SymCom Motor Saver 460-SP Скачать руководство пользователя страница 3

SETTINGS

1. Line voltage adjustment:  Rotate the 

“VOLTAGE ADJ. (VAC)”

 to the nominal

line voltage feeding the motor to be protected.

2. Restart delay adjustment:  Rotate the 

“RESTART (SEC)” 

adjustment to the

desired position.  The restart delay is the time between the MotorSaver®
seeing acceptable voltage and the MotorSaver® closing its output contacts.
For compressor applications, the restart delay should be set for the
approximate time it takes for the head pressure to bleed off of the
compressor.  For other applications, the restart delay is typically set between
2 and 10 seconds.

100

500

1

VOLTAGE ADJ. (VAC)

RESTART (SEC)

MODEL 460-SP

220

230

20

250

240

200

190

208

LED STATUS

RUN
RESTART DELAY
HIGH / LOW VOLTAGE

GREEN
GREEN

RED

2

1

4

5

6

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

Содержание Motor Saver 460-SP

Страница 1: ...or near the motor control panel If the location is wet or dusty the MotorSaver should be mounted in a NEMA 4 or 12 enclosure The MotorSaver can be mounted to a back panel using two 6 or 8 x 5 8 screw...

Страница 2: ...L VOLTAGE 24 240 VAC 460 SP FIGURE 1 CONTROL WIRING DIAGRAM LIGHT 3 Phase Voltage CONTROL VOLTAGE 24 240 VAC 460 SP FIGURE 2 ALARM WIRING DIAGRAM Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com...

Страница 3: ...torSaver closing its output contacts For compressor applications the restart delay should be set for the approximate time it takes for the head pressure to bleed off of the compressor For other applic...

Страница 4: ...e RESTART delay After the RESTART delay the MotorSaver will energize its output contacts and the green RUN light will illuminate If the contacts do not energize and the RUN light does not illuminate s...

Страница 5: ...voltage is 7 above or below the nominal voltage as selected by the LINE VOLTAGE ADJUST the MotorSaver is functioning properly If the voltage is within 7 of the selected line voltage call SymCom at 1 8...

Страница 6: ...480 VA 240 VAC General Purpose 10 A 240 VAC Power Consumption 6 Watts maximum Weight 14 oz Enclosure Polycarbonate Terminal Torque 6 Inch Pounds Wire AWG 12 20 AWG Safety Marks UL UL508 File E68520 CE...

Страница 7: ...tions please refer to the SymCom Terms and Conditions of Sale document DIMENSIONS Surge IEC IEC 1000 4 5 Level 3 4kv line to line Level 4 4kv line to ground ANSI IEEE C62 41 Surge and Ring Wave Compli...

Отзывы: