Section IV
Multiple UPS Configurations
006-0007129 10/12/2018
Rev B
36 of 60
UPS-1500 3-Phase Guide
www.synqor.com
Parallel Configurations of the AC OUTPUTS: Up to 32 Unit “R” option
The “R” option adds a single pole electronic breaker to the hot wire of the AC OUTPUT. This breaker
allows for fault-tolerant, glitch-free operation of up to 32 UPS units in a multi-system. Single-Phase,
Split-Phase, and 3-Phase systems can be formed. These systems can be N+1 or N+M redundant on
each phase.
The block diagrams below show a summary of the different system configurations that can be made
using units with the “R” option. Please note that each multi-unit system requires its own unique
system CONFIGURATION (Single-Phase, Split-Phase, and 3-Phase) cable. Contact the SynQor factory
to purchase the system specific configuration cables. Note that configuration cables for two, three,
four and five unit Single-Phase parallel systems are offered as standard products.
Line 1
UPS Unit 1
(0°)
Line 2
UPS Unit 1
(180°)
Line 1
UPS Unit 2
(0°)
Line 2
UPS Unit 2
(180°)
Line 1
UPS Unit 16
(0°)
Line 2
UPS Unit 16
(180°)
Split-Phase Output System
Line 1
Neutral
Up t
o 1
6 units on Line 1
Up t
o 1
6 units on Line 2
* Configuration Cable
* AC Output
UPS Unit 1
UPS Unit 2
UPS Unit 32
Single-Phase Output System
Hot
Up t
o 32 units t
otal
* Configuration Cable
* AC Output
Neutral
Line 2
Phase A
UPS Unit 1
(0°)
Phase B
UPS Unit 1
(120°)
Phase A
UPS Unit 2
(0°)
Phase B
UPS Unit 2
(120°)
Phase A
UPS Unit 10
(0°)
Phase B
UPS Unit 10
(120°)
3-Phase Output System
(Y - Connection Only)
Phase A
Phase B
Phase C
Neutral
Up t
o 1
0 units on Phase A
Up t
o 1
0 units on Phase B
Up t
o 1
0 units on Phase C
* Configuration Cable
* AC Output
Phase C
UPS Unit 1
(240°)
Phase C
UPS Unit 2
(240°)
Phase C
UPS Unit 10
(240°)