Installation instructions for the optical detector with built-in 
control unit, TBLZ-1-72-a  
GOLD/COMPACT

1. General

The TBLZ-1-72-a optical smoke detector with built-in control unit 
is used for measuring smoke gases in ventilation ducts. 
It consists of an optical detector mounted in an adapter system 
in which both the tube and enclosure are designed for optimum 
airflow through the detector. The system meets all fire safety 
requirements at air speeds between 0.2m/s and 20m/s. The smoke 
detector also has a built-in control unit for controlling fans, fire 
and combustion gas dampers.

Accessories

Use an installation bracket when installing on circular or insulated 
ducts.

2. Function

A green LED is lit on the control unit's circuit card when the unit is 
operating in the normal mode. All the relays are activated.
When combustion gas is detected, a red LED lights up on the 
circuit card and detector.
If the smoke detector becomes dirty, it becomes more sensitive 
and slowly switches to alarm mode. To prevent false alarms if dirty, 
the detector is equipped with a service alarm (green LED on the 
smoke detector and yellow LED on the circuit card of the control 
unit). This indicates that the detector requires cleaning.
If a malfunction arises, the green LED will be off and no relays 
will be activated. Example: If the smoke detector is removed or a 
power failure occurs.
A tripped alarm can be reset on the rear side of the smoke detec-
tor. See illustration.

3. Technical Data

Type of detector   

Optical

Operating voltage 24 V AC/DC +/- 10% 
Power consumption: 

 

Operation 

 

About 165 mA

Ambient temperature 

-10°C to +55°C

Atmospheric humidity 

Max. 99% rH

Enclosure class 

 

IP54

Tested and passed To  

VdS

Dimensions

Venturi tube length of 600 mm or 1500 mm.

(All dimensions are given in mm)

4. Maintenance

When the smoke detector becomes dirty, it becomes more 
sensitive and may trigger the service alarm. This can be delayed by 
vacuuming the detector once a year.

Reset button

Содержание TBLZ-1-72-a GOLD

Страница 1: ...combustion gas is detected a red LED lights up on the circuit card and detector If the smoke detector becomes dirty it becomes more sensitive and slowly switches to alarm mode To prevent false alarms if dirty the detector is equipped with a service alarm green LED on the smoke detector and yellow LED on the circuit card of the control unit This indicates that the detector requires cleaning If a ma...

Страница 2: ...ee example of interfering sources below in the direction of airflow is the same as 3 x the duct s hydraulic diameter Nearest location after an interfering source must be at least 5 x the duct s hydraulic diameter MIN 3xdh MIN 5xdh GX GX MIN 3xdh MIN 5xdh GX GX MIN 3xdh MIN 5xdh GX GX MIN 3xdh MIN 5xdh GX GX MIN 3xdh MIN 5xdh GX GX MIN 5xdh GX MIN 3xd h GX MIN 5xdh GX MIN 3xd h GX GX MIN 3xdh GX GX...

Страница 3: ...Secure the detector box at 3 points at the markings of the arrows Important IMPORTANT The direction arrows see the shape of the detector s base or the top of the housing must point in the same direction as the air flow in the duct End plug Stop screw Seal 5 Flow indicator The detector is equipped with an indicator a red plastic tab which when the detector is correctly installed swings out due to t...

Страница 4: ... up see point 8 The detector insert must be replaced 10 8 9 The installation bracket is supplied flat The installation bracket is easy to bend shape so that it fits circular or flat ducts Secure the bracket s legs to the duct Hole ø 51 mm Rubber seal Circular duct Insulated flat duct Rubber seal Final checks Installing different tubes in different duct widths Venturi tube 600 mm Venturi tube 1200 ...

Страница 5: ... trips the alarm is forwarded to GOLD COMPACT external fire alarm When the smoke detectors become dirty a service alarm is initiated and is forwarded to GOLD COMPACT via the external alarm 2 Alarms can be reset on the smoke detector and in the hand held micro terminal Wiring terminals on the control unit Power supply 24V AC DC Smoke alarm relay NO Smoke alarm relay C Free change over contact NC Ma...

Страница 6: ...We reserve the right to alter specifications 6 www swegon com GB TBLZ172 190411 ...

Отзывы: