Technician menu
Page 30/56
Programming instructions for
SYCLOPE EVASION
®
Calibration of the slope must not be performed with a value near zero. Proceed to the slope
calibration with a highest possible value.
To make the zero (or pH=7) of the sensor.
►
Validate with to execute the zeroing of channel E4.
To realize a perfect “zero point”, ensure you have water without chemical product or a
reference value at pH=7 for pH calibration.
To delete calibrations
►
Validate with to execute the erasing of all calibrations for channel E4.
To ensure the user of the calibration sensors without technician access code, a special key
named on the front face of the controller is usable. These accesses to the slope only.
5)
Setting points
This procedure allows you to fix the setting points of each regulation processes.
Sensors calibration
E1:Temp.
E6:Not used
E2:pH
E7:Not used
E3:Not used E8:Not used
E4:
Free Cl.
E9:Not used
E5:Level
E10:Not used
Calibration..:(E4)
Standard ..:0
3.04ppm
Zero ........: No
Erasing .....: No
Calibration..:(E4)
Standard ..:03.04ppm
Zero ........:
No
oo
Erasing .....: No
Calibration..:(E4)
Standard ..:03.04ppm
Zero ........:
Yes
o
Erasing .....: No
Sensors calibration
E1:Temp.
E6:Not used
E2:pH
E7:Not used
E3:Not used E8:Not used
E4:
Free Cl.
E9:Not used
E5:Level
E10:Not used
Calibration..:(E4)
Standard ..:0
3.04ppm
Zero ........: No
Erasing .....: No
Calibration..:(E4)
Standard ..:03.04ppm
Zero ........: No
Erasing .....:
No
oo
Calibration..:(E4)
Standard ..:03.04ppm
Zero ........: No
Erasing .....:
Yes
o
DIRECT CALIBRATIONS
Sensors calibration
E1:Temp.
E6:Not used
E2:pH
E7:Not used
E3:Not used
E8:Not used
E4:Free Cl.
E9:Not used
E5:Level
E10:Not used
Calibration..:(E1)
Standard ..: 28.2°C
USER MENU
> Technician menu access
Select language
Setting real time clock
Interface management
Printing management
TECNICIAN MENU
> Specialist menu access
Technician code
Working timers
Sensors calibration
Setting points
Technical alarms
Analogue outputs