Specialist menu
Page 35/56
Programming instructions for
SYCLOPE EVASION
®
2)
Analogical inputs
This procedure allows you to add or to remove an analogical parameter. (8 programmable)
Use the arrow keys to select the channel
and the type of parameter.
►
Use the key to validate your selection.
The entries E1 and E2 are fixed and not programmable.
E1 => Temperature
Range : -5 à 45°C
E2 => pH
Range : 0 à 14pH
Special entry : Level flow switch :
If you decide to use one analogical entry as a « level flow switch » entry, you must select one of the 3
types of function :
(Open) : For a detection with an opened active switch (Normally open)
High threshold : 13 mA
low threshold : 8 mA
(Closed) : For a detection with a closed active switch (Normally closed)
High threshold : 8 mA
Low threshold : 13 mA
(Analog) : For a detection with a special analogical sensor with 4-20 mA output current.
High threshold : 13 mA
Low threshold : 8 mA
USER MENU
> Technician menu access
Select language
Setting real time clock
Interface management
Printing management
TECNICIAN MENU
> Specialist menu access
Technician code
Working timers
Sensors calibration
Setting points
Technical alarms
Analogue outputs
SPECIALIST MENU
> Specialist code
Analogue inputs definition
Chemical computations
Numerical inputs
Conditioned functions
Relays definition
Analogue outputs definition
SPECIALIST MENU
Specialist code
> Analog. inputs definition
Chemical computations
Numerical inputs
Conditioned functions
Relays definition
Analogue outputs definition
Analog inputs definition
E1:Temp.
E6:Not used
E2:pH
E7:Not used
E3:Not used
E8:Not used
E4:Free Cl.
E9:Not used
E5:Level
E10:Not used
E03:
Not used
*
E03:Total Cl.
0 to 5ppm
**
E03:
Total Cl.
E03:Total Cl.
0 to 10ppm
*