REMOTE RESET  

The R terminals can be connected to a normally open pushbutton to remotely reset a connected 
777-P/P1 overload.  

DIAGNOSTIC INDICATOR LIGHTS (CIO-EN) 

The unit is energized when 24 VDC is applied between V+ and V- on the 5-pin connector on the front 
of the CIO-EN module.  The MODBUS MODULE NETWORK STATUS (MNS) LED and OVERLOAD 
COMM. (OLC) STATUS LED will flash until communication is established. The MNS LED indicates 
the state of an upstream Modbus connection to the module. The OLC LED indicates the state of the 
overload connection to the module. For a complete description of the indicator LED’s see tables 2 
and 3 below: 

TABLE 2: MNS LED State Table 

For this state: 

LED is: 

To indicate: 

Not Powered 

Off 

The CIO-EN is not powered. 

Upstream Modbus/RTU 
Comm. Operational 

Green 

The CIO-EN is communicating with an upstream Modbus/RTU device 
and the CIO-EN is powered. 

Upstream Modbus/RTU 
Comm. NOT Operational 

Flashing 
Green 

The CIO-EN is powered but upstream communications are not 
established. 

TABLE 3: OLC LED State Table 

For this state 

LED is: 

To Indicate: 

Not Powered 

Off 

The CIO-EN is not powered. 

Overload Comm. 
Operational 

Green 

The CIO-EN is communicating with an overload device and the CIO-EN 
is powered. 

Overload Comm. NOT 
Operational 

Flashing 
Green 

The CIO-EN is powered but overload communications are not 
established. 

NOTE: If an unrecoverable error has occurred with the nonvolatile memory (which stores the 
device settings), the CIO-EN will enter a lockdown mode and flash both the OLC and MNS 
LEDs every second.  The remote reset input must be triggered in order to reset all settings to 
factory defaults.  The connected 777-P/P1 will not be reset when this occurs. 

The CIO-EN Ethernet jack on top of the unit contains LED’s to represent communication and activity 
over the network.  Tables 4 and 5 describe the LED functions. 

TABLE 4: Yellow Ethernet LED 

For this state: 

LED is: 

To indicate: 

No Link 

Off 

The CIO-EN is not connected to an Ethernet network. 

Active Link 

Solid 
Yellow 

The CIO-EN is connected to an Ethernet network. 

TABLE 5: Green Ethernet LED 

For this state 

LED is: 

To Indicate: 

No Network Activity 

Off 

The CIO-EN is not transmitting or receiving any data over 
Ethernet. 

Network is Actively 
Operational 

Green 

The CIO-EN is transmitting or receiving data over Ethernet. 

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

Содержание CIO-EN

Страница 1: ...INSTALLATION INSTRUCTIONS Revision B1 Rapid City SD USA 05 2009 MODEL CIO EN MODBUS TCP MODBUS RTU I O MODULE Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Страница 2: ...rly rated enclosure The module can be mounted to a back panel using screws or can be snapped onto a DIN rail 2 For Modbus RTU networks connect the three Modbus wires A B Shield to the 5 pin connector on the front of the CIO EN module 3 For communication with a SymCom overload connect the CIO EN to the side of a 777 P P1 via the 9 pin D SUB connector located on the side of the CIO EN NOTE Do not pl...

Страница 3: ...nnection SHIELD Shield Connection B RS 485 B Connection R Remote Reset Switch R Remote Reset Switch C Input Common I1 Input 1 I2 Input 2 I3 Input 3 I4 Input 4 1 Output A terminal 1 2 Output A terminal 2 3 Output B normally open 4 Output B common 5 Output B normally closed Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Страница 4: ...CIO EN is not powered Overload Comm Operational Green The CIO EN is communicating with an overload device and the CIO EN is powered Overload Comm NOT Operational Flashing Green The CIO EN is powered but overload communications are not established NOTE If an unrecoverable error has occurred with the nonvolatile memory which stores the device settings the CIO EN will enter a lockdown mode and flash ...

Страница 5: ...equired 120Ω terminating resistors should be connected at both the CIO EN across A and B and also at the upstream device also across A and B SymCom recommends that terminating resistors be used in all circumstances to optimize RS 485 signals Existing Network Installations The CIO EN can be added to a Model 777 P P1 overload in an existing network Flexible addressing is enabled by default therefore...

Страница 6: ...t communications settings for the CIO EN are IP Address 192 168 50 1 as stand alone 192 168 50 FLEX where FLEX 777 P P1 Modbus Address Subnet Mask 255 255 0 0 Gateway 192 168 50 1 DHCP Disabled Changing the Ethernet Configuration Settings The Ethernet configuration settings can be changed at any time through the CIO EN s embedded webpage Figure 2 To access this webpage simply type the IP address o...

Страница 7: ...click on a unit to view its properties NOTE If the unit does not appear on the screen recheck the device connections and network communication settings Reattempt to Auto Detect for Units PHYSICAL DIMENSIONS CIO EN All dimensions are in inches FIGURE 3 Physical Dimensions CIO EN Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Страница 8: ...nal block Torque 3 in lbs max Wire AWG 12 20 AWG Safety Marks UL UL508 File E68520 CSA C 22 2 CE IEC 60947 Standards Passed Electrostatic Discharge ESD IEC 61000 4 2 Level 3 6kV contact 8kV air Radio Frequency Immunity Radiated 150 MHz 10V m Fast Transient Burst IEC 61000 4 4 Level 3 4kV input power Hi Potential Test Meets UL508 2 x rated V 1000V for 1 minute Surge Input Power IEC 61000 4 5 Level ...

Отзывы: