background image

SS-400-000 

I56-3065-000R

NOTE:

 This procedure should only be used in an emergency, and 

it is not intended as a permanent substitute for ordering the cor-
rect length tubes.

Step 6. Field Wiring

Wiring Installation Guidelines

All  wiring  must  be  installed  in  compliance  with  the  local  codes 
having jurisdiction. Proper wire gauges should be used. The con-
ductors used to connect smoke detectors to control panels and ac-
cessory devices should be color-coded to prevent wiring mistakes. 
Improper  connections  can  prevent  a  system  from  responding 
properly in the event of a fire.
For  signal  wiring,  (the  wiring  between  interconnected  detectors 
or  from  detectors  to  auxiliary  devices),  it  is  recommended  that 
single-conductor  wire  be  no  smaller  than  16  gauge  (1.5  square 
mm), and that two- or three-conductor wire be no smaller than 
18 gauge (1.0 square mm). The last foot or so of conduit should 
be  flexible  steel  conduit  (available  in  electrical  supply  houses) 
which  facilitates  easier  installation  and  puts  less  strain  on  the 
conduit holes in the housing. Solid conduit connections may be 
used if desired.
Smoke  detectors  and  alarm  system  control  panels  have  specifi-
cations  for  allowable  loop  resistance.  Consult  the  control  panel 
manufacturer’s specifications for the total loop resistance allowed 
for  the  particular  model  control  panel  being  used  before  wiring 
the detector loop.

Wiring Instructions

The 7251DH is designed for easy wiring. The housing provides a 
terminal strip with clamping plates. Wiring connections are made 
by stripping approximately 

1

/

2

˝ of insulation from the end of the 

wire,  sliding  this  bare  end  under  the  plate,  and  tightening  the 
clamping plate screw.

Step 7. Install the Filters

Most duct installations are subject to dust accumulation. System 
filters  remove  a  large  percentage  of  this  contamination,  but 
cannot  remove  all  of  it.  Dust  inside  the  duct  detector  causes 
problems. First, very fine particles of dust can enter the detector 
sensing  chamber  and  cause  the  unit  to  go  into  alarm.  Second, 

AIR FLOW

DIRECTION

DETECTOR

HOUSING

DOTS INDICATE POSITION OF

SAMPLING TUBE HOLES

AIR FLOW

DIRECTION

DETECTOR

HOUSING

INLET

TUBE

EXHAUST

TUBE

AIR FLOW

DIRECTION

EXHAUST

TUBE

INLET

TUBE

INLET

TUBE

EXHAUST

TUBE

DETECTOR

HOUSING

AIR FLOW

DIRECTION

EXHAUST

TUBE

INLET

TUBE

DETECTOR

HOUSING

A.

B.

C.

D.

HORIZONTAL MOUNTING OF HOUSING

VERTICAL MOUNTING OF HOUSING

Figure 5. Tube mounting configurations with varying air flow direction and orientation of detector housing. 
Vertical as well as horizontal mounting is acceptable:

H0109-00

the  accumulation  of  dust  and  dirt  necessitates  a  more  frequent 
periodic  cleaning  schedule,  which  can  result  in  substantial  cost 
and/or down time.
Disposable sampling tube filters can greatly reduce the nuisance 
alarms  caused  by  dust,  and  can  also  significantly  extend  the 
maintenance interval. To install the sampling tube filters, simply 
push the filter adapter into the exhaust tube, and then push the 
filter onto the adapter tube on the left, as shown in Figure 6. Then 
install the other filter over the end of the inlet sampling tube.

CAUTION

Filters require periodic cleaning or replacement, depending on the 
amount of dust and dirt accumulated. Visually inspect the filters 
at least quarterly; inspect them more often if the dust accumula-
tion warrants it. Replacement filters can be ordered from System 
Sensor (exhaust tube/intake tube filter P/N F36-05-00).

The filters do not substantially affect smoke performance under 
normal conditions. There is very little restriction of smoke entry 
even when up to 90% of the filter is clogged. Visual inspection 
is  usually  adequate  to  determine  whether  the  filters  should  be 
replaced because such a high percentage of contamination is re-
quired to affect performance. 
However,  if  further  testing  is  desired,  a  Dwyer  Model  460  (or 
equivalent) Differential Pressure Gauge may be used. Simply com-
pare the differential pressure readings with and without the filters 
attached. There should be little or no difference. If the difference 
exceeds 10%, replace the filters. In no case, however, should the 
pressure differential be less than 0.01 inches of water or greater 
than 1.2 inches of water.

Step 8. Perform Detector Check 
8.1 Air Flow

1.   To verify sufficient sampling of ducted air, use a manometer 

to  measure  the  differential  pressure  created  from  air  flow 
across the sampling tubes. The pressure should measure no 
less than 0.01 inches of water and no greater than 1.20 inches 
of water.

firealarmresources.com

Содержание 7251DH

Страница 1: ...Station Specifications Length 14 5 inches 36 7 cm Width 5 inches 12 7 cm Depth 3 5 inches 8 9 cm Weight 2 8 lbs 1 1 kg Operating Temperature Range 32 to 100 F 0 to 38 C Operating Humidity Range 10 to 93 Relative Humidity Duct Air Velocity 300 4000 ft min Voltage Range 15 32 VDC Peak Standby Current nominal 230uA at 24 VDC no communication 330uA at 24 VDC one communication every 5 sec with LED enab...

Страница 2: ...uct Air Flow Direction and Velocity The 7251DH is designed to be used in air handling systems having air velocities of 300 to 4000 feet per minute Be sure to check en gineering specifications to ensure that the air velocity in the duct falls within these parameters If necessary an Alnor Model 6000 P velocity meter Dwyer 460 differential pressure gauge or their equivalent may be used to check the a...

Страница 3: ... Figure 3B Installation of foam gaskets over sam pling tube bushings B Installation for Ducts More Than 8 Feet Wide NOTE To install inlet tubes in ducts more than 8 feet wide work must be performed inside the air duct Sampling of air in ducts wider than 8 feet is accomplished by using the ST 10 inlet sam pling tube Install the inlet tube as follows 1 Any tube over 3 feet long that doesn t protrude...

Страница 4: ... EXHAUST TUBE AIR FLOW DIRECTION EXHAUST TUBE INLET TUBE INLET TUBE EXHAUST TUBE DETECTOR HOUSING AIR FLOW DIRECTION EXHAUST TUBE INLET TUBE DETECTOR HOUSING A B C D HORIZONTAL MOUNTING OF HOUSING VERTICAL MOUNTING OF HOUSING Figure 5 Tube mounting configurations with varying air flow direction and orientation of detector housing Vertical as well as horizontal mounting is acceptable H0109 00 the a...

Страница 5: ...all the RTS451 RTS451KEY test coil connect the device as shown in Figure 11 wire runs must be limited to 25 ohms or less per interconnecting wire Place the coil in the detector housing with the arrow facing up and pointing toward the detector as in Figure 11 Attach the coil leads to the housing terminals as shown polarity is not important Firmly screw the bracket in place over the test coil 8 4 Tr...

Страница 6: ...ine Comm Line Alarm Initiation Loop Comm Line ULC Listed Control Panel 1st Detector in Loop 2nd Detector in Loop The RTS451 RTS451KEY test coil circuit requires an external 24VDC power supply which must be UL listed Figure 9C System wiring diagram for duct detectors using a ULC listed control panel Figure 9A Figure 9B H0542 00 DETECTOR HEAD TEST COIL H0292 00 Figure 11 RTS451 RTS451KEY test coil i...

Страница 7: ...y vacuuming or blowing out dust and particles 5 Replace the sensing chamber cover aligning the arrow on the top with arrow on the printed circuit board 6 To replace the screen place it over the chamber assembly turning it until it snaps into place 7 Replace the cover using the LEDs to align the cover and then gently pushing it until it locks into place 8 Reinstall the detector 9 Test the detector ...

Страница 8: ...T LOG Detector Identification Information Manufacturer Detector Model Serial Number Date Installed Description of Detector Location The Results and Maintenance Data Date Tested Test Description Test Results Maintenance Performed Comments firealarmresources com ...

Отзывы: