Technician menu
Page 31/56
Programming instructions for
SYCLOPE EVASION
®
The process is identical for the 8 measured parameters, the 8 computed parameters and for
the 2 numerical parameters.
Particular case for the settings points of the flow measurements. In the case of the flow
meter, the setting point is a control compensated setting point. It is necessary to set the
flow settings corresponding to 0 % and 100 % of the control ratio
6)
Technical alarms
This procedure allows you to define the usual technical thresholds of each parameter.
Setting points
E1:Temp.
E6:Not used
E2:pH
E7:Not used
E3:Not used
E8:Not used
E4:Free Cl.
E9:Not used
E5:Level
E10:Not used
Setting .....:(E1)
Value .....: 28.2°C
USER MENU
> Technician menu access
Select language
Setting real time clock
Interface management
Printing management
TECNICIAN MENU
> Specialist menu access
Technician code
Working timers
Sensors calibration
Setting points
Technical alarms
Analogue outputs
TECNICIAN MENU
Specialist menu access
Technician code
Working timers
Sensors calibration
Setting points
> Technical alarms
Analogue outputs
TECHNICIAN MENU
Technical alarms
> Measured parameters
Computed parameters
Numerical parameters
Flow parameters
Technical alarms
E1:Temp.
E6:Not used
E2:
pH
******
E7:Not used
E3:Not used
E8:Not used
E4:Free Cl.
E9:Not used
E5:Level
E10:Not used
Alarm channel:(E2)
Thre. Min.: 6.80pH
Thre. Max.: 7.90pH
TECHNICIAN MENU
Setting points
> Measured parameters
Computed parameters
Numerical parameters
Flow parameters
Setting .....:(E22)
Thre. 0% ...: 10.0 m3h
Thre. 100%..: 30.0 m3h
Control compensation
E21: Flw. CAD1 E22: Flw. CAD2
TECNICIAN MENU
Specialist menu access
Technician code
Working timers
Sensors calibration
> Setting points
Technical alarms
Analogue outputs
TECHNICIAN MENU
Setting points
> Measured parameters
Computed parameters
Numerical parameters
Flow parameters
Содержание EVASION
Страница 53: ...Programming instructions for SYCLOPE EVASION NOTES...
Страница 54: ...Programming instructions for SYCLOPE EVASION...
Страница 55: ...Programming instructions for SYCLOPE EVASION...