Commissioning
Page 17/40
Installation and starting instruction manual
SYCLOPE TRACE’O
®
5)
Connexion of the free of potential relays (KA, KB, KC et KD)
The free of potential output relays are used to control the various measured parameters. They are
used also for alarm transfers or for driving magnet valves of water entries when the controller is
programmed as a trace measurement.
6)
Connection of the measurement inputs
The main entry and the auxiliary entry are dedicated to various type of parameters. The controller is
equipped with three entries maximum according to the module configuration.
Using SYCLOPE cells is mandatory. They are adapted to the different type of sensors and
offer the best guaranty of good measurement. No claim will be received in case of unrespect
of this condition.
a)
Basic version (2 entries 4…20mA NOT isolated)
The amperometric measurement inputs generate their own power supply and should not be
powered in any case!
When no module is used, the entries are NOT insolated!
Please, respect the polarity of the amperometric sensor! When using a SYCLOPE cell, the
colors of the wires are :
Entry
+ : White wire
Entry
- : Blue wire
Temperature probe
without polarity
Amperometric sensor :
Respect polarity