background image

D200-09-00 

I56-0058-004R

C0100-00

3

2

1

3

2

1

+

+

OPTIONAL RETURN LOOP

REMOTE ANNUNCIATOR

+

CLeaning

It is recommended that the detector be removed from its mounting base to 
facilitate cleaning. The detector is cleaned as follows:

NOTE:  Before  removing  the  detector,  notify  the  proper  authorities  that  the 
smoke  detector  system  is  undergoing  maintenance  and  will  be  temporarily 
out of service. Disable the zone or system undergoing maintenance to prevent 
unwanted alarms.
1.   Remove  the  detector  cover  by  prying  away  the  four  side  tabs  with  a 

small-bladed screwdriver, and then pulling the cover from the base.

2.   Vacuum the screen carefully without removing it. If further cleaning is 

required continue with Step 3, otherwise skip to Step 7.

3.   Remove  the  screen/chamber  cover  assembly  by  pulling  it  straight  out 

(see Figure 4).

4.  Clean the chamber by vacuuming or blowing out dust and particles.
5.   Replace the sensing chamber cover, aligning the arrow on the top with 

arrow on the printed circuit board.

6.   To replace the screen, place it over the chamber assembly, turning it until 

it snaps into place.

7.   Replace  the  cover  using  the  LEDs  to  align  the  cover  and  then  gently 

pushing it until it locks into place. 

8.  Reinstall the detector.
9.  Test the detector as described in TESTING.
10.  Reconnect disabled circuits.
11.  Notify the proper authorities that the system is back on line.

FigUre 1. Wiring diagram:

CAUTION

Do not loop wire under terminal 1 or 2. Break wire run to pro-
vide supervision of connection.

UL Listed Compatible

Control Panel

LaSer SaFetY inFOrmatiOn

This smoke detector does not produce any hazardous laser radiation and is 
certified as a Class 1 laser product under the U.S. Department of Health and 
Human  Services  (DHHS)  Radiation  Performance  Standard  according  to  the 
Radiation Control for Health and Safety Act of 1968.

Any radiation emitted inside the smoke detector is completely within the pro-
tective housings and external covers. The laser beam cannot escape from the 
detector during any phase of operation.

The Center of Devices and Radiological Health (CDRH) of the U.S. Food and 
Drug Administration implemented regulations for laser products on August 2, 
1976. These regulations apply to laser products manufactured after August 1, 
1976. Compliance is mandatory for products marketed in the United States.

CAUTION

Use of controls, adjustments, or performance of procedures other than those 
specified in this manual may result in hazardous radiation exposure.

SPeCiaL nOte regarding SmOke deteCtOr gUardS

Smoke detectors are not to be used with detector guards unless the combina-
tion has been evaluated and found suitable for that purpose.

Содержание 7251

Страница 1: ...te the communication line 5 Test the sensor s as described in the TESTING section of this manual Specifications Operating Voltage Range 15 to 32 VDC Standby Current 330µA 24 VDC one communication every 5 sec with LED blink enabled Max Alarm Current LED on 6 5 mA 24 VDC Operating Humidity Range 10 to 93 Relative Humidity noncondensing Operating Temperature Range 0 C to 38 C 32 F to 100 F U S 10 C t...

Страница 2: ...r 9 Test the detector as described in TESTING 10 Reconnect disabled circuits 11 Notify the proper authorities that the system is back on line Figure 1 Wiring diagram CAUTION Do not loop wire under terminal 1 or 2 Break wire run to pro vide supervision of connection UL Listed Compatible Control Panel Laser Safety Information This smoke detector does not produce any hazardous laser radiation and is ...

Страница 3: ... Test magnet position TENS ONES 9 8 7 6 5 4 3 2 1 0 9 8 7 6 5 4 3 2 1 0 D N T N I A P T O O T E S T M A G N E T TEST MAGNET PAINTED SURFACE MAGNET TEST MARKER LED STATUS INDICATORS PAINTED SURFACE C0170 00 Figure 4 Sensor assembly SENSOR COVER COVER REMOVAL TABS SCREEN ASSEMBLY SENSING CHAMBER ...

Страница 4: ...art 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a ...

Отзывы: