3.3.1 Height adjustment to height of GOLD/
water trap
COOL DX, size 08
In combination with the GOLD RX 08
The design of the GOLD unit makes it necessary to place it
on base beams, a stand or some other form of foundation,
to be able to open the inspection doors. The base beams
and stand are available as accessories.
Appropriate base beams are also available as accessories
for the COOL DX. The base beams/stand are matched to
one another in terms of height. The stands also provide
space for accommodating a possible water trap in the
lower level (right-hand unit version).
In combination with the GOLD PX 08
The air handling unit is supplied on a 180 mm high base
frame.
A corresponding base frame is also available as an acces-
sory for the COOL DX. The heights of the base frames
are matched to one another and also provide space for a
water trap, if required, for connection at the lower section
(right-hand version).
COOL DX, sizes 12-40
The GOLD air handling unit and the cooling unit COOL DX
are supplied with 100 mm high base beams.
Applicable to cooling coil in lower level:
If a water trap (accessory) is fitted, the GOLD unit and
the cooling unit must be raised at least 50 mm to provide
space for the water trap. Adjustable support feet (acces-
sories) can be appropriately fitted to the base beams for
this purpose.
COOL DX, sizes 60-80
The GOLD air handling unit and the cooling unit COOL DX
are supplied with 100 mm high support feet. The support
feet can be removed or left on the unit.
Applicable when cooling coil in lower level:
If a water trap (accessory) is fitted, the GOLD unit and the
cooling unit must be raised at least 50 mm above the base
beams to provide space for the water trap. This can appro-
priately be done by leaving the factory-fitted support feet
on the base beams. Or you can replace them with adjusta-
ble feet (accessory).