6. Electrical connections

The electrical connections should be wired by a qualified 
electrician in accordance with local electrical safety regulations.

Smoke detector, supervisory unit

SMOKE FUNCTION

Wiring terminals on the 

control unit and on the 

electrical equipm. 

cubicle.

Ext. fire alarm 1

Ext. alarm 2

Function:
If the smoke detector in the duct trips, the alarm is forwarded to 
GOLD/COMPACT, external fire alarm. 
When the smoke detectors become dirty, a service alarm is 
initiated and is forwarded to GOLD/COMPACT via the external 
alarm 2.
Alarms can be reset on the smoke detector and in the hand-held 
micro terminal.

Wiring terminals on the 

control unit

Power supply: 24V AC/DC

Smoke alarm relay

NO   

 Smoke alarm relay

C   

 Free change-over contact

NC   

 Max. 250V. 5A.

NC 

GOLD

COMPACT

***Ext. fire alarm 2

* Should be selected for ext. fire 
alarm in the micro terminal.
** Should be selected for ext. alarm 
in the micro terminal.
*** Alternative connections

* DI-1

**DI-2

Wiring terminals on the 

module

4567

89

ABC

DE

F0

12

3

Function selector switch set to position 0.

Содержание TBLZ-1-72-a GOLD

Страница 1: ...combustion gas is detected a red LED lights up on the circuit card and detector If the smoke detector becomes dirty it becomes more sensitive and slowly switches to alarm mode To prevent false alarms if dirty the detector is equipped with a service alarm green LED on the smoke detector and yellow LED on the circuit card of the control unit This indicates that the detector requires cleaning If a ma...

Страница 2: ...ee example of interfering sources below in the direction of airflow is the same as 3 x the duct s hydraulic diameter Nearest location after an interfering source must be at least 5 x the duct s hydraulic diameter MIN 3xdh MIN 5xdh GX GX MIN 3xdh MIN 5xdh GX GX MIN 3xdh MIN 5xdh GX GX MIN 3xdh MIN 5xdh GX GX MIN 3xdh MIN 5xdh GX GX MIN 5xdh GX MIN 3xd h GX MIN 5xdh GX MIN 3xd h GX GX MIN 3xdh GX GX...

Страница 3: ...Secure the detector box at 3 points at the markings of the arrows Important IMPORTANT The direction arrows see the shape of the detector s base or the top of the housing must point in the same direction as the air flow in the duct End plug Stop screw Seal 5 Flow indicator The detector is equipped with an indicator a red plastic tab which when the detector is correctly installed swings out due to t...

Страница 4: ... up see point 8 The detector insert must be replaced 10 8 9 The installation bracket is supplied flat The installation bracket is easy to bend shape so that it fits circular or flat ducts Secure the bracket s legs to the duct Hole ø 51 mm Rubber seal Circular duct Insulated flat duct Rubber seal Final checks Installing different tubes in different duct widths Venturi tube 600 mm Venturi tube 1200 ...

Страница 5: ... trips the alarm is forwarded to GOLD COMPACT external fire alarm When the smoke detectors become dirty a service alarm is initiated and is forwarded to GOLD COMPACT via the external alarm 2 Alarms can be reset on the smoke detector and in the hand held micro terminal Wiring terminals on the control unit Power supply 24V AC DC Smoke alarm relay NO Smoke alarm relay C Free change over contact NC Ma...

Страница 6: ...We reserve the right to alter specifications 6 www swegon com GB TBLZ172 190411 ...

Отзывы: