We reserve the right to alter specifications.

www.swegon.com     3

GB.TBLZ172.190411

• Open the cover above the junction hood by lifting the catch.
• Insert the cable through any cable grommet.
When using another type of grommet, remove them premounted 
by first pressing through one side and then through the other 
(1-2).
• Connect the cables according to the wiring diagram in Section 6.

1

2

Drill holes in the duct. 

 

• Make holes without 38 mm installation bracket.
• Make holes with 51 mm installation bracket (see 
point 9).

3

Do not cut this end!

• Measure the ventilation duct.
• Cut the tube.
• The tubes must cover at least 90% of the duct’s width.  
Detectors with venturi tubes of 600 mm are intended for ducts 
with a max. duct width of 600 mm.
• Insert the end plug.

• Insert the seal onto the tube.
• Insert the tube into the bottom of the detector box.
• Lock the tube using the stop screw

4

• Install the tube and detector on the duct.
• Secure the detector box at 3 points at the markings of the 
arrows.

Important! IMPORTANT!
The direction arrows (see the shape of the detector’s base or the top 
of the housing) must point in the same direction as the air flow in 
the duct.

End plug

Stop screw

Seal

5

Flow indicator.
The detector is equipped with an indicator, a red plastic 
tab, which, when the detector is correctly installed, 
swings out due to the air flow.

6

Electrical installation.

Important!
If the indicator does not 
move, consider moving 
the detector or install a 
fan tube.

Flow indicator

Venturi tube with auxiliary fan

7

Performance checks.
Check the detector using the smoke detector tester in 
spray form.

• Move the "test hole plug" to the side 
and then quickly spray.
In the event of a tripped alarm, the 
LED shines red on the circuit board and 
the detector. In the event of a tripped 
service alarm, the LED shines green on 
the detector and yellow on the circuit 
board.
• Reinstall the test hole plug.

Important! 
Do NOT drill holes for signs or similar in the plastic cover. This can 
cause leakage that seriously affects the function of the detector.

Содержание TBLZ-1-72-a GOLD

Страница 1: ...combustion gas is detected a red LED lights up on the circuit card and detector If the smoke detector becomes dirty it becomes more sensitive and slowly switches to alarm mode To prevent false alarms if dirty the detector is equipped with a service alarm green LED on the smoke detector and yellow LED on the circuit card of the control unit This indicates that the detector requires cleaning If a ma...

Страница 2: ...ee example of interfering sources below in the direction of airflow is the same as 3 x the duct s hydraulic diameter Nearest location after an interfering source must be at least 5 x the duct s hydraulic diameter MIN 3xdh MIN 5xdh GX GX MIN 3xdh MIN 5xdh GX GX MIN 3xdh MIN 5xdh GX GX MIN 3xdh MIN 5xdh GX GX MIN 3xdh MIN 5xdh GX GX MIN 5xdh GX MIN 3xd h GX MIN 5xdh GX MIN 3xd h GX GX MIN 3xdh GX GX...

Страница 3: ...Secure the detector box at 3 points at the markings of the arrows Important IMPORTANT The direction arrows see the shape of the detector s base or the top of the housing must point in the same direction as the air flow in the duct End plug Stop screw Seal 5 Flow indicator The detector is equipped with an indicator a red plastic tab which when the detector is correctly installed swings out due to t...

Страница 4: ... up see point 8 The detector insert must be replaced 10 8 9 The installation bracket is supplied flat The installation bracket is easy to bend shape so that it fits circular or flat ducts Secure the bracket s legs to the duct Hole ø 51 mm Rubber seal Circular duct Insulated flat duct Rubber seal Final checks Installing different tubes in different duct widths Venturi tube 600 mm Venturi tube 1200 ...

Страница 5: ... trips the alarm is forwarded to GOLD COMPACT external fire alarm When the smoke detectors become dirty a service alarm is initiated and is forwarded to GOLD COMPACT via the external alarm 2 Alarms can be reset on the smoke detector and in the hand held micro terminal Wiring terminals on the control unit Power supply 24V AC DC Smoke alarm relay NO Smoke alarm relay C Free change over contact NC Ma...

Страница 6: ...We reserve the right to alter specifications 6 www swegon com GB TBLZ172 190411 ...

Отзывы: