7. Alarms and Troubleshooting

7.1 Alarm indication, cooker hood

If the ventilation unit detects critical alarm, all signal 
lamps on the cooker hood blinks three times every 30 
seconds. 

Following alarms are indicated:

•  Sensor fault
•  Supply air hot
•  Internal overheat
•  Supply air cold 
•  Water radiator freezing protection shutdown
•  Repeating post heater fail
•  Repeating preheater fail

NOTE! The service reminder is indicated with one blink-
ing damper timer signal lamp.

7.2 Alarm indication, control panel

If the ventilation unit detects alarm or info message it is 
indicated in the user panel main screen. The symbol for 
an active alarm is  . The malfunction that has caused 
the alarm is shown in the menu 

(Main menu / Alarm)

Info message   indicates unconfirmed alarms when the 
malfunction is fixed. Info message also indicates the set 
service interval has elapsed. The Info message can be 
reset from the 

Alarm

 menu.

Important

Frost protection function
Ice can form in the heat exchanger during 
periods of cold weather if the extract air is 
humid. Under such conditions, variations in 
the fan speed are normal. 
Under such conditions, small amounts of 
ice can form inside the ventilation unit.

!

!

The unit has inbuild diagnostics for malfunction and protective functions to prevent damage. Malfunction is indicated 
with alarm in cooker hood, user interface and with digital relay outputs. This section contains description of alarms, ac-
tions and troubleshooting. Most of the actions listed in alarm description table is allowed only for qualified person with 
needed permissions.

7.3 Troubleshooting

A ventilation system is composed of several system com-
ponents which all influence how the system operates. A 
malfunction in ventilation performance could be caused 
by any system component or fail in installation, commis-
sioning or service.

The unit warranty is valid during the warranty period 
if unit installation, commissioning and service is done 
according this manual. If despite proper usage there are 
functional disruptions in the ventilation unit, register 
these using the response form at the address www.
casahelp.fi. 

There are also instructions, service videos and frequently 
asked questions on the same website. You directly 
access a web page with model specific instructions by 
reading the QR code on the door of the ventilation unit 
with a smartphone.

If a problem or a fault occurs on the ventilation sys-
tem after the warranty period, contact our network of 
authorised service companies on www.swegonhomeso-
lutions.com, your real estate company’s service division 
or another service company that is fully conversant with 
ventilation repairs.

Troubleshooting and service 
instructions:

www.casahelp.se

Содержание CASA R15H Smart

Страница 1: ...R9HR15H_b_EN t CASA R9 H R15 H SMART Installation commissioning and maintenance instruction TECHNICAL MANUAL...

Страница 2: ...mum automatic boost 9 3 1 4 General notifications 9 3 2 Cooker hood function 10 4 Units external connections 12 4 1 Modbus 12 4 2 Switch inputs DI 13 4 3 Voltage inputs AI 13 4 4 Relay outputs 14 4 5...

Страница 3: ...eze during a power failure and unit freez ing protection works correctly Condensation The surface temperature of the ventilation unit can drop down to 12 C during periods of low outdoor temperature an...

Страница 4: ...n Therefore it s not suitable in houses where unit s extract air humidity may be high i e sauna spa etc Air flow range 100 550 l s Heat exchanger temperature efficiency up to 86 Built in humidity sens...

Страница 5: ...rature is maintained by rotor efficiency control and heating and cooling control In Eco mode maximum heating cooling efficiency is maintained Supply air temperature is controlled only in heating or co...

Страница 6: ...tc 2 1 1 Mounting on the floor The unit should be installed on the floor The device is heavy Make sure that the mounting base will withstand its weight The rear edge of the unit must be at least 50 mm...

Страница 7: ...If the air inside the duct is colder than in the sur roundings the insulation should be protected by a vapour barrier It is important to preserve the tightness of the vapour barrier at the duct penet...

Страница 8: ...tructions for accessories are included in the delivery of the each product 2 6 1 Smart sensor package Smart Sensor package is a combination sensor Humidity sensor SRH Humidity and carbon dioxide senso...

Страница 9: ...9 R9 H R15 H Smart All rights to changes reserved 2020 11 12...

Страница 10: ...aust NOTE If the selection does not correspond the duct installation the unit does not work Adjust the fan control for the operating modes Home Away and Boost so that the planned air flow rates are re...

Страница 11: ...Roof fan 85 In use Commissioning mode Choose commissioning mode The ventilation unit s fans run at the selected speed and functions such as anti freeze protection and heat exchanger by pass are disab...

Страница 12: ...al box Register access Modbus registers defined in registers list are direct ac cessible without password All defined registers are PLC addresses base 1 Most commonly used registers are listed below H...

Страница 13: ...de active when input active 9 Modbus not priority Input status can be read from Modbus 10 Relay control not priority Input status can control relay output 11 Emergency stop resettable Emergency stop a...

Страница 14: ...it is operating in restricted mode 10 Alarm Output is active when any alarm is active 4 5 Voltage outputs AO External devices or systems can be controlled with analog output 0 10 V SEM SEC module has...

Страница 15: ...IO 5 7 GND 8 5 V Out 1 Air handling units external connections 2 Swegon CASA Smart control panel UP1 3 Swegon CASA Smart control panel UP2 4 Connection points on the ventilation unit IO1 IO2 24 V 5 V...

Страница 16: ...and full boost limit Select Use in Away mode to allow boost in Away mode Select Hood boost to open the damper on CASA Smart cooker hood when summer night cooling is active 5 1 Functions The Smart fun...

Страница 17: ...e limits 5 1 3 Cooker hood function The cooker hood function balances the air flows when the cooker hood is used This will help to prevent house nega tive pressure and improves fume extraction capabil...

Страница 18: ...rol The function is available only on models equipped with VOC sensor The function boosts the ventilation step lessly according to air quality level The function can be activated and level selected fr...

Страница 19: ...can be selected Control method Control method Supply control min value Room air Supply controller max value Cooling min setpoint 17 C 17 C 14 C Cooling max setpoint 25 C Setpoint Setpoint away Setpoin...

Страница 20: ...etpoint 5 4 Restoring factory settings Resets all settings made from the control panel except commissioned air flows 5 6 Changing the settings password Settings password can be changed from Settings 1...

Страница 21: ...21 R9 H R15 H Smart All rights to changes reserved 2020 11 12...

Страница 22: ...l The first filter change should therefore be made more often The ventilation unit must not be operated without filters Use only filters recommended by Swegon This is important as filters with exactly...

Страница 23: ...nt are absolute humidity values used by auto humidity control Humidity boost starts when AH is above AH setpoint The control information shows how much different automatic Smart functions boost the ve...

Страница 24: ...alfunction and protective functions to prevent damage Malfunction is indicated with alarm in cooker hood user interface and with digital relay outputs This section contains description of alarms ac ti...

Страница 25: ...ivated The ventilation unit is stopped by the emergency stop function The emergency stop alarm is reset and unit is started when the input is deactivated The emergency stop resettable alarm is reset f...

Страница 26: ...4 Set of filters R0915FS 5 Heat exchanger R000032 6 Rotor motor R000031 7 Door R000097 Accessories Smart control panel SC10 Extension frame for control panel TB00301 Modular cable PMK20 Filter replace...

Страница 27: ...200 400 600 800 1000 0 50 100 150 200 250 300 350 400 450 500 550 600 0 40 80 120 160 200 240 280 SFPv 2 0 100 1 5 70 1 0 Reference airflow Max airflow Min airflow Pressure differential Pa m3 h l s Ai...

Страница 28: ...it T1 Extract air temperature T3 Fresh air temperature T4 Exhaust air temperature T5 Supply air temperature 2 Connector for the Smart control panel 3 External connections See the section Units exter n...

Страница 29: ...T4 Exhaust air temperature T5 Supply air temperature 2 Connector for the Smart control panel 3 External connections See the section Units exter nal connections 4 Rotor motor 5 Proximity sensor 6 Smar...

Страница 30: ...nsion Temperature module accessory SEM CONNECTION UNIT Smart Extension Modbus module accessory HR HEAT EXCHANGER Heat exchanger SD2 DAMPERS Shut off dampers accessory HU AIR HEATER External air heater...

Страница 31: ...ions Duct connections 1 2 3 4 Left hand version Supply air 315 Extract air 315 Outdoor air 315 Exhaust air 315 Right hand version Exhaust air 315 Outdoor air 315 Extract air 315 Supply air 315 1100 40...

Страница 32: ...connectors Smart Extension Cable SEC IO extension cable with Modbus RTU single point connector Humidity switch 117KKH For the Boost operating mode activation Fireplace function switch 102TKC A push bu...

Страница 33: ...me extract 70 Away supply 20 Away extract 40 Boost supply 65 Boost extract 85 Travelling supply 20 Max Smart boost supply 65 Cooker hood function Home state compensation difference 10 Boost state comp...

Страница 34: ...R9 H R15 H Smart 34 All rights to changes reserved 2020 11 12...

Страница 35: ...35 R9 H R15 H Smart All rights to changes reserved 2020 11 12...

Страница 36: ...tal swegon com fi docs TM_R9HR15H_SE Installasjons igangkj rings og vedlikeholdsveiledning https serviceportal swegon com fi docs TM_R9HR15H_NO Installations Inbetriebnahme und Wartungsanleitung https...

Отзывы: