4.5.3
IO Remote Control
The SysmikScaNetwork sets up a TCP connection to an IO server, to access the IO
terminals. The property Address defines address and port of this server. Default is
the local address
127.0.0.1:2015
, which establishes contact to the local IO
server. But it is also possible to connect to an IO server of a different device by
configuring its address here.
Fig. 4.5.3.1:
Configuration of the IO server to be contacted
To do so the remote access must be activated first. In Workbench an allowed
remote control address can be configured via
Station
Config
Drivers
SysmikScaIoNetwork
localPlatform
IoRemoteAddr
Address setting
Description
invalid address (empty string)
remote control deactivated (default)
valid IP address
IO server accepts only accesses from this IP address
255.255.255.255
any IP address can access the IO server
Table 4.5.3.1:
Address settings for IO server access
Furthermore, the port number of the IO server can be defined via
Station
Config
Drivers
SysmikScaIoNetwork
localPlatform
Io Port
Fig. 4.5.3.2:
Configuration of IO server
4.5.4
Sedona Integration
Data points of the local Sedona application can be added to Niagara via the Sedona
driver. If a parallel operation of Niagara and Sedona is not desired, Sedona can be
deactivated via
Station
Config
Drivers
SysmikScaIoNetwork
localPlatform
SedonaEnabled