Section III
Operation
006-0007097 02/14/2019
Rev E
32 of 52
UPS-1250DC Guide www.synqor.com
Audible alarm
For critical situations a pattern of audible tones will be repeated every 5 seconds, according to
the table below. This audible alarm can be silenced by holding the ON/OFF switch on the front
panel in the “UP” position until a chirp is heard. A new alarm condition will cause the audible
alarm to be reactivated. Contact Factory for instructions on how to permanently silence the
alarm.
Number of Tones in Pattern
Indication
One
UPS is Drawing Power From the Battery Pack
Two
Load Power is greater than or approaching 100%
Rated Power
Three
Fault Appears on the DC Output
UPS Must be Turned Off and Back On to Reset Fault
Four
UPS is Drawing Power From the Battery Pack and the
Remaining Charge is <10%
Hot Swapping the Battery Pack
The battery pack can be removed from the UPS and it, or another one, can be inserted into the
UPS without disrupting the delivery of power to the load as long as a source of input power is
available. This feature is referred to as “hot swapping” in the industry. It can be used to replace a
battery pack that needs servicing, or to replace a drained battery pack with a spare, fully charged
one if additional back-up protection must be ensured before the drained battery pack will have
time to be recharged.
Of course, if there is no source of input power available and the UPS is therefore drawing power
from the battery, then the removal of the battery pack would cause the UPS’s outputs to shut
down until a recharged battery pack is inserted.