GB.SILVERF120.181005
We reserve the right to alter specifications.
www.swegon.com 3
3440
1070
1070
1868
1170
2350
1861
2930
1.1 General
All staff concerned must acquaint themselves with these
instructions before beginning any work on the unit. Any
damages to the unit or parts of it due to improper han-
dling or misuse by the purchaser or the fitter cannot be
considered subject to guarantee if these instructions have
not been followed correctly.
The product identification label is affixed on the inspection
side of the air handling unit. Refer to the particulars on the
product identification plate when you contact Swegon.
The air handling unit is supplied in packaged condition.
Possible ordered accessories are supplied in separate pack-
aging with the unit.
1.2 Transport within the site
Before removing the transport pallet/transport cradle, if
used, determine whether a forklift truck or a pallet trans-
porter will be used for further transporting the unit within
the site to the spot where it will be installed.
1.3 Parts packed together with the unit
Components such as the commissioning plates, bolts and
document pocket are supplied in separate packaging and
delivered together with the air handling unit.
1.3.1 Document pocket
Secure the document pocket to the exterior of the air
handling unit or another appropriate place.
1.4 Arrangement
The air handling unit must be mounted horizontally on a
flat and firm supporting surface and this surface must be
constructed in a way enabling it to support the weight of
the unit.
When installing the air handling unit and connecting pipe-
work and electric cables, make sure that adequate free
space is provided for opening the inspection doors and
covers and withdrawing functional sections, such as filter
cassettes and fan assemblies, clear of the unit casing.
Inspection space required
A clear space of 1,000 mm should be provided in front of
the unit for opening the inspection doors.
1. Installation
1.5 Method of delivery
1.5.1 SILVER C RX
The SILVER C RX 120 is normally supplied in five separate
sections: Two fan sections, two filter sections and one
heat exchanger section.
The heat exchanger section can also be supplied split into
two casing sections and rotor, in which case the rotor is
supplied tilted in a transport cradle (transport height =
2,930 mm, minimum transport width = 2,350 mm). See
Section 1.7 for installation particulars.
For other dimensions and weights, see Section 2.1.
Heat exchanger section supplied as a separate unit
Heat exchanger section, sup-
plied split into two casing sec-
tions and rotor
Rotor, Ø 3150
Transport cradle
3440
1070
1070
1868
1170
2350
1861
2930
1.5.2 SILVER C CX
The SILVER C CX 120 is supplied in six separate sections:
Two fan sections, two filter sections and two coil heat
exchanger sections.
For dimensions and weights, see Section 2.2.