SPECIFICATIONS
1 - Phase Line Voltage
190 - 240 (95-120) VAC
Frequency
50* - 60 Hz
High Voltage (% of setpoint)
Trip
110%
±
1%
Reset
107%
±
1%
Low Voltage (% of setpoint)
Trip
90%
±
1%
Reset
93%
±
1%
Trip Delay Time
Low Voltage
4 Seconds Fixed
High Voltage
4 Seconds Fixed
Restart Delay Time
After a complete power loss
1-500 Seconds Adjustable
Output Contact Rating - SPDT
Pilot Duty
480 VA @ 240 VAC
General Purpose
10 A @ 240 VAC
Power Consumption
6 Watts (maximum)
Weight
14 oz
Enclosure
Polycarbonate
Terminal
Torque
6 Inch-Pounds
Wire AWG
12 - 20 AWG
Safety Marks
UL
UL508 (File # E68520)
CE
IEC 60947-6-2
Standards Passed
Electrostatic Discharge (ESD)
IEC 1000-4-2, Level 3, 6 kv contact,
8 kv air
Radio Frequency Immunity, Radiated 159 MHz, 10 V/m
Fast Transient Burst
IEC 1000-4-4, Level 3, 3.5 kv input
power and controls
*NOTE: 50 Hz will increase all delay timers by 20%