6. Electrical connections
The electrical connections should be wired by a qualified
electrician in accordance with local electrical safety regulations.
Smoke detector, supervisory unit
SMOKE FUNCTION
Wiring terminals on the
control unit and on the
electrical equipm.
cubicle.
Ext. fire alarm 1
Ext. alarm 2
Function:
If the smoke detector in the duct trips, the alarm is forwarded to
GOLD/COMPACT, external fire alarm.
When the smoke detectors become dirty, a service alarm is
initiated and is forwarded to GOLD/COMPACT via the external
alarm 2.
Alarms can be reset on the smoke detector and in the hand-held
micro terminal.
Wiring terminals on the
control unit
Power supply: 24V AC/DC
Smoke alarm relay
NO
Smoke alarm relay
C
Free change-over contact
NC
Max. 250V. 5A.
C
NC
GOLD
COMPACT
***Ext. fire alarm 2
* Should be selected for ext. fire
alarm in the micro terminal.
** Should be selected for ext. alarm
in the micro terminal.
*** Alternative connections
* DI-1
**DI-2
Wiring terminals on the
module
4567
89
ABC
DE
F0
12
3
Function selector switch set to position 0.