Sizing
There are many factors that influence what size of cooling
unit is required.
The COOL DX/COOL DX Top units have been designed to
enable them to meet many different prerequisites.
10 GENERAL TECHNICAL DATA
Cooling system COOL DX
COOL
DX
Size
Capac-
ity var.
Nom.
air-
flow
(m
3
/s)
Min.
air-
flow
(m
3
/s)
Nom.
cooling
capac-
ity
1)
(kW)
Nom.
power
required
(kW)
Refrigerant
(kg)
Power
supply
Weight
excl. end
conn.
panel
(kg)
Weight/pc.
- end conn.
panel, if
required
2)
(kg)
Cir-
cuit 1
Cir-
cuit 2
08
1
0.55
0.22
9.8
2.39
1,20
1,30
3-ph.+N, 400 V, 16 A
194
8
2
0.70
0.3
13.9
4.33
1,20
1,30
3-ph.+N, 400 V, 20 A
215
8
12
1
0.85
0.35
15.4
3.95
1,50
1,70
3-ph.+N, 400 V, 20 A
260
10
2
1.05
0.4
20.9
6.53
1,50
1,70
3-ph.+N, 400 V, 25 A
287
10
20
1
1.1
0.45
15.4
4.06
1,20
1,50
3-ph.+N, 400 V, 25 A
243
10/13
2
1.3
0.5
23.3
5.73
2,50
2,80
3-ph.+N, 400 V, 25 A
283
10/13
3
1.6
0.6
31.0
9.15
2,10
2,40
3-ph.+N, 400 V, 40 A
314
10/13
30
1
1.8
0.7
25.0
6.33
1,80
2,00
3-ph.+N, 400 V, 32 A
322
11/17
2
2.0
0.8
35.8
9.34
3,00
3,20
3-ph., 400 V, 25 A
374
11/17
3
2.4
1.0
46.2
13.5
2,90
3,30
3-ph., 400 V, 40 A
414
11/17
40
1
2.9
1.1
38.6
8.40
3,30
4,00
3-ph., 400 V, 25 A
468
18/22
2
3.1
1.3
48.4
12.3
3,30
4,50
3-ph., 400 V, 40 A
476
18/22
3
3.6
1.5
67.0
17.5
5,50
4,50
3-ph., 400 V, 50 A
529
18/22
60
1
2
3
3.9
4.1
5.0
1.5
1.6
2.0
56.2
66.7
97.5
11.8
17.1
26.3
4,50
5,00
6,00
5,50
5,20
7,50
3-ph., 400 V, 40 A
3-ph., 400 V, 50 A
3-ph., 400 V, 80 A
708
779
852
31
31
31
80
1
2
3
5,2
6,0
7.0
2.0
2.4
2.8
67.0
96.5
134.0
13.3
24.8
36.4
6,60
6,50
9,00
7,30
9,00
11,50
3-ph., 400 V, 50 A
3-ph., 400 V, 80 A
3-ph., 400 V, 100 A
852
979
1035
38
38
38
1)
For an outdoor temperature of 26°C, 50% RH (capacity variant 1), 27°C, 50% RH (capacity variant 2) or 28°C, 50% RH (capacity variant 3), and
an extract air temperature of 26°C.
2)
The first weight applies to a small end connection panel; the second weight applies to a large end connection panel. COOL DX can be supplied
completely without end connection panels or with a maximum of 2 small and two large end connection panels depending on the variant selected.
For correct sizing we refer to our ProUnit unit selection
program.
1)
For an outdoor temperature of 26°C, 50% RH (capacity variant 1) or 28°C, 50% RH (capacity variant 2), and an extract air temperature of 26°C.
COOL
DX Top
Size
Capac-
ity
variant
Nom.
airflow
(m
3
/s)
Min.
airflow
(m
3
/s)
Nom.
cooling
capacity
1)
(kW)
Nom. power
required
(kW)
Refrigerant
(kg)
Power supply
Weight
(kg)
Circuit
1
Circuit
2
05
1
0.40
0.10
6.77
1.66
0.95
1.00
3-ph.+N, 400 V, 16 A
200
2
0.55
0.20
9.30
2.48
1.02
1.03
3-ph.+N, 400 V, 20 A
200
08
1
0.55
0.22
9.31
2.38
1.15
1.20
3-ph.+N, 400 V, 20 A
280
2
0.70
0.3
13.5
4.34
1.29
1.30
3-ph.+N, 400 V, 20 A
280
12
1
0.85
0.35
14.8
3.95
1.60
1.70
3-ph.+N, 400 V, 20 A
340
2
1.05
0.40
20.4
6.69
1.75
1.92
3-ph.+N, 400 V, 25 A
340
Cooling system COOL DX Top