at 16...

Страница 2: ...l panel manufacturer s specifications for the total loop resistance allowed for the particular model control panel being used before wiring the detector loops Locate installations where normal ambient temperatures do not exceed 100 F Wiring Instructions For system supervision For terminals 2 3 and 5 do not use looped wire under terminals Break wire run to provide system supervision of connections ...

Страница 3: ...ring diagram POWER LOOP 2 WIRE CONTROL PANEL POWER LOOP 3 2 4 5 1 12 13 14 COM CONTACT N C AUXILIARY N O FORM C E O L CLASS A OPTIONAL WIRING A78 1577 00 remove the detector from the base once the tamper resist ance feature has been activated place a small bladed screwdriver into the small hole on the side of the base and push plastic lever away from the detector head see Figure 3B This will allow...

Страница 4: ... 800 SENSOR2 736 7672 for a Return Authorization number send defective units postage prepaid to System Sensor Repair Department RA __________ 3825 Ohio Avenue St Charles IL 60174 Please include a note describing the malfunction and suspected cause of failure The Company shall not be obligated to repair or replace units which are found to be defective because of damage unreasonable use modification...

Отзывы: