Important information

Installation and commissioning

Only qualified personnel should carry out installation, 

configuration and commissioning. Only a qualified 

electrician is allowed to make electrical installations in 
accordance with national regulations.

The national standards and regulations dealing with 

unit installation, configuration and commissioning 

must be followed. 

Do not use the ventilation unit until all work that 

produces large quantities of dust or other impurities 

has been completed.

The duct connections of the ventilation unit must be 

covered by lids until it is mounted at its final location.

Make sure that the ventilation unit, filters and ducts 

are clean and that there are no loose objects in them 

before you commission the ventilation system.

Electrical work and connections

If you carry out voltage tests, measure the electri-

cal insulation resistance at various points or perform 

other remedial measures that could damage sensitive 

electronic equipment, you must first isolate the venti-

lation unit from the electrical supply grid.

It is recommended that all Smart ventilation units 

should be equipped with a surge protection device.

It is recommended that all Smart ventilation units 

should be equipped with a residual current circuit 

breaker. Comply with local electrical safety regula-

tions when you install electrical equipment.

Drying laundry

A tumbler dryer of extract air type or a drying cabinet 

must not be connected to the system due to the high 

moisture content in the air it discharges.

Models with water-based air heater

When there is a water-based post heater in the ven-

tilation system the system should be equipped with 

damper in outdoor air duct so that the air heater 

cannot freeze during a power failure and unit freez-

ing protection works correctly.

Condensation

The surface temperature of the ventilation unit can 

drop down to 12 °C during periods of low outdoor 

temperature and depending on the moisture content 

of the air surrounding the unit, moisture may con-

dense on the surface. Condensation should be taken 

into account when choosing furnishings that are to 

be installed in the vicinity of the ventilation unit.

Balancing functions

It is recommended to use external preheater when 

balancing functions are used at temperatures below 

-10 °C.

To open the ventilation unit for service

Always isolate the ventilation unit’s power supply cable 

before you open the inspection door! Wait a few min-

utes before you open the inspection door so that the 

fans are stopped and electrical heaters are cooled.

There are no components inside the electrical box 

that can be serviced by the user. In case of malfunc-

tion, do not restart the ventilation unit before the cause 

of the fault is identified and fixed.

Filters

The ventilation unit must not be operated  without 

filters! Use only original Swegon filters. Find the cor-

rect filter in the section ”Technical data”.

Warranty conditions

Warranty conditions are included in delivery of the 

unit as a separate document.

Declaration of conformity

Link to the declaration of conformity:  

  

casahelp.fi

!

This document is intended for everyone involved in the installation work for or the use of a Swegon CASA ven-

tilation unit. Read this Instructions for Use before you use the ventilation unit. Save the Instructions for Use for 

future use. This document is available in our website. 

The ventilation unit is not designed to be used by children (below 8 years old) or by persons whose senses, physi-

cal or mental capacity or a lack of knowledge and experience limits safe use of the ventilation unit. Such persons 

may use the ventilation unit if supervised by a person who is responsible for their safety, or according to the 

instructions.

Содержание CASA R15H Smart

Страница 1: ...R9HR15H_b_EN t CASA R9 H R15 H SMART Installation commissioning and maintenance instruction TECHNICAL MANUAL...

Страница 2: ...mum automatic boost 9 3 1 4 General notifications 9 3 2 Cooker hood function 10 4 Units external connections 12 4 1 Modbus 12 4 2 Switch inputs DI 13 4 3 Voltage inputs AI 13 4 4 Relay outputs 14 4 5...

Страница 3: ...eze during a power failure and unit freez ing protection works correctly Condensation The surface temperature of the ventilation unit can drop down to 12 C during periods of low outdoor temperature an...

Страница 4: ...n Therefore it s not suitable in houses where unit s extract air humidity may be high i e sauna spa etc Air flow range 100 550 l s Heat exchanger temperature efficiency up to 86 Built in humidity sens...

Страница 5: ...rature is maintained by rotor efficiency control and heating and cooling control In Eco mode maximum heating cooling efficiency is maintained Supply air temperature is controlled only in heating or co...

Страница 6: ...tc 2 1 1 Mounting on the floor The unit should be installed on the floor The device is heavy Make sure that the mounting base will withstand its weight The rear edge of the unit must be at least 50 mm...

Страница 7: ...If the air inside the duct is colder than in the sur roundings the insulation should be protected by a vapour barrier It is important to preserve the tightness of the vapour barrier at the duct penet...

Страница 8: ...tructions for accessories are included in the delivery of the each product 2 6 1 Smart sensor package Smart Sensor package is a combination sensor Humidity sensor SRH Humidity and carbon dioxide senso...

Страница 9: ...9 R9 H R15 H Smart All rights to changes reserved 2020 11 12...

Страница 10: ...aust NOTE If the selection does not correspond the duct installation the unit does not work Adjust the fan control for the operating modes Home Away and Boost so that the planned air flow rates are re...

Страница 11: ...Roof fan 85 In use Commissioning mode Choose commissioning mode The ventilation unit s fans run at the selected speed and functions such as anti freeze protection and heat exchanger by pass are disab...

Страница 12: ...al box Register access Modbus registers defined in registers list are direct ac cessible without password All defined registers are PLC addresses base 1 Most commonly used registers are listed below H...

Страница 13: ...de active when input active 9 Modbus not priority Input status can be read from Modbus 10 Relay control not priority Input status can control relay output 11 Emergency stop resettable Emergency stop a...

Страница 14: ...it is operating in restricted mode 10 Alarm Output is active when any alarm is active 4 5 Voltage outputs AO External devices or systems can be controlled with analog output 0 10 V SEM SEC module has...

Страница 15: ...IO 5 7 GND 8 5 V Out 1 Air handling units external connections 2 Swegon CASA Smart control panel UP1 3 Swegon CASA Smart control panel UP2 4 Connection points on the ventilation unit IO1 IO2 24 V 5 V...

Страница 16: ...and full boost limit Select Use in Away mode to allow boost in Away mode Select Hood boost to open the damper on CASA Smart cooker hood when summer night cooling is active 5 1 Functions The Smart fun...

Страница 17: ...e limits 5 1 3 Cooker hood function The cooker hood function balances the air flows when the cooker hood is used This will help to prevent house nega tive pressure and improves fume extraction capabil...

Страница 18: ...rol The function is available only on models equipped with VOC sensor The function boosts the ventilation step lessly according to air quality level The function can be activated and level selected fr...

Страница 19: ...can be selected Control method Control method Supply control min value Room air Supply controller max value Cooling min setpoint 17 C 17 C 14 C Cooling max setpoint 25 C Setpoint Setpoint away Setpoin...

Страница 20: ...etpoint 5 4 Restoring factory settings Resets all settings made from the control panel except commissioned air flows 5 6 Changing the settings password Settings password can be changed from Settings 1...

Страница 21: ...21 R9 H R15 H Smart All rights to changes reserved 2020 11 12...

Страница 22: ...l The first filter change should therefore be made more often The ventilation unit must not be operated without filters Use only filters recommended by Swegon This is important as filters with exactly...

Страница 23: ...nt are absolute humidity values used by auto humidity control Humidity boost starts when AH is above AH setpoint The control information shows how much different automatic Smart functions boost the ve...

Страница 24: ...alfunction and protective functions to prevent damage Malfunction is indicated with alarm in cooker hood user interface and with digital relay outputs This section contains description of alarms ac ti...

Страница 25: ...ivated The ventilation unit is stopped by the emergency stop function The emergency stop alarm is reset and unit is started when the input is deactivated The emergency stop resettable alarm is reset f...

Страница 26: ...4 Set of filters R0915FS 5 Heat exchanger R000032 6 Rotor motor R000031 7 Door R000097 Accessories Smart control panel SC10 Extension frame for control panel TB00301 Modular cable PMK20 Filter replace...

Страница 27: ...200 400 600 800 1000 0 50 100 150 200 250 300 350 400 450 500 550 600 0 40 80 120 160 200 240 280 SFPv 2 0 100 1 5 70 1 0 Reference airflow Max airflow Min airflow Pressure differential Pa m3 h l s Ai...

Страница 28: ...it T1 Extract air temperature T3 Fresh air temperature T4 Exhaust air temperature T5 Supply air temperature 2 Connector for the Smart control panel 3 External connections See the section Units exter n...

Страница 29: ...T4 Exhaust air temperature T5 Supply air temperature 2 Connector for the Smart control panel 3 External connections See the section Units exter nal connections 4 Rotor motor 5 Proximity sensor 6 Smar...

Страница 30: ...nsion Temperature module accessory SEM CONNECTION UNIT Smart Extension Modbus module accessory HR HEAT EXCHANGER Heat exchanger SD2 DAMPERS Shut off dampers accessory HU AIR HEATER External air heater...

Страница 31: ...ions Duct connections 1 2 3 4 Left hand version Supply air 315 Extract air 315 Outdoor air 315 Exhaust air 315 Right hand version Exhaust air 315 Outdoor air 315 Extract air 315 Supply air 315 1100 40...

Страница 32: ...connectors Smart Extension Cable SEC IO extension cable with Modbus RTU single point connector Humidity switch 117KKH For the Boost operating mode activation Fireplace function switch 102TKC A push bu...

Страница 33: ...me extract 70 Away supply 20 Away extract 40 Boost supply 65 Boost extract 85 Travelling supply 20 Max Smart boost supply 65 Cooker hood function Home state compensation difference 10 Boost state comp...

Страница 34: ...R9 H R15 H Smart 34 All rights to changes reserved 2020 11 12...

Страница 35: ...35 R9 H R15 H Smart All rights to changes reserved 2020 11 12...

Страница 36: ...tal swegon com fi docs TM_R9HR15H_SE Installasjons igangkj rings og vedlikeholdsveiledning https serviceportal swegon com fi docs TM_R9HR15H_NO Installations Inbetriebnahme und Wartungsanleitung https...

Отзывы: