Hardware Manual of 30kW Servo Drive II (SPD-32B1-300)
Wiring and Signal
(
30kW SPD
)
–
53
12.8 Connector and Terminal Definition (30kW SPD)
Name
Terminal
Description
Main Loop Power Input Terminal
R, S, T
Connects to 3-phase AC
Controller Power
L1, L2
Optional L1 and L2, depending on wiring schematic
Motor Power Input Terminal
U, V, W
Connects to motor
Regenerator Terminal
P, B2
Connects to external regenerative resistor
Serial Communication Interface
M2
Connects to host controller (either M2 or M3)
Serial Communication Interface
M3A, M3B
Connects to host controller (either M2 or M3)
USB Port
mini USB
Connects to PC's USB port
General Signal IO
Connects to host controller
Safe Torque Off (STO)
STO
terminal
Encoder Feedback
ENC1
Connects to motor encoder
2nd Encoder Feedback
ENC2
Connects to loaded encoder
Ground Terminal
Connects to ground
Wiring Precautions:
Keep the six power lines R, S, T and U, V, W away from other signal lines, at least a 30 cm distance if possible.
When the power is cut off,
the drive's internal capacitor still contains a large amount of charge--
do NOT
touch the six power lines R, S, T, and U, V, W. Please wait until the charging light goes out.
When lengthening the encoder cable, apply twisted pair cabling to the encoder cable and the grounding
signal cable. Do not exceed a length of 20 m (65.62 in or 14 ft); if it is absolutely necessary to do so, please use
a signal line with twice the wire diameter in order to minimize signal attenuation.
Please wire according to relevant regulations. Select the wire diameter according to motor wattage, as
follows: