SWT TECH Series Скачать руководство пользователя страница 4

Page 4

When set up as a softener, the backwash and rinse cycles automatically increase with increasing salt dosage. 

Backwashes can be set to be NORMAL or LONGER. The option selected will apply to all backwashes. Tables 2 

and 3 (below) show the length of the cycles when the valve is set up as a softener.

Table 2

Backwash NORMAL Length Softener

Cycle Times in Minutes

*  These are reference numbers that approximate the amount of salt needed. The actual capacity in grains per pound of salt is used in calculations.

** Total Time does not include Fill Time, which is dependent upon the amount of salt needed. When in the Fill Mode the system is providing treated water.

Table 3

Backwash LONGER Length Softener

Cycle Times in Minutes

*  These are reference numbers that approximate the amount of salt needed. The actual capacity in grains per pound of salt is used in calculations.

** Total Time does not include Fill Time, which is dependent upon the amount of salt needed. When in the Fill mode the system is providing treated water.

Table 4 (page 5) shows the order of the cycles when the valve is set up as a filter. When the control valve is used as 

a downflow regenerating filter (i.e. both backwash and regeneration), it allows the option to specify one backwash or 

two backwashes. Regenerating filters also have the option of having the regenerant refill after the rinse cycle or 

prefill before regeneration. If the regenerant prefills before regeneration, the prefill starts two hours before the 

regeneration time set. During the 2-hour period in which the regenerant is being made, treated water is still available. 

For example: If a downflow filter regeneration time is set for 2:00 a.m. with the prefill option selected, then the fill 

cycle occurs at 12:00 a.m. and the start of the backwash cycle occurs at 2:00 a.m. There is only one rinse. 

Backwashes can be set to NORMAL or LONGER. The option selected will apply to all backwashes. Tables 5 and 6 

(page 5) show the length of the cycles when the valve is set up as a filter.

When the control valve is used as a non-regenerating filter (backwash only), it has the option to specify one 

backwash or two backwashes. If two backwashes are specified, two rinses occur. Tables 5 and 6 (page 5) show the 

length of the cycles when the valve is set up as a filter. When used as a non-regenerating filter, the downflow piston 

must be installed, the regenerant piston removed, injector plugs must be installed in both the DN and UP injector 

locations, and the refill elbow must be replaced with a refill port plug.

WS1 & WS1.25 Downflow Softener 

WS1 & WS1.25  Upflow Softener

Grains Capacity / Lb. NaCl 

6000 to 3501 

3500 to 2501 

2500 to 1700 

6000 to 3501 

3500 to 2501 

2500 to 1700

Lbs. NaCl / Cu.Ft. Resin * 

Less than 7.5 

7.5 to 12 

More than 12 

Less than 7.5 

7.5 to 12 

More than 12

Cycle 

Time

in Minutes

Backwash Normal 

8

Regenerate 

45 

60 

75 

45 

60 

75

Backwash Normal 

10 

10 

12

Rinse 

6

Total **

57 

80 

99 

54 

74 

93

WS1 & WS1.25 Downflow Softener 

WS1 & WS1.25  Upflow Softener

Grains Capacity / Lb. NaCl 

6000 to 3501 

3500 to 2501 

2500 to 1700 

6000 to 3501 

3500 to 2501 

2500 to 1700

Lbs. NaCl / Cu.Ft. Resin * 

Less than 7.5 

7.5 to 12 

More than 12 

Less than 7.5 

7.5 to 12 

More than 12

Cycle 

Time

in Minutes

Backwash Normal 

10 

12

Regenerate 

45 

60 

75 

60

70

80

Backwash Normal 

10 

12 

12

14 

16

Rinse 

5

7

9

Total **

65 

86 

107 

77

91 

105

Содержание TECH Series

Страница 1: ...I n c O P E R A T I O N I N S T R U C T I O N M A N U A L TECH SERIES CONTROL VALVES F I L T E R S S O F T E N E R S C O N D I T I O N E R S 1 INCH TECH SERIES CONTROL VALVE MODEL WS1 1 25 INCH TECH SERIES CONTROL VALVE MODEL WS1 25 APRIL 2016 ...

Страница 2: ...Clock Options 7 General Instructions 8 Softener Setup 9 Table 8 Softener and Filter Setting Options 10 Filter Setup 11 Installer Display Settings 12 User Display Settings 12 General Operation 12 Regeneration Mode 12 Manual Regeneration 13 Set Time of Day 13 Power Loss 14 Error Message 14 Diagnostics 15 Valve History 16 Drawings and Part Numbers 16 Front Cover and Drive Assembly 17 WS1 Drive Cap As...

Страница 3: ...r tube can be cut 0 5 inch above to 0 5 inch below the top of tank thread The distributor tube is held in place by an o ring seal and the control valve also has a bayonet lock feature for upper distributor baskets The AC adapter power pack comes with a 15 foot power cord and is designed for use with the control valve The AC adapter power pack is for dry location use only The control valve remember...

Страница 4: ...reated water is still available For example If a downflow filter regeneration time is set for 2 00 a m with the prefill option selected then the fill cycle occurs at 12 00 a m and the start of the backwash cycle occurs at 2 00 a m There is only one rinse Backwashes can be set to NORMAL or LONGER The option selected will apply to all backwashes Tables 5 and 6 page 5 show the length of the cycles wh...

Страница 5: ...ity should be set to oFF 2 See Installer Display Settings Step 3 NA page 11 Softener Setup Step 6 SS page 8 and Filter Setup Step 5 FS page 10 for explanations of Day Override and Gallon Capacity WS1 WS1 25 Single Backwash WS1 WS1 25 Double Backwash NORMAL LONGER NORMAL LONGER Backwash 14 16 8 12 Regenerate 60 60 60 60 2nd Backwash 10 12 Rinse 8 10 8 10 Total 82 86 86 94 WS1 WS1 25 Single Backwash...

Страница 6: ...ing and holding the REGEN button for approximately 3 seconds will immediately start the regeneration The user cannot cancel this request except by resetting the control by pressing NEXT and REGEN buttons simultaneously for 3 seconds A unique feature of this control valve is the ability to display actual water usage for the last 63 days The values are initially stored as This means the value is unk...

Страница 7: ...isplay Any changes made prior to the five minute time out are incorporated The one exception is the current flow rate display under the diagnostic procedure The current flow rate display has a 30 minute time out feature To quickly exit Softener Setup Filter Setup Installer Display Settings Diagnostics or Valve History press SET CLOCK Any changes made prior to the exit are incorporated All informat...

Страница 8: ...capacity and water hardness oFF bases regeneration on Day Override in Step 3 NA page 11 or number of gallons 20 to 50 000 gallons See Table 8 page 9 for more detail 3 Press NEXT to go to Step 7 SS Press REGEN to return to the previous step STEP 7 SS Refill Set refill option using or buttons PoST to refill the brine tank after the final rinse or PrE to refill the brine tank two hours before the reg...

Страница 9: ...ons is reached AUTO on 0 oFF Reserve capacity not automatically estimated Regeneration occurs immediately when gallons capacity reaches 0 Time of regeneration will not be allowed to be set because regeneration will always occur when gallons capacity reaches 0 Any number on 0 oFF Reserve capacity not automatically estimated Regeneration occurs immediately when gallons capacity reaches 0 Time of reg...

Страница 10: ...h LONGER for one longer backwash 16 minutes or LONGER 2 for two longer backwashes 12 minutes each See Tables 5 and 6 page 5 for additional details Press NEXT to go to Step 5 FS Press REGEN to return to the previous step STEP 5 FS Gallons Capacity Set gallons capacity using or buttons oFF bases regeneration on Day Override in Step 3N page 11 or number of gallons 20 to 50 100 gallons See Table 8 pag...

Страница 11: ...mber of days between regeneration 1 to 28 a regeneration initiation will be called for on that day even if a sufficient number of gallons were not used to call for a regeneration or oFF regeneration initiation is based solely on gallons used Press NEXT to go to step 4 NA Press REGEN to return to the previous step STEP 4 NA Next Regeneration Time hour Set the hour of day for regeneration using or b...

Страница 12: ...egeneration process and the time remaining for that step to be completed The system runs through the steps automatically and will reset itself to provide treated water when the regeneration has been completed Manual Regeneration Sometimes there is a need to regenerate the system sooner than when the system calls for it usually referred to as manual regeneration There may be a period of heavy water...

Страница 13: ... Step 3 UD STEP 3 UD Current Time minutes Set the minutes of the day using or buttons Press NEXT to exit Set Clock Press REGEN to return to previous step Power Loss If the power goes out the system will keep time for up to 8 hours or until the battery is depleted If a power outage of more than 8 hours occurs the time of day will flash on and off which indicates the time of day should be reset The ...

Страница 14: ...aximum number of gallons treated for the last 63 days This display will show dashes if a water meter is not installed Press NEXT at any time to go to Step 6 DA Press REGEN to return to the previous step STEP 6 DA Flow Rate current Turn the water on at one or more taps in the building The flow rate in gallons per minute will be displayed If flow stops the value will fall to 0 zero in a few seconds ...

Страница 15: ...STEP 4 VH Gallons total used since start up This display shows the total gallons treated since start up This display will equal 0 zero if a water meter is not installed Press NEXT to go to Step 5 VH Press REGEN to return to the previous step STEP 5 VH Days total since start up This display shows the total days since start up Press NEXT to go to Step 6 VH Press REGEN to return to the previous step ...

Страница 16: ... VAC 230 VAC Supply Frequency 60 Hz 50 Hz Output Voltage 12 VAC 12 VAC Output Current 500 mA 500 mA Drawing No Part No Description Quantity 1 LC V3175 01 WS1 Front Cover Assembly 1 LC V3002 WS1 Drive Assembly 1 2 LC V3107 01 WS1 Motor 1 3 LC V3106 01 WS1 Drive Bracket and Spring Clip 1 4 LC V3108 10BOARD WS1 PC Board XMEGA Replace 1 5 LC V3110 WS1 Drive Reducing Gear 12 x 36 3 6 LC V3109 WS1 Drive...

Страница 17: ...ty 1 LC V3005 02 WS1 Spacer Stack Assembly 1 2 LC V3004 Drive Cap Assembly 1 3 LC V3178 WS1 Drive Backplate 1 4a LC V3011 WS1 Piston Downflow Assembly 1 4b LC V3011 01 WS1 Piston Upflow Assembly 1 5 LC V3174 WS1 Regenerant Piston 1 6 LC V3135 O ring 228 1 7 LC V3180 O ring 337 1 8 LC V3105 O ring 215 Distributor Tube 1 Not Shown LC V3001 WS1 Body Downflow Assembly 1 LC V3001 02 WS1 Mixing Valve Bo...

Страница 18: ...sembly 1 4b LC V3011 01 WS1 Piston Upflow Assembly 1 5 LC V3174 WS1 Regenerant Piston 1 6 LC V3135 O ring 228 1 7 LC V3180 O ring 337 1 8 LC V3358 O ring 219 Distributor Tube Opening 1 32 inch 1 LC V3357 O ring 218 Distributor Tube Opening 32mm 1 Not Shown LC V3020 WS1 25 Body Downflow Assembly Distributor Tube Opening 1 32 inch 1 LC V3020 01 WS1 25 Mixing Valve Body Downflow Assembly Distributor ...

Страница 19: ...iston is black and amber NOTE The WS1 downflow piston is a solid amber color The WS1 upflow piston is black and amber 1 25 inch 1 5 inch Spacer Color Black Spacer Color Gray 1 5 inch 1 25 inch Black Plug Spacer Color Gray 1 25 inch DOWNFLOW BACKWASH UPFLOW 1 25 inch Gray Plug Gray Ring Gray Distributor O ring Retainer NOTE The WS1 downflow piston is a solid amber color The WS1 upflow piston is bla...

Страница 20: ... U F F C I T Y B O U L E V A R D E L G I N I L 6 0 1 2 0 U S A T E L E P H O N E 8 4 7 8 8 8 6 9 0 0 F A C S I M I L E 8 4 7 8 8 8 6 9 2 4 E M A I L i n f o s w t w a t e r c o m W E B S I T E w w w s w t w a t e r c o m FORM TECH MANUAL EFFECTIVE APRIL 2016 ...

Отзывы: