5.1.7 Automatic humidity control

The function is available only on models equipped with 
a humidity sensor. The function boosts the ventilation 
steplessly by demand. For example if humidity in the 
house rises due to showering. 

If the humidity level (RH) remains above 60 % for a long 
period, we recommend that the ventilation is boosted 
and the humidity source is investigated.

The function can be activated and level selected from the 

Settings/(1234)/Smart Functions/Auto RH control

 menu or 

from 

Smart shortcuts

 menu.

Auto RH control

Level

Boost limit
Full boost limit

Boost delay

30 % + RH

Boost during delay

5 %

5 % + RH

User

0 min

The user can select preset boost levels in the shortcut 
menu (

off, low, normal, high 

or

 full)

. The preset levels 

define 

Boost limit

 and 

Full boost limit

. To define these 

limits manually select “

User

” level.

The ventilation is boosted steplessly when the humidity 
has risen from average 

Boost limit

 defined amount. The 

maximum ventilation boost is reached when the humidi-
ty has risen the 

Full boost limit

 defined amount from the 

average.   

The boost can be increased by decreasing the 

Full boost 

limit

.

The boost start can be delayed with 

Boost delay

. (The 

delay is started when humidity is stabilized after show-
er or sauna.) Fixed 

boost

 level 

during the delay

 can be 

defined.   

NOTE! The function is only visible if the sensor has been 
detected. The function is enabled automatically when 
the sensor is detected. 
NOTE! Humidity is measured from extract air and it 
represents average of the whole house.

5.1.8 Automatic air quality control

The function is available only on models equipped with 
VOC sensor. The function boosts the ventilation step-
lessly according to air quality level.

The function can be activated and level selected from 
the 

Settings/(1234)/Smart Functions/Auto Air Quality 

control

 menu or from 

Smart shortcuts

 menu. 

Auto Air Quality control

Level

AQ now
Boost limit

800 ppm

750 ppm

User

Full boost limit

1500 ppm

The user can select preset boost levels in the shortcut 
menu (

off, low, normal, high 

or

 full)

. The preset levels 

define 

Boost limit

 and 

Full boost limit

. To define these 

limits manually select “

User

” level.

The ventilation is boosted steplessly when the VOC has 
risen over 

Boost limit

. The maximum ventilation boost is 

reached when the VOC has risen to the 

Full boost limit

.  

Appropriate values can be established based on the 

AQ 

now

 value shown in the menu.  

The boost can be increased by decreasing the 

Full boost limit

.

NOTE! The function is only visible if the sensor has been 
detected. 
NOTE! VOC measurement reacts on air quality changes 
and absolute value can vary highly but by selecting suit-
able boost level the function works effectively. 

5.1.9 Weekly program

The ventilation unit’s functions can be controlled with a 
maximum of four different weekly programs.

Operating mode and temperature for each program can 
be selected. Time limits and weekdays for the programs 
can be selected. 

Smart boost can be disabled for a desired time, e.g. 
during the night by selecting Silent mode.

Weekly programs can be enabled and settings can be 
made from 

Main menu/Weekly programs 

menu.

NOTE! Program 1 has highest priority and program 4 
lowest. Highest priority overrides other active programs.

Program 1

State

17°C

Temperature
Start time
Stop time
Monday

Tuesday
Wednesday

Thursday
Friday
Saturday

Away

Sunday

07:00
16:00

Содержание CASA R15H Smart

Страница 1: ...R9HR15H_b_EN t CASA R9 H R15 H SMART Installation commissioning and maintenance instruction TECHNICAL MANUAL...

Страница 2: ...mum automatic boost 9 3 1 4 General notifications 9 3 2 Cooker hood function 10 4 Units external connections 12 4 1 Modbus 12 4 2 Switch inputs DI 13 4 3 Voltage inputs AI 13 4 4 Relay outputs 14 4 5...

Страница 3: ...eze during a power failure and unit freez ing protection works correctly Condensation The surface temperature of the ventilation unit can drop down to 12 C during periods of low outdoor temperature an...

Страница 4: ...n Therefore it s not suitable in houses where unit s extract air humidity may be high i e sauna spa etc Air flow range 100 550 l s Heat exchanger temperature efficiency up to 86 Built in humidity sens...

Страница 5: ...rature is maintained by rotor efficiency control and heating and cooling control In Eco mode maximum heating cooling efficiency is maintained Supply air temperature is controlled only in heating or co...

Страница 6: ...tc 2 1 1 Mounting on the floor The unit should be installed on the floor The device is heavy Make sure that the mounting base will withstand its weight The rear edge of the unit must be at least 50 mm...

Страница 7: ...If the air inside the duct is colder than in the sur roundings the insulation should be protected by a vapour barrier It is important to preserve the tightness of the vapour barrier at the duct penet...

Страница 8: ...tructions for accessories are included in the delivery of the each product 2 6 1 Smart sensor package Smart Sensor package is a combination sensor Humidity sensor SRH Humidity and carbon dioxide senso...

Страница 9: ...9 R9 H R15 H Smart All rights to changes reserved 2020 11 12...

Страница 10: ...aust NOTE If the selection does not correspond the duct installation the unit does not work Adjust the fan control for the operating modes Home Away and Boost so that the planned air flow rates are re...

Страница 11: ...Roof fan 85 In use Commissioning mode Choose commissioning mode The ventilation unit s fans run at the selected speed and functions such as anti freeze protection and heat exchanger by pass are disab...

Страница 12: ...al box Register access Modbus registers defined in registers list are direct ac cessible without password All defined registers are PLC addresses base 1 Most commonly used registers are listed below H...

Страница 13: ...de active when input active 9 Modbus not priority Input status can be read from Modbus 10 Relay control not priority Input status can control relay output 11 Emergency stop resettable Emergency stop a...

Страница 14: ...it is operating in restricted mode 10 Alarm Output is active when any alarm is active 4 5 Voltage outputs AO External devices or systems can be controlled with analog output 0 10 V SEM SEC module has...

Страница 15: ...IO 5 7 GND 8 5 V Out 1 Air handling units external connections 2 Swegon CASA Smart control panel UP1 3 Swegon CASA Smart control panel UP2 4 Connection points on the ventilation unit IO1 IO2 24 V 5 V...

Страница 16: ...and full boost limit Select Use in Away mode to allow boost in Away mode Select Hood boost to open the damper on CASA Smart cooker hood when summer night cooling is active 5 1 Functions The Smart fun...

Страница 17: ...e limits 5 1 3 Cooker hood function The cooker hood function balances the air flows when the cooker hood is used This will help to prevent house nega tive pressure and improves fume extraction capabil...

Страница 18: ...rol The function is available only on models equipped with VOC sensor The function boosts the ventilation step lessly according to air quality level The function can be activated and level selected fr...

Страница 19: ...can be selected Control method Control method Supply control min value Room air Supply controller max value Cooling min setpoint 17 C 17 C 14 C Cooling max setpoint 25 C Setpoint Setpoint away Setpoin...

Страница 20: ...etpoint 5 4 Restoring factory settings Resets all settings made from the control panel except commissioned air flows 5 6 Changing the settings password Settings password can be changed from Settings 1...

Страница 21: ...21 R9 H R15 H Smart All rights to changes reserved 2020 11 12...

Страница 22: ...l The first filter change should therefore be made more often The ventilation unit must not be operated without filters Use only filters recommended by Swegon This is important as filters with exactly...

Страница 23: ...nt are absolute humidity values used by auto humidity control Humidity boost starts when AH is above AH setpoint The control information shows how much different automatic Smart functions boost the ve...

Страница 24: ...alfunction and protective functions to prevent damage Malfunction is indicated with alarm in cooker hood user interface and with digital relay outputs This section contains description of alarms ac ti...

Страница 25: ...ivated The ventilation unit is stopped by the emergency stop function The emergency stop alarm is reset and unit is started when the input is deactivated The emergency stop resettable alarm is reset f...

Страница 26: ...4 Set of filters R0915FS 5 Heat exchanger R000032 6 Rotor motor R000031 7 Door R000097 Accessories Smart control panel SC10 Extension frame for control panel TB00301 Modular cable PMK20 Filter replace...

Страница 27: ...200 400 600 800 1000 0 50 100 150 200 250 300 350 400 450 500 550 600 0 40 80 120 160 200 240 280 SFPv 2 0 100 1 5 70 1 0 Reference airflow Max airflow Min airflow Pressure differential Pa m3 h l s Ai...

Страница 28: ...it T1 Extract air temperature T3 Fresh air temperature T4 Exhaust air temperature T5 Supply air temperature 2 Connector for the Smart control panel 3 External connections See the section Units exter n...

Страница 29: ...T4 Exhaust air temperature T5 Supply air temperature 2 Connector for the Smart control panel 3 External connections See the section Units exter nal connections 4 Rotor motor 5 Proximity sensor 6 Smar...

Страница 30: ...nsion Temperature module accessory SEM CONNECTION UNIT Smart Extension Modbus module accessory HR HEAT EXCHANGER Heat exchanger SD2 DAMPERS Shut off dampers accessory HU AIR HEATER External air heater...

Страница 31: ...ions Duct connections 1 2 3 4 Left hand version Supply air 315 Extract air 315 Outdoor air 315 Exhaust air 315 Right hand version Exhaust air 315 Outdoor air 315 Extract air 315 Supply air 315 1100 40...

Страница 32: ...connectors Smart Extension Cable SEC IO extension cable with Modbus RTU single point connector Humidity switch 117KKH For the Boost operating mode activation Fireplace function switch 102TKC A push bu...

Страница 33: ...me extract 70 Away supply 20 Away extract 40 Boost supply 65 Boost extract 85 Travelling supply 20 Max Smart boost supply 65 Cooker hood function Home state compensation difference 10 Boost state comp...

Страница 34: ...R9 H R15 H Smart 34 All rights to changes reserved 2020 11 12...

Страница 35: ...35 R9 H R15 H Smart All rights to changes reserved 2020 11 12...

Страница 36: ...tal swegon com fi docs TM_R9HR15H_SE Installasjons igangkj rings og vedlikeholdsveiledning https serviceportal swegon com fi docs TM_R9HR15H_NO Installations Inbetriebnahme und Wartungsanleitung https...

Отзывы: