Step 5. Install the Inlet Tube

The inlet tube (shown in Figure 4) is identified by a series of air 
inlet holes on the tube. This tube must be purchased separately. 
Order the correct length, as specified in Table 1, for the width of 
the duct where it will be installed. The exhaust tube is molded 
into the base of the duct housing.
The inlet tube is always installed in the right house bushing, with 
the air inlet holes facing into the air flow. To assure proper instal-
lation, the tube mounting flange is marked with arrows. Mount 
the inlet tube so that the arrows point into the air flow. Figure 5 
shows the various combinations of tube mounting configurations 
with respect to air flow.

Figure 4. Air duct detector inlet sampling tube:

INLET

TUBE

END

PLUG

AIR HOLES

ARROWS

MUST FACE

INTO AIR FLOW

AIR FLOW DIRECTION

FLANGE

H0108-00

A. Installation for Ducts Less Than 8 Feet Wide

1.   Any inlet tube over 3 feet long must be supported on the op-

posite side of the duct detector housing.

2.   If the inlet tube is longer than the width of the air duct, drill a 

3

/

4

˝ hole in the duct directly opposite the hole already cut for 

the inlet tube. If the inlet tube is shorter than the width of the 
air duct, install the end cap into the inlet tube (see Figure 4).

3.   Slide the inlet tube into the right housing bushing. Position 

the tube so that the arrows point into the air flow.

4.   Secure the tube flange to the housing bushing with the two 

#6 self-tapping screws.

5.   For  tubes  longer  than  the  width  of  the  air  duct,  the  tube 

should extend out of the opposite side of the duct. If there are 
more than 2 holes in the section of the tube extending out of 
the duct, select a different tube length using Table 1. Other-
wise, trim the end of the tube protruding through the duct so 
that 1 to 2 inches of the tube extends outside the duct. Plug 
this end with the tube end plug and tape closed any holes in 
the  protruding  section  of  the  tube.  Be  sure  to  seal  the  duct 
when the tube protrudes.

WARNING

In no case should more than 2 air inlet holes be cut off the tube. 
There must be a minimum of 10 holes in the tube exposed to the 
air stream.

HOLE B

HOLE A

DUCT

WALL

SPEED

NUT

SCREW HOLES FOR ATTACHING

DETECTOR HOUSING TO DUCT

FOAM GASKETS

EXHAUST TUBE

(EXTENSION BUSHING)

DUCT DETECTOR

HOUSING

O-RINGS

MOUNTING

SCREWS

INLET SAMPLING

TUBE BUSHING

Figure 3A. Speed nut mounting location: 

H0116-00

H0238-00

Figure 3B. Installation of foam gaskets over sam-
pling tube bushings:

B. Installation for Ducts More Than 8 Feet Wide

NOTE:

 To install inlet tubes in ducts more than 8 feet wide, work 

must be performed inside the air duct. Sampling of air in ducts 
wider than 8 feet is accomplished by using the ST-10 inlet sam-
pling tube.
Install the inlet tube as follows:
1.   Any tube (over 3 feet long) that doesn’t protrude through the 

duct (on the side opposite the housing) must be supported by 
other means.

2.   Drill a 

3

/

4

˝ hole in the duct directly opposite the hole already 

drilled for the inlet tube.

3.   Slide  the  inlet  tube  with  the  flange  into  the  right  housing 

bushing. Position the tube so that the arrows point into the 
air flow. Secure the tube flange to the housing bushing with 
the two #6 self-tapping screws.

4.   From  inside  the  duct,  couple  the  other  section  of  the  inlet 

tube  to  the  section  already  installed  using  the 

1

/

2

˝  conduit 

fitting supplied. Make sure the holes on both of the air inlet 
tubes are lined up facing the air flow.

5.   Trim the end of the tube protruding through the duct so that 

1 to 2 inches of the tube extends outside the duct. Plug this 
end with the tube end cap and tape closed any holes in the 
protruding section of the tube. Be sure to seal the duct when 
the tube protrudes.

NOTE:

 An alternate method to using the ST-10 is to use two ST-5 

inlet tubes. Remove the flange from one of the tubes and install 
as described above. After the installation, use electrician’s tape to 
close off some of the sampling holes so that there are a total of 12 
holes spaced as evenly as possible across the width of the duct.

NOTE:

 Air currents inside the duct may cause excessive vibration. 

This vibration can slowly open the seal around the tube and per-
mit air to escape. To prevent this from occurring, a 3˝ floor flange, 
available  at  most  plumbing  supply  houses,  may  be  used.  This 
flange/connector  mounting  technique  makes  the  initial  installa-
tion  easier  because  a  1˝  to  1

1

/

4

˝  hole  may  be  drilled  where  the 

flange/connector will be used. It is easier to push the inlet tube 
through the larger hole.

Modification of Inlet Sampling Tubes

There  may  be  applications  where  duct  widths  are  not  what  is 
specified  for  the  installation.  In  such  cases,  it  is  permissible  to 
modify  an  inlet  sampling  tube  that  is  longer  than  necessary  to 
span the duct width.
Use  a  0.193-inch  diameter  (#11)  drill  and  add  the  appropriate 
number  of  holes  so  that  the  total  number  of  holes  exposed  to 
the air flow in the duct is 10 to 12. Space the additional holes as 
evenly as possible over the length of the tube.

firealarmresources.com

Содержание 7251DH

Страница 1: ...Station Specifications Length 14 5 inches 36 7 cm Width 5 inches 12 7 cm Depth 3 5 inches 8 9 cm Weight 2 8 lbs 1 1 kg Operating Temperature Range 32 to 100 F 0 to 38 C Operating Humidity Range 10 to 93 Relative Humidity Duct Air Velocity 300 4000 ft min Voltage Range 15 32 VDC Peak Standby Current nominal 230uA at 24 VDC no communication 330uA at 24 VDC one communication every 5 sec with LED enab...

Страница 2: ...uct Air Flow Direction and Velocity The 7251DH is designed to be used in air handling systems having air velocities of 300 to 4000 feet per minute Be sure to check en gineering specifications to ensure that the air velocity in the duct falls within these parameters If necessary an Alnor Model 6000 P velocity meter Dwyer 460 differential pressure gauge or their equivalent may be used to check the a...

Страница 3: ... Figure 3B Installation of foam gaskets over sam pling tube bushings B Installation for Ducts More Than 8 Feet Wide NOTE To install inlet tubes in ducts more than 8 feet wide work must be performed inside the air duct Sampling of air in ducts wider than 8 feet is accomplished by using the ST 10 inlet sam pling tube Install the inlet tube as follows 1 Any tube over 3 feet long that doesn t protrude...

Страница 4: ... EXHAUST TUBE AIR FLOW DIRECTION EXHAUST TUBE INLET TUBE INLET TUBE EXHAUST TUBE DETECTOR HOUSING AIR FLOW DIRECTION EXHAUST TUBE INLET TUBE DETECTOR HOUSING A B C D HORIZONTAL MOUNTING OF HOUSING VERTICAL MOUNTING OF HOUSING Figure 5 Tube mounting configurations with varying air flow direction and orientation of detector housing Vertical as well as horizontal mounting is acceptable H0109 00 the a...

Страница 5: ...all the RTS451 RTS451KEY test coil connect the device as shown in Figure 11 wire runs must be limited to 25 ohms or less per interconnecting wire Place the coil in the detector housing with the arrow facing up and pointing toward the detector as in Figure 11 Attach the coil leads to the housing terminals as shown polarity is not important Firmly screw the bracket in place over the test coil 8 4 Tr...

Страница 6: ...ine Comm Line Alarm Initiation Loop Comm Line ULC Listed Control Panel 1st Detector in Loop 2nd Detector in Loop The RTS451 RTS451KEY test coil circuit requires an external 24VDC power supply which must be UL listed Figure 9C System wiring diagram for duct detectors using a ULC listed control panel Figure 9A Figure 9B H0542 00 DETECTOR HEAD TEST COIL H0292 00 Figure 11 RTS451 RTS451KEY test coil i...

Страница 7: ...y vacuuming or blowing out dust and particles 5 Replace the sensing chamber cover aligning the arrow on the top with arrow on the printed circuit board 6 To replace the screen place it over the chamber assembly turning it until it snaps into place 7 Replace the cover using the LEDs to align the cover and then gently pushing it until it locks into place 8 Reinstall the detector 9 Test the detector ...

Страница 8: ...T LOG Detector Identification Information Manufacturer Detector Model Serial Number Date Installed Description of Detector Location The Results and Maintenance Data Date Tested Test Description Test Results Maintenance Performed Comments firealarmresources com ...

Отзывы: