TROUBLESHOOTING
SYMPTOM
LIGHT
PATTERN
SOLUTION
No lights are on.
The unit seems
completely dead.
N / A
Measure the voltage. If the voltage is below
75 VAC, the MotorSaver
does not have
enough power to operate its internal elec-
tronics.
If the voltage is correct, call SymCom at
1-800-843-8848 or 1-605-348-5580.
Red light is on
steady.
The voltage is out of tolerance. Measure
the input voltage. If the voltage is 7% above
or below the nominal voltage as selected
by the LINE VOLTAGE ADJUST, the
MotorSaver
is functioning properly. If the
voltage is within ±7% of the selected line
voltage, call SymCom at
1-800-843-8848 or 1-605-348-5580.
Green light blinks
and motor is not
running.
The MotorSaver
is in restart delay.
Green light is on
steady, but motor
does not start.
The MotorSaver
is in run mode. Ensure
other control devices are allowing the
motor to start. Check control circuit for
loose wires or malfunctioning switches.